9911004rev27
Title
Date
2017-02-16
Page
66(81)
SBS MicroSMART Battery Charger Technical Handbook
4.
On the charger which is set to
Master
a new menu has appeared in the service menu.
Put the marker on
Parallel control
and press
OK
. The following menu is shown.
5.
Set the field
Function
to
Enabled.
6.
Enter the menu
Charger select
. Here it is possible to choose which chargers should be
a part of the cluster by making sure the charger is marked with an X in the column
Ctrl
.
In the column
S/N
the serial numbers of the present chargers are viewed. Note that
also the charger which acts as master has to be selected.
7.
Press
ESC
until the main menu is shown. The chargers will now work together in order
to be able to charge the battery even faster. How the charge is carried out is controlled
entirely by the master. Below you can see the main screen of a charger which acts as
a slave in the cluster. Note that a cluster can have of maximum of 5 slaves and 1 master.