SEL-251, -2, -3 Instruction Manual
EVENT n
EVENT displays an event report. Type
EVENT n <ENTER>
to display an event report for the
nth event. The parameter n ranges from 1 for the newest event through 12 for the oldest event
stored in relay memory. If n is not specified, the default value is 1 and the relay displays the
newest event report.
You can control transmissions from the relay with the following keystrokes:
•
<CTRL>S
Pause transmission
•
<CTRL>Q
Continue transmission
•
<CTRL>X
Terminate transmission
The following incidents clear the event buffers:
•
Control power interruption
•
Changing any relay setting via the SET commands
•
Changing any relay setting group via the COPY command
Switching setting groups does not clear the buffers.
All event data are lost when event buffers are cleared. If an event buffer is empty when you
request an event, the relay returns an error message:
=>EVENT 12 <ENTER>
EVENT 12 <ENTER>
Invalid event
=>
Section 4: Event Reporting
explains the generation and analysis of event reports.
HISTORY
HISTORY displays the date, time, event type, reclosing relay shot, maximum phase current,
enabled setting group, and fault type targets for each of the last twelve events. If the event is a
fault, the fault location also appears. The full eleven-cycle event reports also include this
information (
EVENT n
to display).
=>HISTORY <ENTER>
HISTORY <ENTER>
Example 21.6 kV distribution feeder Date: 04/01/93 Time: 09:11:27
# DATE TIME EVENT LOCAT SHOT CURR GROUP TARGETS
1 4/2/91 01:36:59.070 AG T 2.43 0 2798 2 INSTAQN
2 3/17/91 08:07:40.129 CG T 3.52 1 2361 3 INSTCQN
3 3/17/91 08:07:35.133 CG T 3.51 0 2364 3 INSTCQN
4 3/15/91 01:07:35.862 TRIG 0 345 1
5
6
7
8
9
10
11
12
=>