VLV55|VLV65 - Volumetric flow controller
TECHNICAL DOCUMENTATION
Startup using PC-Tool |
Construction subject to change
No return possible
Version: 2017-04-24 | Page 26
STARTUP USING PC-TOOL
Direct connection to switch cabinet or socket
(traditional application)
ZTH EU as MP level converter
Description
The ZTH EU is also a potential-free interface between the USB
port of a PC and the Belimo MP bus. It is used to connect the
Belimo PC-Tool directly to the MP bus or directly to a program-
mable MFT drive.
Power supply
The ZTH EU is supplied with power by the USB port. The MP bus
voltage is obtained internally by means of DC/DC converter.
This is why no external power supply is necessary.
Driver
To be able to work with the ZTH EU, a suitable driver must be
installed on the PC. The driver can be downloaded from the
Belimo website (download section). After installation of the
driver, the ZTH EU device will log in to the PC as a virtual COM
interface.
Note
For connection to USB ports of PCs and BELIMO 24 V drives
only (to safety extra low voltage SELV or US class 2 feeds)
Connection diagram 1
Local connection via a service socket of the MF/MP or LON
drive using a ZK1-GEN cable.
Connection diagram 2
Local connection via a connecting cable of the MF/MP or LON
drive using a ZK2-GEn cable.
1.)
white
=
GND
green
=
MP
blue
=
not connected
…A-MF
…A-MP
…D3-MP
…ALON
…D3LON
…MFT(2)
A-AF
…A-MP
…D3-MP
…LON
…ALON
…D3LON
1.)