Hardware Manual PCD1.M2110R1 │ Document 27-619 │ Version ENG 04 │ 2018-08-20
Saia-Burgess Controls AG
Communications Interfaces
6
6-6
On-board │ Port#1 │ Slot A
Malfunction
If interface modules of the PCD7.F1xxS series (hardware version A) are used
with the following devices, the interface modules will become hot and their correct
function cannot be guaranteed.
- PCD1.M1xx
- PCD2.M1xx
- PCD2.M48x
- PCS
The hardware version can be seen on the white label of a PCD7.F1xxS module in
the middle text line.
Solution
Only use PCD7.F1xxS interface modules PCD7.F1xxS with hardware version B
or newer. These are suitable for all PCD generations.