background image

 

VLV55|VLV65 - Volumetric flow controller

 

 

 

TECHNICAL DOCUMENTATION

 

 

Startup using the setting device GUIV-A |   Smartphone app - Belimo Assistant

  

 

 

 

Construction subject to change 

 

No return possible 

Version: 2017-04-24 | Page  28 

STARTUP USING THE SETTING DEVICE GUIV-A 

Application 

The setting device GUIV-A is used by the startup or service per-
sonnel in order to carry out simple settings to the equipment or 
to check the actual values. 
The controller type 227VM does not have any operating ele-
ments such as switches or setpoint potentiometers. To program 
the operating modes and the operating parameters V

min

 and 

V

max

, the setting device GUIV-A is required, which can also be 

used to switch from 2 - 10 V DC to 0 - 10 V DC. 
 

Connection 

The GUIV-A can be connected electrically to 227 V via the U/PP 
connection by direct on site or remote control, for example in a 
switch cabinet. 
 

Structure and operation 

The relevant parameters can be set and queried in the individ-
ual menu items, while the operating parameters programmed 
in-factory can be queried under menu item 10. 
 

Note 

As long as the U/PP connector is connected to the GUIV-A, the 
output signal U does not correspond to the actual value. 
 
 

Connection diagram 
 

 

 

1 Earth, 

neutral 

Supply voltage 24 V AC 

Setpoint value signal Y and positive control Z input 227VM, 
GUAC 

Output communication signal PP and actual volumetric flow 

 

SMARTPHONE APP - BELIMO ASSISTANT 

The NFC antenna area of the VAV Compact is located between 
the Belimo or OEM logo and the NFC label.  
Align NFC-capable android smartphone with loaded Assistant 
app on the VAV-Compact such that the two antennae are 
above one another. 

 

 

 

 
 

 
The Belimo Assistant app can be downloaded from the Google 
Play Store. 
 

NFC-capable devices:

-

LMV-D3-MP, NMV-D3-MP, SMV-D3-MP and LHV-D3-MP with 
printed NFC label. 

Non-NFC-capable devices

-

All devices without NFC label

-

LMV-D3-MF

-

LMV-D3-LON and NMV-D3-LON 

 

Содержание VLV55

Страница 1: ...ES after moulded parts no inflow area required optimised for air velocities from 0 5 m s high control accuracy at low pressures and air veloci ties position independent installation resistant to pollu...

Страница 2: ...55 radiated noise relative sound spectrum 11 VLV65 flow generated noise 12 VLV65 flow generated noise relative sound spectrum 13 VLV65 Radiated noise 14 VLV65 Radiated noise relative sound spectrum 15...

Страница 3: ...stems also at low duct pressures and air velocities When suitable controller types are used room or duct pressure regulation can be achieved For the measurement of the effective pressure SCHAKO is us...

Страница 4: ...n connecting SCHAKO components to customer installa tions any compatibility problems are beyond our scope of re sponsibility and must be solved on site Tests and standards The volumetric flow controll...

Страница 5: ...flow controller is no longer guaranteed If only Vmax is specified in the order a variable volumetric flow controller will be delivered The Vmin value will be set to the value specified in the catalog...

Страница 6: ...l mineral wool filling DIMENSIONS OF ACCESSORIES METU flange MF1 Tension ring provided by the customer VLV Metu flange MF1 Counter flange provided by the customer Flat flange FF1 on both sides to DIN...

Страница 7: ...96 100 5 200 0 5 55 15 5 15 2 218 61 20 10 4 436 121 60 7 5 546 152 100 5 250 0 5 86 24 5 15 2 344 96 20 10 4 687 191 60 7 5 859 239 90 5 315 0 5 137 38 5 15 2 549 153 20 10 4 1097 305 65 7 5 1372 38...

Страница 8: ...4 59 62 64 5 132 37 56 61 65 67 125 0 5 21 6 35 38 43 45 48 2 84 23 49 54 58 59 61 4 167 46 47 58 63 65 67 5 209 57 56 63 67 69 160 0 5 35 10 38 45 46 50 51 2 139 38 51 57 60 62 63 4 277 77 50 60 64 6...

Страница 9: ...und spectrum dB Correction value KL Frequency Hz Hz 63 125 250 500 1000 2000 4000 8000 KL 6 5 1 0 7 11 18 26 NW250 Relative sound spectrum dB Correction value KL Frequency Hz Hz 63 125 250 500 1000 20...

Страница 10: ...0 5 13 4 2 53 15 25 28 30 4 105 29 27 30 33 34 5 132 37 32 34 36 38 125 0 5 21 6 2 84 23 25 29 30 4 167 46 25 28 32 33 36 5 209 57 33 35 38 42 160 0 5 35 10 25 2 139 38 28 31 33 36 4 277 77 34 37 39 4...

Страница 11: ...spectrum dB Correction value KL Frequency Hz Hz 63 125 250 500 1000 2000 4000 8000 KL 3 4 8 6 7 6 7 9 NW250 Relative sound spectrum dB Correction value KL Frequency Hz Hz 63 125 250 500 1000 2000 400...

Страница 12: ...57 62 65 66 8 210 58 62 66 69 125 1 42 12 41 45 49 51 53 3 125 35 50 58 61 63 64 5 210 60 47 59 63 67 70 8 334 93 65 69 71 160 1 69 19 45 49 53 54 57 3 208 58 50 58 63 65 67 5 345 95 51 59 64 67 69 8...

Страница 13: ...und spectrum dB Correction value KL Frequency Hz Hz 63 125 250 500 1000 2000 4000 8000 KL 5 3 0 1 6 11 18 27 NW250 Relative sound spectrum dB Correction value KL Frequency Hz Hz 63 125 250 500 1000 20...

Страница 14: ...6 7 3 79 22 26 28 30 5 130 35 25 30 32 35 8 210 58 35 39 40 125 1 42 12 3 125 35 26 29 30 5 210 60 30 33 34 36 8 334 93 38 40 41 42 160 1 69 19 25 28 31 3 208 58 33 36 38 40 5 345 95 39 41 43 45 8 554...

Страница 15: ...spectrum dB Correction value KL Frequency Hz Hz 63 125 250 500 1000 2000 4000 8000 KL 0 2 6 4 7 7 7 11 NW250 Relative sound spectrum dB Correction value KL Frequency Hz Hz 63 125 250 500 1000 2000 400...

Страница 16: ...50 50 34 21 7 19 28 40 50 50 50 32 125 4 11 21 33 50 50 32 19 6 17 25 34 49 50 36 22 160 3 8 15 23 34 9 18 14 5 12 18 28 41 48 26 16 200 2 5 11 18 30 24 14 11 4 10 15 24 35 41 22 13 250 2 4 9 15 27 1...

Страница 17: ...tching contact If the Compact controllers of the Belimo make must be deliv ered with the operating mode 0 10V DC on customer request please note that a positive control CLOSED can only be ef fected vi...

Страница 18: ...ied out with a 0 10 V signal Attention Controller DDC must be able to pull the command signal to 0 V Cable designations Com mand sig nal Y Volumetric flow Function 0 1 V 0 Damper CLOSED VAV control in...

Страница 19: ...0 10 V 0 10 V 2 10 V 2 10 V 2 10 V 2 10 V 2 10 V Signal 0 10 V 2 10 V Function 3 3 3 3 3 Damper CLOSED a CLOSED c CLOSED Vmin Vmax b VAV CAV Vmin everything open Vmin active Damper OPEN e OPEN CAV Vma...

Страница 20: ...are pressed again after 2 hours have passed LED 1 LED 2 Lack of air Damper opens as actual volume is too low LED 1 LED 2 Target volume reached Control circuit balanced LED 1 LED 2 Air excess Damper cl...

Страница 21: ...et the required actual volumetric flow unit in m3 h and l s Vmin To set the required min volumetric flow setpoint value Y 0V 2V Vmax To set the required max volumetric flow setpoint value Y 10V Mode t...

Страница 22: ...nn or Vmax volumetric flow depending on con troller type Information regarding the set value Vmin in the following controllers Vmin refers to Vnenn Product Type Belimo LMV D3 MP LMV D3 MF Gruner 227VM...

Страница 23: ...ignal 0 10 V DC Example Assume Measurement output signal U5 6 3 V DC see calibration value VRA E 12 m sec Measured va lue Duct velocity 7 6 m s Air volume Duct velocity x area m x 3600 m h U5 signal 2...

Страница 24: ...s III safety extra low voltage Protection type IP 54 hose connected EMC CE according to 39 336 EEC Measuring air and ambient tempera tures 0 C 50 C 5 95 rH non condensing Storage temperature 20 C 80 C...

Страница 25: ...0 100 of Vnom Vkonst 0 100 of Vnom Command variable Y Z inherent resistance min 100 k DC 0 10 V 0 20 mA min 500 inherent resistance DC 2 10 V 4 20 mA min 500 inherent resistance Setting range actual...

Страница 26: ...internally by means of DC DC converter This is why no external power supply is necessary Driver To be able to work with the ZTH EU a suitable driver must be installed on the PC The driver can be down...

Страница 27: ...ctional test of MP bus backward compatible with all Belimo PP MP units from 1992 efficient handling can be operated with one hand Selection of stages for test OPEN CLOSE MIN MAX STOP Damper position i...

Страница 28: ...le in a switch cabinet Structure and operation The relevant parameters can be set and queried in the individ ual menu items while the operating parameters programmed in factory can be queried under me...

Страница 29: ...properly disposed of INSTALLATION INFORMATION Installation and commissioning Installation with horizontal or vertical damper axle possible position independent direct connection to moulded parts such...

Страница 30: ...227VM 024 05 setting values 150 600 m h with METU flange ORDER DETAILS 01 Type VLV55 version with diameter ratio 55 0 5 5 m s VLV65 version with diameter ratio 65 1 8 m s STANDARD 02 Size 100 NW 100...

Страница 31: ...seal made of EPDM silicone and halogen free Ring chamber sealing made of EPDM silicone and halogen free Venturi nozzle made of aluminium with attached measuring points for determining average values...

Отзывы: