background image

www.schischek.com

Description size S

The new RedMax actuators are a revolution for safety, fire and shut-off
dampers, VAV systems, ball valves, throttle valves and other motorized
applications for HVAC systems, in chemical, pharmaceutical, industrial
and Offshore-/Onshore plants, for use in EEx-areas zone 2 (gas) and
zone 22 (dust).
Highest protection class (ATEX) and IP 66 protection, small dimensions,
only 3,5 kg weight, universal functions and technical data, an integrated
heater and an optional stainless steel housing guarantee safe operation
even under difficult environmental conditions. High quality brushless
motors guarantee long life.
All actuators are programmable and adjustable on site. Special tools
or equipment are not required. 5 motor running times and 2 torques as

well as 2 spring return times - according to the actuator type - are

selectable or adjustable on site. The integrated universal  power supply
is self adaptable to input voltages in the range of 24 to 230 VAC / DC.
The  actuators  are  100%  overload  protected  and  self  locking.

RedMax-...-BF

 actuators are equipped with spring return fail safe function,

with integrated aux. switches for end position indication and an intrinsic
safe circuit to connect an external passive potential free thermostat.
Standard shaft connection is a double squared direct coupling with
12 x 12 mm.
Different accessories are available to adapt aux. switches, terminal
boxes  or  adaptations  for  ball  valves  and  throttle  valves.

Application

Highlights

Firedamper

Damper

Ball valve, Throttle valve

Schischek GmbH 

Germany D-90579 Langenzenn, Mühlsteig 45, Gewerbegebiet V, Tel. ++49 (0)9101-90810, Fax  ++49 (0)9101-908177, Email [email protected]

RedMax-5.10-BF

RedMax-   15-BF

RedMax -   ...-BF  - VA

RedMax -   ...-BF  - CT

E X P L O S I O N P R O O F

Type

Torque

Supply

Motor running time 

Spring return

Control mode Additional features

Wiring diagram

RedMax-  5.10 - BF   5 Nm & 10 Nm

24..230VAC/DC 3/15/30/60/120 sec. at 90° 3 or 10 sec. at 90° On-off, 3-pos 2 contacts (5/85° ) + EEx-i circuit   SB 7.0/7.1

RedMax-     15 - BF 15 Nm

24..230VAC/DC 3/15/30/60/120 sec. at 90° 3 or 10 sec. at 90° On-off, 3-pos 2 contacts (5/85° ) + EEx-i circuit   SB 7.0/7.1

RedMax- ... - VA

Type as above but with stainless steel housing (AISI 316) for aggressive ambient (12x12 shaft, shaft manual override, cable glands and hollow rivet nickel-plated)

RedMax- ... - CT

Type as above but with Al housing and amercoat painting (12x12 shaft connenction, shaft manual override, cable glands and hollow rivet nickel-plated)

Electrical, explosion proof rotary actuators - size S
On-off / 3-pos , 24..230 VAC/DC,  95° angle of rotation, potential free contacts, EEx-i circuit
5/10 Nm - 15/30 Nm without and 5/10 Nm - 15 Nm with safety operation (spring return)
PTB-tested in acc. with ATEX RL 94/9/EG for zone 2, 22.

u

For all type of gas, mixtures, vapours and dust for use in zone 2 and 22

u

Universal supply unit from 24 to 230 V - AC/DC

u

EEx-i circuit for directly connection of a passive potential free safety thermostat

u

2 integral aux. switches , switching at 5° and 85° angle of rotation

u

5 different motor running times (3-15-30-60-120 sec./90°), adjustable on site

u

2 different spring return running times (3-10 sec./90°), selectable on site

u

On-off and 3-pos control with spring return function

u

5 - 10 - 15 Nm  actuators in the same size (S)

u

100 %  overload protected, Self locking

u

Compact design and small dimension  (l x w x h = 210 x 95 x 80 mm)

u

Direct coupling to the damper shaft with double-squared connection 12 x 12 mm

u

95° Angle of rotation incl. 5° pre-tention

u

Robust aluminium  housing (optional stainless steel or amercoat painting)

u

IP 66 protection

u

Simple manual override i preparation for comfortable manual override

u

Gear made of stainless steel and sinter metal

u

Only 3,5 Kg weight

u

Integral heater for ambient temperatures down to -40°C

u

Integral safety temperature sensor

u

Integral equipment for manual adjustment (push button, lamp, switch)

u

Preparation for adaptable aux. switches type RedSwitch

u

Range of accessories

RedMax - Revolution

Compact - Easy installation - Universal - Cost effective - Safe

Subject to change

Содержание RedMax-...-BF-CT

Страница 1: ...or 10 sec at 90 On off 3 pos 2 contacts 5 85 EEx i circuit SB 7 0 7 1 RedMax 15 BF 15 Nm 24 230VAC DC 3 15 30 60 120 sec at 90 3 or 10 sec at 90 On off 3 pos 2 contacts 5 85 EEx i circuit SB 7 0 7 1 RedMax VA Type as above but with stainless steel housing AISI 316 for aggressive ambient 12x12 shaft shaft manual override cable glands and hollow rivet nickel plated RedMax CT Type as above but with A...

Страница 2: ...on Axle of the actuator double squared 12 x 12 mm direct coupling 100 overload protected and 100 self locking up to 15 Nm Electrical connection cable 1 m diameter of wires 0 5 mm for connection inside hazardous areas an terminal box is required Diameter of cable Æ 9 6 mm Æ 6 2 mm Cable gland M16 x 1 5 standard cable and wire entries are integral part of explosions proof encapsulation tested acc to...

Страница 3: ...same like supply of the actuator on same fuse 5 8 9 10 85 11 1 2 3 PE heater 5 24 230 VAC DC FireSafe 4 Attention If you use this type of wiring the heater does not work in case of open contact a b EEx i intrinsic safe data If 3 sec mode is selected the self adju stment ofAngle of rotation must be started and operation mode of max 10 ED must be guaranteed Never use actuators in this mode without e...

Страница 4: ...rection of the spring return function by left right mounting In acc to the actuator type 5 different motor running times and 2 different spring return running times can be selscted on site The integral heater is for ambient temperatures down to 40 C C Working with 3 sec motor running time See extra information EL D 3 pos control mode See extra information EL E Spring return Spring return function ...

Страница 5: ...it length in m Factor 0 0714 drive specific factor Vmm m based on the electrical conductivity of electrolytic copper with a coefficient of 56m Wmm pannel length L m terminal box actuator line cross section A mm voltage Uv V Formula for max cable length L at cable cross section A L A l Uv 18V 0 0714 Formula of needed cable cross section A at a cable length of L A 0 0714 l L Uv 18V The EL data sheet...

Страница 6: ...ate actuator in the 3 sec mode without an outside load of min 3 Nm Engaging 1 wire On Off controlls in the 3 sec modus with spring return the ac tuator can only be operated with 1 On Off function per minute otherwise electronics will be liable to overheating Attention If you use this type of wiring the heater does not work in case of open contact Attention If you use this type of wiring the heater...

Страница 7: ...se function bridge 3 4 reverse input and output signals Selection of running time for spring return Standard wiring spring return in 10 Sek Additional wiring terminal 5 spring return in 3 Sek B A B A B A B A SB 5 0 SB 5 1 SB 5 3 SB 5 2 I Operation with 3 sec motor running time mode While operating the ExMax actuator in 3 sec mode following parameters have to be aligned 1 Maximum cyclic duration 10...

Страница 8: ...tor sits diagonally on the squared damper shaft l The actuators have an angle of rotation of 95 inclusive 5 pre tention While assembling the pre loading was not considered l Dismount actuator of the damper use the enclosed socket wrench to draw up approx 5 over the hand operated control device before remounting on the damper shaft Consider additional information ME of the assembly instructions 09 ...

Страница 9: ... inl radius of bend for the cable All ExMax and RedMax actuators are equipped with a 10 position switch a push button and a multicolor LED for calibration These control elements are to be found cable laterally behind the two middle sectioned dummy plugs For operation these must be removed The calibration can be achieved despide lining up tension at the actuator The explosion prevention is not impa...

Страница 10: ...with drill template on the damper or to a mounting bracket 2 Adjust drive shaft of the actuator with the socket wrench that the drive stands perpendicular to the damper before pluging actuator on to the damper shaft 3 Plug actuator onto damper shaft and fix diagonally with 2 screws 4 Remove the socket wrench 5 Pivot and tighten the remaining screws Note the drive shaft is selflockingly produced an...

Страница 11: ...ire dampers Mounting to a ball valve Mounting to a butterfly valve Fire damper Assembly It is to be considered that the actuators have a total angle of rotation of approx 95 in order to realize a pre tention on the damper Therefore thr actuator sits tilted on the damper shaft In order to prevent this and to assure pre tention to the damper the driving shaft has to be adjusted mechanically before c...

Страница 12: ...ssory to the actuator Mounting of terminal boxes type ExBox RedBox via mounting bracket type MKK S to the actuator accessory 1 Put the squared connection part to the actuator then mount ExSwitch RedSwitch and fix it with 4 screws 2 ExMax RedMax with mounted ExSwitch RedSwitch 4 x 1 Screw mounting bracket MKK S to the actuator A then terminal box to the mounting bracket B schrauben 2 x 2 x B A Moun...