Hardware Manual PCD1.M2110R1 │ Document 27-619 │ Version ENG 04 │ 2018-08-20
Saia-Burgess Controls AG
On-board │ Interrupt Inputs
Inputs/Outputs (I/O)
4-9
4
Signal edge selection
The signal edges that causes the as-
sociated XOB to be called is selected
as follows:
PG5 Device Configurator
Onboard In-/Outputs
Properties
Interrupts
Operation IX0 (also applies for IX1)
With a positive flank at Input IX0, XOB 20 is called. The maximum reaction time
until the call of XOB 20 is 1
ms. The code in this XOB defines how the system
should react to the events, e.g. by increment a counter (max. input frequency
1
kHz, whereas the pulse/pause ratio is 1:1, maximum sum of the two frequencies
is 1
kHz).