   burner disturbance table

disturbance

cause

burner does not start

power supply interrupted
boiler thermostats set incorrectly
safety thermostat has tripped
oil preheater does not switch through

burner goes to malfunc-

tion during pre-ventilation

extraneous light
ignition cable influences sensor cable

burner running� but no 

flame formation

normal operating sequence
no ignition

solenoid valve does not open
air monitor does not switch
no fan function
air pressure switch defective
clutch sheared off
no oil supply
Oil pump defective

burner starts� but flame 

goes out after 

Switching off the ignition

NO

X

 lowered too far

fan speed too high

burner goes to fault 

despite stable flame or 

to fault after safety time 

has elapsed

flame monitoring defective or dirty

automatic burner control does not 

take over
NO

X

 zu weit abgesenkt�  Flamme ist 

zu glasig

flame burns long and 

yellow from the flame 

tube

nozzle dirty� nozzle splashes at an 

angle
air in the oil supply� flame pulsating

nozzle penetrates too much oil 

fan speed too low

mechanical noises

air in the oil pump 

engine Bearing damage

burner goes into 

malfunction at irregular 

intervals

coupling defective
oil pump or engine running heavily

 

ignition transformer stops
IRD no longer takes over

relief

check fuse
set thermostats correctly
press the release button
replace oil preheater
check KLC
route sensor cable differently
nozzle defective - replace
check ignition system� replace defective parts if 

necessary
replace solenoid coil or complete solenoid valve
check hose connection
check connection
change
replace coupling
open oil valves� check oil level in tank� clean filter
replace oil pump
advance nozzle assembly by means of adjusting 

screw
reduce blower fan speed�

recalibrate burner
check flame monitoring for correct installation or 

sensitivity adjustment� 

clean flame monitoring replace if necessary
check connections� replace if necessary

reciprocate with the help of the nozzle holder

close adjustment
replace nozzle

check oil supply� ensure bubble-free� clean oil

check nozzle size according to setting table� replace 

if necessary check pump pressure
Increase speed� calibrate burner
check oil line and filter� seal or replace if necessary 

replace motor or rolling bearing
replace coupling
check oil pump or motor for pressure point� replace 

defective part

check capacitor (+/- 5 %)
replace ignition transformer
check setting� replace IRD

13

 

 

 

 

 

 

 

 

Содержание heater to move

Страница 1: ...revised 06 2019 innovative heat systems user s instructions heater to move MH 5 MH 10...

Страница 2: ...eration over the boiler control field are very efficient and environmentally friendly We hope that how to use the heating system and all of its functions are explained to you to your full satisfaction...

Страница 3: ...ta boiler boiler dimensions warning and safety signs definition warning and safety signs general operating instructions transport storage and assembly commissioning filling and venting boiler setting...

Страница 4: ...d with SCHEER precision spring technology in the nozzle block Blautherm DUO BE burner type Blaubrenner with start level fuel Heating oil EL according to DIN 51603 power kW 17 oil pump AL V 35C oil noz...

Страница 5: ...put kW 19 CE label according to oil equipment directive CE 0045CMKD 2340 Permissible flow temperature safety temperature C 95 Permissible operating pressure bar 3 heating gas side resistance mbar 0 30...

Страница 6: ...Regelung Verbrennungsschutz Abgasrohr Vorlauf R cklaufanschluss Bef ll und Ablasshahn Leergewicht gesamt 110 Kg Ausdehnungsgef Rahmenkonstruktion aus 30x30 Vierkantrohr Elektronische Regelung Kesselu...

Страница 7: ...R Death or serious injury by suffocation see also next page classification of the signal word according to ANSI Z535 4 signal word identification of hazard NOTICE Notice this header is preferred to ad...

Страница 8: ...The heating system must be turned off before you get fuel at gas stations The year of the first start up must be permanently marked on the identification plate Make sure all existing shut off valves o...

Страница 9: ...ARNING To prevent misuse and the associated dangers make your old equipment unusable before disposal There for disconnect the device from the power supply and remove the power cable from the device To...

Страница 10: ...se if necessary filling and venting Fill up the system via the filling device on the top side Monitoring the fill level indicator during the filling process Fill the unit with water via the on site sy...

Страница 11: ...a ture Use the arrow buttons to set the desired target temperature and confirm with the P but ton SP and the set target temperature light up alternately again Press the P button to display the boiler...

Страница 12: ...a tic circuit breakers in the device and in the on site distributor check whether the system is switched on at low pressure top up with water If the pressure is too high Drain water check oil filter f...

Страница 13: ...ing damage burner goes into malfunction at irregular intervals coupling defective oil pump or engine running heavily ignition transformer stops IRD no longer takes over relief check fuse set thermosta...

Страница 14: ...ng activating deactivating and diagnos tics The multi color signal lamp behind the clear cover of the lockout reset button is the key indicating compo nent for visual diagnostics and interface diagnos...

Страница 15: ...ion and console With integrated sack truck to facilitate transport The air heater is equipped with a thermostat The connection between air heater and heater to move is made with a flow return flow hos...

Страница 16: ...teme de SCHEER Heizsysteme Produktionstechnik GmbH Chausseestr 16 D 25797 W hrden Tel 49 0 4839 905 0 Fax 49 0 4839 453 info scheer heizsysteme de www scheer heizsysteme de best in convenience and com...

Отзывы: