User manual SCAIME: 

NU-eNodTouch-E-0413 

3.6.

 

Dosing Setup menu (eNod4-D) 

 

Detailed explanations on Dosing functioning and parameters could be found into eNod4-D manuals 

 

The following setup menu allows modifying the parameters related to dosing (Filling or Unloading) mode. 

 

 

3.6.1.

 

Dosing Cycle Setup 

 

Parameter 

Possible Value 

Description 

Dosing cycle parameters  

      

     

 

 

Page 1/3 

Feeds sequence 

eNod4-D  could  manage  up  to  3  feeds:  High  Feed  (HF),  Coarse  Feed  (CF),  Fine  Feed  (FF).  The 
number and order of used feeds during a cycle is configured by this parameter. 

Auto. TARE at Start 

[Yes], [No] 

If enable, TARE function is operated after each dosing cycle start 

 

Page 2/3 

Emptying / reloading 

[No],  [At  End], 
[At Start] 

define the activation / deactivation and position of emptying (Reloading in 
unloading mode) option 

Emptying mode 

[Auto], [Manual] 

In  filling  mode,  define  the  emptying  mode:  In  manual  mode,  emptying 
start after input ‘Manual Emptying’ activation 

Emptying end level 

0 – 1 000 000 

The ‘emptying’ output is disabled if the net value becomes inferior to this 
level and if the ‘emptying holding time’ has elapsed. 

Reloading Min Level 

0 – 1 000 000 

Output  assigned  to  the  reloading  function  is  activated  if  the  gross 
measurement  is  less  than  reloading  Min  Level,  until  the  measurement 
become greater than reloading max Level. 

Reloading Max Level 

0 – 1 000 000 

 

Page 3/3 

Dynamic mode 

[Yes], [No] 

Selecting  this  option  replaces  the  stability  condition  for  taking  tare  / 
results by averaging measurements over the ‘Calc time Tare/Result’. 

Activ FF if OUT- 

[Yes], [No] 

In  filling  mode,  this  option  automatically  restart  the  Fine  Feed  if  dosing 
result is below low tolerance 

Suspend/Resume 

cycle allowed 

[Yes], [No] 

Allows SUSPEND and RESUME cycle. It  makes possible to  restart a dosing 
cycle when starting weight is greater than "empty max. weight". 

 

 

 

Содержание eNodTouch

Страница 1: ...NU eNodTouch E 0413 SCAIME SAS Technosite Alt a BP501 74105 ANNEMASSE Cedex T l 33 0 4 50 87 78 64 www scaime com eNodTouch Touch screen for eNod4 controllers User Manual...

Страница 2: ...tartup screens 9 3 2 Main screen 10 3 2 1 Transmitter mode eNod4 T eNod4 C eNod4 D 10 3 2 2 Checkweigher mode eNod4 C 10 3 2 3 Dosing mode eNod4 D 10 3 2 4 Keyboard functions 11 3 3 Result displaying...

Страница 3: ...prox Panel cut dimension W105 x H66 mm Panel thickness area 1 to 5 mm Surrounding air temperature 0 to 50 C Ambient humidity 10 to 90 RH Wet bulb temperature 39 or less no condensation Dust 0 1 mg m o...

Страница 4: ...anel of a cabinet or enclosure Surrounding air temperature indicates both the et or enclosure s internal temperature eNodTouch installation Panel thickness eNodTouch has two projections on the top to...

Страница 5: ...nnection to eNod4 The serial interface is not isolated Always connect the SG Signal Ground of the unit to the connected device SG Signal Ground and FG Frame Ground are connected internally RS422 RS485...

Страница 6: ...n after the startup screen is displayed When Operating Touch the upper right then bottom left corners or the upper left and bottom right corners of the panel within a 40 pixel area in 0 5 seconds When...

Страница 7: ...le the in built Buzzer sound upon a touch Disable Display setting Show Brightness contrast control bar Specify whether to display on touch the Control Bar to adjust brightness and contrast Enable D Sc...

Страница 8: ...fo Manufacturer Schneider Electric SA Series MODBUS SIO Master N of Device 1 Note Never change the parameters in grey 2 2 4 Password menu Menu Input Parameter Description Default System Password Syste...

Страница 9: ...es of network communication 3 On Line Functioning 3 1 Startup screens At Power On the connection screen is displayed while eNodTouch try to communicate with connected eNod4 device If the connection sc...

Страница 10: ...ouch 3 2 3 Dosing mode eNod4 D To switch from the Bar graph to the Status bar touch the Weight value area To switch from the main keyboard to the 2 nd keyboard touch Bar graphe Gross Net indicator Sta...

Страница 11: ...t stability condition START DOSING Start the dosing cycle if starting conditions are satisfied dosing cycle is ongoing STOP DOSING Stop the dosing cycle the dosing counter is not incremented SUSPEND D...

Страница 12: ...ore information about parameters consult eNod4 software manuals Setup menu access can be secured by password see 3 4 1 In that case the following screen is displayed After entering a valid password or...

Страница 13: ...tion loads used during the physical calibration load 1 2 3 1 1 000 000 Weight values corresponding to each calibration segment Zero Calibration Allows acquiring stable measurement with no load on the...

Страница 14: ...logical inputs before their activation Output 1 4 Parameters Function Function assigned to the related output None Thresholds Stability Coarse feed High feed fine feed Cycle ongoing result available O...

Страница 15: ...ter with frequency rejection of 50 Hz or 60 Hz harmonics Frequency 6 1600 Hz Filtered measurement frequency is adjustable from 6 25 to 1600 Hz Bessel low pass filter parameters Filter Order 0 2 3 4 Fo...

Страница 16: ...ng measurements during the specified time Automatic Dyn Zero Yes No Automatic zero correction allows to dynamically track the Zero evolution When enabled an average Zero value is continuously calculat...

Страница 17: ...mode Auto Manual In filling mode define the emptying mode In manual mode emptying start after input Manual Emptying activation Emptying end level 0 1 000 000 The emptying output is disabled if the net...

Страница 18: ...Page 1 3 Start cycle delay 0 65535 ms This stabilization time precedes the tare execution Meas Stab delay This stabilization time follows the FF stop After this delay a new dosing result is calculate...

Страница 19: ...o FF level Page 2 2 Correction 0 100 If Automatic correction enabled the correction formula is In flight In flight Dosing result Target weight x Correction X3 correction if Out of Tolerance Yes No If...

Страница 20: ...represents the value to reach at the end of the dosing process Used in sequences using at least 2 or 3 feeds Defines the transition threshold relative to the target weight Coarse feed and Fine Feed p...

Отзывы: