Date Code 20000421
Maintenance and Testing
7-19
SEL-251, -2, -3 Instruction Manual
2. Using the SET G command (G signifies the global setting group: settings
common to all groups), enter additional example settings:
.
.
.
TDUR
= 4
trip duration timer (cycles)
.
.
.
IN3
= RE
reclose enable
IN4
= DC
direct close
IN5
= 52A
circuit breaker auxiliary
The choice of inputs IN3, IN4, and IN5 is for demonstration purposes only.
3. After the settings are made, energize IN3 (IN3 = RE) to enable the reclosing
relay.
Note that if IN3 is de-energized, the reclosing relay goes to lockout. The relay
illuminates the front panel LO (lockout) LED and asserts the A3 output contact
(A3 =
79LO
).
4. Note that the front panel RS (reset) and LO (lockout) LEDs follow the
79RS
and
79LO
Relay Word bits, respectively.
Reclosing Relay Reset Interval Timer Test
Purpose:
Verify the reclosing relay reset interval timer accuracy.
Method:
1. Enter the settings in the preceding
Reclosing Relay Tests Setup
if you haven't
already.
2. Open the circuit breaker simulator manually or via the OPEN command. With
the circuit breaker simulator open, IN5 is de-energized (IN5 = 52A), the front
panel LO (lockout) LED is illuminated, and the A3 output contact is asserted
(A3 =
79LO
).
3. Connect the circuit breaker simulator output to an external timer. When the
circuit breaker simulator output is asserted (indicating that the circuit breaker has
closed), the external timer starts.
4. Connect the A1 output contact to stop the same external timer. The external
timer should stop when the A1 output contact asserts (A1 =
79RS
), indicating
that the reclosing relay is in the reset state. When the circuit breaker remains
closed for the duration of the reset interval time (79RST = 1800 cycles), the
reclosing relay goes into the reset state.
5. Execute the CLOSE Command or energize the IN4 input (IN4 = DC; direct
close) to cause CLOSE output contact assertion. When the circuit breaker
simulator output asserts (IN5 = 52A energized), the external and reset interval