Technical data S-Bus
Bus system
S-Bus
Transmission rate
4800-9600-19'200-38'400-57'600-115'200.
The transmission rate is automatically detected
Transmission mode
Data
Bus length (max.)
1200 m (without repeater)
Response time:
Write: 60ms
(to system response)
Read: 60ms
■
The Interface works only if the Phase 1 is connected.
■
The communication is ready 30s after the Power On
■
The use of Energy meter in bus with intensive communication could reduce the performance of the Bus
■
Refresh Time for the Data is 10s. For this reason one energy meter should be not polled faster as 10s.
■
254 Devices could be connected to the S-Bus. Over 128 Devices, a repeater should be used.
■
The Interface don’t have a terminal resistor, this should be provided external.
■
For a description of the used Registers please look at the Register Page
Data transmission
■
Only «read/write» register instructions are recognized.
■
Only one register can be written at a time.
■
The device will respond «NAK» if more than 1 register is written.
■
Up to 10 Registers could be read at a time.
■
The device will respond «NAK» if more than 10 registers are read.
■
The device will not respond to any unknown query.
■
The device has a voltage monitoring system. In case of voltage loss, registers are stored in EEPROM
(transmission rate etc.)
Change the S-Bus address direct on device
■
To modify the S-Bus address, press 3 sec on
►
touch
■
In menu,
▼
increase address by 10,
►
increase by 1
■
Once the address is selected wait for the root menu to come back