51
2021-02-10 / V1.0
Contactors C195 Series – Installation and Maintenance Instructions
Maintenance
Disassembling/assembling the contact
bridge unit – type C195 A/, B/, S/, T/, W/
Requirements
-
The contact unit is disassembled, see section
“Disas-
sembling/assembling the contact unit – type C195 A/,
B/, S/, T/, W/” on page 46.
-
The armature is disassembled, see section
“Disas-
sembling/assembling the armature – type C195 A/,
B/, S/, T/, W/” on page 48.
-
The cover is removed, see section
“Removing/at-
taching the cover – type C195 A/, B/, S/, T/, W/” on
page 50.
Disassembly
X
Remove the contact bridge unit (5) upwards from
the contact unit (2).
2
5
15
13
14
Fig. 66: C195 A/, C195 B/: Disassembling/assembling the
contact bridge unit (the figure shows C195 A/, the pro-
cedure is identical for C195 B/)
X
Insert the contact bridge unit (5) into the contact
unit (2). Make sure that
-
the sealing ring (13) and the contact pressure
spring (14) are in place and correctly positioned,
-
the return spring (15) is in place and correctly
positioned.
2
5
15
13
14
Fig. 67: C195 S/, C195 T/: Disassembling/assembling the con-
tact bridge unit (the figure shows C195 S/, the proce-
dure is identical for C195 T/)
2
5
15
14
Fig. 68: C195 W/: Disassembling/assembling the contact
bridge unit
Assembly
X
Insert the contact bridge unit (5) into the contact
unit (2). Make sure that
-
the sealing ring (13) and the contact pressure
spring (14) are in place and correctly positioned,
-
the return spring (15) is in place and correctly
positioned.