Installation manual
PSC1-C-10 Installation manual V2.6
Page 51 of 173
Version: 57E
Type of
sensor /
input
element
Input
Tests that can be
configured /
operative tests
Achievab
le PL
accordin
g to EN
ISO
13849-1
Fault exclusion for
input element
Condition for input element
Cro
ss
-c
ircu
it te
st
W
ith
ti
me
mo
n
ito
ri
n
g
Star
t te
st
Cyc
lic
te
st i
n
o
p
erat
io
n
Dual-
channel
serial
I00..I04
I08..I13
d
Short-circuit on the
input/signal wire
Stuck / positive opening
Connection in the switch cabinet
or protected laying
MTTF
d
= medium
O
O
e
Short-circuit on the
input/signal wire
Connection in the switch cabinet
or protected laying
MTTF
d
= high
All
O
O
d
Short-circuit on the
input/signal wire
Connection in the switch cabinet
or protected laying
MTTF
d
= medium
X
O
O
e
MTTF
d
= high
Options:
X:
Diagnostic measure activated
O:
At least 1 diagnostic measure activated
Содержание PSC1-C-10 Series
Страница 1: ...Installation manual for PSC1 modules Series PSC1 C 10 PSC1 C 10 SDMx PSC1 E 3x...
Страница 98: ...Installation manual PSC1 C 10 Installation manual V2 6 Page 98 of 173 Version 57E 2 I 09 3 I 10 4 I 11...
Страница 140: ...Installation manual PSC1 C 10 Installation manual V2 6 Page 140 of 173 Version 57E...
Страница 153: ...Installation manual PSC1 C 10 Installation manual V2 6 Page 153 of 173 Version 57E Example for a hazard analysis...