4-8
Operation Within SEL-2030
Date Code 980420
SEL-2711 Instruction Manual
**>>
STATUS<ENTER>
STATUS<ENTER>
Date: 10/06/97 Time: 15:07:11
FID=SEL-2030-X013-V0-D970922 FID=SLBT-2030-XRAM-V0-970314
SELF-TESTS
RAM SRAM CODE ARCH EEPROM P.S. SET BATTERY
512 kb 256 kb OK Absent OK OK OK OK
IRIG-B Input: Absent
I/O Board: Absent
Port Status Success Rate SET M Database Delays
1 Active None
2 Inactive 87% None D1 D2 D3 D4
3 Inactive None
4 Inactive None
5 Inactive None
6 Inactive None
7 Inactive None
8 Inactive None
9 Inactive None
10 Inactive None
11 Inactive None
12 Inactive None
13 Inactive None
14 Inactive None
15 Inactive None
16 Inactive None
18 Normal(100h) NORM Running
F Active 98% None
Once the status has been confirmed, the SEL-2711 address must be set, and the three relay ports
must be configured to capture the data of interest. The following screens illustrate this process.
*>>
SET P 18<ENTER>
SET P 18<ENTER>
Port communications settings for Port 18
Modbus Plus node Address (1-64)
ADDRESS = 1 ?
12<ENTER>
12<ENTER>
Map Input Registers to Holding Registers(Y/N)
MAP_IR = "N"
?
END<ENTER>
END<ENTER>
ADDRESS = 12
MAP_IR = "N"
PATH_1 = "00.00.00.00.00"
COIL_1 = 1
PATH_2 = "00.00.00.00.00"
COIL_2 = 1
PATH_3 = "00.00.00.00.00"
COIL_3 = 1
PATH_4 = "00.00.00.00.00"
COIL_4 = 1
PATH_5 = "00.00.00.00.00"
COIL_5 = 1
PATH_6 = "00.00.00.00.00"
COIL_6 = 1
PATH_7 = "00.00.00.00.00"
COIL_7 = 1
(continued on next page)