R
Read
Write
Description
Value / Unit
0
X
Firmware-Version
Ex: „11“= FW 1.1
1
X
Number of supported registers
will give „41“
2
X
Number of supported flags
will give „0“
3
X
Baudrate
BPS
4
NOT USED
will give a „0“
5
X
ASN (letter 1-4)
will give „ALE3“
6
X
ASN (letter 5-8)
will give “D5FS”
7
X
ASN (letter 9-12)
will give “10Cx”
x=2 : No MID
x=3 : MID
8
X
ASN (letter 13-15)
will give “A00 ”
9
X
HW Vers. Modif
Ex: „11“= FW 1.1
10
NOT USED
will give a „0“
11
X
Serialnumber
Serialnumber high
12
X
Serialnumber
Serialnumber low
13
NOT USED
will give a „0“
14
X
Status
„0“ = no Problem
„1“ = Problem with last communication request
15
X
S-Bus Timeout
ms
16
X
X
S-Bus Address
17
X
Error Flags
0 : No error
1 : Error Phase 1
2 : Error Phase 2
3 : Error Phase 1 and 2
4 : Error Phase 3
5 : Error Phase 1and 3
6 : Error Phase 2 and 3
7 : Error Phase 1, 2 and 3
18
X
NOT USED
will give a “0”
19
X
Tariff flag
0 is Tariff 1
4 is Tariff 2
20
X
WT1 total
Counter Energy Total Tarif 1
10
-2
kWh (multiplier 0,01)
Ex: 00912351= 009123,51kWh
21
X
X
WT1partial
Counter Energy partial Tarif 1
10
-2
kWh (multiplier 0,01)
Ex: 00912351= 009123,51kWh
22
X
WT2 total
Counter Energy Total Tarif 2
10
-2
kWh (multiplier 0,01)
Ex: 00912351= 009123,51kWh
23
X
X
WT2partial
Counter Energy partial Tarif 2
10
-2
kWh (multiplier 0,01)
Ex: 00912351= 009123,51kWh
24
X
URMS phase 1
Effective Voltage of Phase 1
V
Ex: 230 = 230V
25
X
IRMS phase 1
Effective Current of phase 1
10
-1
A (multiplier 0,1)
Ex: 314 = 31,4A
26
X
PRMS phase 1
Effective active Power of phase 1
10
-2
kW (multiplier 0,01)
Ex: 1545 = 15,45kW
27
X
QRMS phase 1
Effective reactive power of phase 1
10
-2
kVA (multiplier 0,01)
Ex: 1545 = 15,45kVA
28
X
cos phi phase 1
10
-2
(multiplier 0.01)
Ex: 67 = 0.67
29
X
URMS phase 2
Effective Voltage of Phase 2
V
Ex: 230 = 230V
30
X
IRMS phase 2
Effective Current of phase 2
10
-1
A (multiplier 0,1)
Ex: 314 = 31,4 A
31
X
PRMS phase 2
Effective active Power of phase 2
10
-2
kW (multiplier 0,01)
Ex: 1545 = 15,45 kW
32
X
QRMS phase 2
Effective reactive power of phase 2
10
-2
kVA (multiplier 0,01)
Ex: 1545 = 15,45 kVA
33
X
cos phi phase 2
10
-2
(multiplier 0.01)
Ex: 67 = 0.67
34
X
URMS phase 3
Effective Voltage of Phase 3
V
Ex: 230 = 230 V
35
X
IRMS phase 3
Effective Current of phase 3
10
-1
A (multiplier 0,1)
Ex: 314 = 31,4 A
36
X
PRMS phase 3
Effective active Power of phase 2
10
-2
kW (multiplier 0,01)
Ex: 1545 = 15,45 kW
37
X
QRMS phase 3
Effective reactive power of phase 3
10
-2
kVA (multiplier 0,01)
Ex: 1545 = 15,45 kVA
38
X
cos phi phase 3
10
-2
(multiplier 0.01)
Ex: 67 = 0.67
39
X
PRMS total
Effective active Power of all phase
10
-2
kW (multiplier 0,01)
Ex: 1545 = 15,45 kW
40
X
QRMS total
Effective reactive power of all phase
10
-2
kVA (multiplier 0,01)
Ex: 1545 = 15,45 kVA