VLV55|VLV65 - Volumetric flow controller

 

 

 

TECHNICAL DOCUMENTATION

 

 

Startup using the setting and diagnostic device ZTH EU (Belimo) |   

  

 

 

 

Construction subject to change 

 

No return possible 

Version: 2017-04-24 | Page  27 

STARTUP USING THE SETTING AND 
DIAGNOSTIC DEVICE ZTH EU (BELIMO) 

 

 

Short description 

The VAV setting device ZTH EU allows efficient testing of VAV 
and CAV installations. Installations fitted with the Belimo VAV 
controller can be simply adapted to the room and user require-
ments. The VAV setting device ZTH EU replaces the previous 
setting device ZTH-GEN (2007-2014).  
 
All standard Belimo VAV controllers with integrated PP commu-
nication (from 1992) that are sold in the EU can be set using the 
ZTH EU. 
 

Specifications 

 

easy, quick setting of the VAV boxes parameters 

 

diagnostic function 

 

one tool for all VAV units 

 

voltage supplied by VAV controllers - no batteries required! 

 

service socket VAV / CR24 controller, PP connection 

 

includes connecting cable RJ12 6/4, 6-pin plug 

 

New generation, MP bus tester  

 

for functional test of MP bus 

 

backward compatible with all Belimo PP / MP units from 
1992 

 

efficient handling, can be operated with one hand 

 

Selection of stages for test (OPEN/CLOSE/MIN/MAX/STOP) 

 

Damper position indicator for diagnostics 

 

Display of the setpoint / actual volume and V

min/max

 setting in 

m³/s (l/s). 

 

 
 
 
Keys / Display 

 

2 x 16-digit LCD with background lighting 
 

 

Forwards / Backwards
Change value / status 

OK

Confirm input

ESC

Cancel input /
Leave submenu / Discard changes 

i

shows additional information if available 

 
 

Connection 

Locally via service socket 

 

 

Dimensions 

85x65x23 (WxHxD) 
 
 

Connection and supply 

Stand-alone operation 

Connection including supply takes place via the service socket 
at the VAV controller or via the terminals. 
 

Bus operation 

The ZTH EU can be used in the following units while the bus is 
running if it is connected via the local service socket: VAV-
Compact L/N/SMV-D3-MP, NMVAX-D3-MP, L/NMV-D3LON. 
 
With the VRP-M, L/NMV-D3-M and NMVAX-D3-MP, the MP-Bus 
must be disconnected when the service socket is used. 
 

 

 
 

Restriction 

Direct connection in an MP network or via an MP-Bus master is 
not possible.  
 
The ZTH EU comes with a quick start guide in German and Eng-
lish to be affixed to the back of the unit. 

 

 

Содержание VLV55

Страница 1: ...ES after moulded parts no inflow area required optimised for air velocities from 0 5 m s high control accuracy at low pressures and air veloci ties position independent installation resistant to pollu...

Страница 2: ...55 radiated noise relative sound spectrum 11 VLV65 flow generated noise 12 VLV65 flow generated noise relative sound spectrum 13 VLV65 Radiated noise 14 VLV65 Radiated noise relative sound spectrum 15...

Страница 3: ...stems also at low duct pressures and air velocities When suitable controller types are used room or duct pressure regulation can be achieved For the measurement of the effective pressure SCHAKO is us...

Страница 4: ...n connecting SCHAKO components to customer installa tions any compatibility problems are beyond our scope of re sponsibility and must be solved on site Tests and standards The volumetric flow controll...

Страница 5: ...flow controller is no longer guaranteed If only Vmax is specified in the order a variable volumetric flow controller will be delivered The Vmin value will be set to the value specified in the catalog...

Страница 6: ...l mineral wool filling DIMENSIONS OF ACCESSORIES METU flange MF1 Tension ring provided by the customer VLV Metu flange MF1 Counter flange provided by the customer Flat flange FF1 on both sides to DIN...

Страница 7: ...96 100 5 200 0 5 55 15 5 15 2 218 61 20 10 4 436 121 60 7 5 546 152 100 5 250 0 5 86 24 5 15 2 344 96 20 10 4 687 191 60 7 5 859 239 90 5 315 0 5 137 38 5 15 2 549 153 20 10 4 1097 305 65 7 5 1372 38...

Страница 8: ...4 59 62 64 5 132 37 56 61 65 67 125 0 5 21 6 35 38 43 45 48 2 84 23 49 54 58 59 61 4 167 46 47 58 63 65 67 5 209 57 56 63 67 69 160 0 5 35 10 38 45 46 50 51 2 139 38 51 57 60 62 63 4 277 77 50 60 64 6...

Страница 9: ...und spectrum dB Correction value KL Frequency Hz Hz 63 125 250 500 1000 2000 4000 8000 KL 6 5 1 0 7 11 18 26 NW250 Relative sound spectrum dB Correction value KL Frequency Hz Hz 63 125 250 500 1000 20...

Страница 10: ...0 5 13 4 2 53 15 25 28 30 4 105 29 27 30 33 34 5 132 37 32 34 36 38 125 0 5 21 6 2 84 23 25 29 30 4 167 46 25 28 32 33 36 5 209 57 33 35 38 42 160 0 5 35 10 25 2 139 38 28 31 33 36 4 277 77 34 37 39 4...

Страница 11: ...spectrum dB Correction value KL Frequency Hz Hz 63 125 250 500 1000 2000 4000 8000 KL 3 4 8 6 7 6 7 9 NW250 Relative sound spectrum dB Correction value KL Frequency Hz Hz 63 125 250 500 1000 2000 400...

Страница 12: ...57 62 65 66 8 210 58 62 66 69 125 1 42 12 41 45 49 51 53 3 125 35 50 58 61 63 64 5 210 60 47 59 63 67 70 8 334 93 65 69 71 160 1 69 19 45 49 53 54 57 3 208 58 50 58 63 65 67 5 345 95 51 59 64 67 69 8...

Страница 13: ...und spectrum dB Correction value KL Frequency Hz Hz 63 125 250 500 1000 2000 4000 8000 KL 5 3 0 1 6 11 18 27 NW250 Relative sound spectrum dB Correction value KL Frequency Hz Hz 63 125 250 500 1000 20...

Страница 14: ...6 7 3 79 22 26 28 30 5 130 35 25 30 32 35 8 210 58 35 39 40 125 1 42 12 3 125 35 26 29 30 5 210 60 30 33 34 36 8 334 93 38 40 41 42 160 1 69 19 25 28 31 3 208 58 33 36 38 40 5 345 95 39 41 43 45 8 554...

Страница 15: ...spectrum dB Correction value KL Frequency Hz Hz 63 125 250 500 1000 2000 4000 8000 KL 0 2 6 4 7 7 7 11 NW250 Relative sound spectrum dB Correction value KL Frequency Hz Hz 63 125 250 500 1000 2000 400...

Страница 16: ...50 50 34 21 7 19 28 40 50 50 50 32 125 4 11 21 33 50 50 32 19 6 17 25 34 49 50 36 22 160 3 8 15 23 34 9 18 14 5 12 18 28 41 48 26 16 200 2 5 11 18 30 24 14 11 4 10 15 24 35 41 22 13 250 2 4 9 15 27 1...

Страница 17: ...tching contact If the Compact controllers of the Belimo make must be deliv ered with the operating mode 0 10V DC on customer request please note that a positive control CLOSED can only be ef fected vi...

Страница 18: ...ied out with a 0 10 V signal Attention Controller DDC must be able to pull the command signal to 0 V Cable designations Com mand sig nal Y Volumetric flow Function 0 1 V 0 Damper CLOSED VAV control in...

Страница 19: ...0 10 V 0 10 V 2 10 V 2 10 V 2 10 V 2 10 V 2 10 V Signal 0 10 V 2 10 V Function 3 3 3 3 3 Damper CLOSED a CLOSED c CLOSED Vmin Vmax b VAV CAV Vmin everything open Vmin active Damper OPEN e OPEN CAV Vma...

Страница 20: ...are pressed again after 2 hours have passed LED 1 LED 2 Lack of air Damper opens as actual volume is too low LED 1 LED 2 Target volume reached Control circuit balanced LED 1 LED 2 Air excess Damper cl...

Страница 21: ...et the required actual volumetric flow unit in m3 h and l s Vmin To set the required min volumetric flow setpoint value Y 0V 2V Vmax To set the required max volumetric flow setpoint value Y 10V Mode t...

Страница 22: ...nn or Vmax volumetric flow depending on con troller type Information regarding the set value Vmin in the following controllers Vmin refers to Vnenn Product Type Belimo LMV D3 MP LMV D3 MF Gruner 227VM...

Страница 23: ...ignal 0 10 V DC Example Assume Measurement output signal U5 6 3 V DC see calibration value VRA E 12 m sec Measured va lue Duct velocity 7 6 m s Air volume Duct velocity x area m x 3600 m h U5 signal 2...

Страница 24: ...s III safety extra low voltage Protection type IP 54 hose connected EMC CE according to 39 336 EEC Measuring air and ambient tempera tures 0 C 50 C 5 95 rH non condensing Storage temperature 20 C 80 C...

Страница 25: ...0 100 of Vnom Vkonst 0 100 of Vnom Command variable Y Z inherent resistance min 100 k DC 0 10 V 0 20 mA min 500 inherent resistance DC 2 10 V 4 20 mA min 500 inherent resistance Setting range actual...

Страница 26: ...internally by means of DC DC converter This is why no external power supply is necessary Driver To be able to work with the ZTH EU a suitable driver must be installed on the PC The driver can be down...

Страница 27: ...ctional test of MP bus backward compatible with all Belimo PP MP units from 1992 efficient handling can be operated with one hand Selection of stages for test OPEN CLOSE MIN MAX STOP Damper position i...

Страница 28: ...le in a switch cabinet Structure and operation The relevant parameters can be set and queried in the individ ual menu items while the operating parameters programmed in factory can be queried under me...

Страница 29: ...properly disposed of INSTALLATION INFORMATION Installation and commissioning Installation with horizontal or vertical damper axle possible position independent direct connection to moulded parts such...

Страница 30: ...227VM 024 05 setting values 150 600 m h with METU flange ORDER DETAILS 01 Type VLV55 version with diameter ratio 55 0 5 5 m s VLV65 version with diameter ratio 65 1 8 m s STANDARD 02 Size 100 NW 100...

Страница 31: ...seal made of EPDM silicone and halogen free Ring chamber sealing made of EPDM silicone and halogen free Venturi nozzle made of aluminium with attached measuring points for determining average values...

Отзывы: