Operation
28
02.00 | SWS-L | Assembly and operating manual | en | 0389037
SWS-L-210-510:
Turn the Lock output off (for double solenoid
valve versions).
SWS-L-210:
Issue the Unlock output.
/ SWS-L-310, 510:
Issue the
Unlock command.
/ SWS-L-1210:
Issue the Unlatch output. Air is
supplied to the locking mechanism to uncouple the SWS-L.
A sufficient delay must be programmed between the Unlock out-
put being activated and reading the state of the Lock/Unlock sig-
nals, so that the coupling process is completed before checking the
Locked state.
Read the Locked and Unlocked signals.
The Unlock signal should read “on” (true) and the Lock signal
should read “off” (false). Any other condition indicates a problem
and the robot program should be halted.
Once the Lock and Unlock signals are verified to be in the proper
state the SWK-L may be moved away from the SWA-L in the axial
direction.
SWS-L-1210
: Check to verify that the RTLs are all “off” (false) after
the SWK-L moves away from the SWA-L.
The robot and SWK-L can now proceed to another SWA-Lfor coup-
ling and subsequent operations.