ENGLISH

17

Temperature sensor 1 is not 

connected.

Temperature sensor 1 is short 

circuit.

Temperature fuse is defective.

Temperature sensor 2 is not 

connected.

Temperature sensor 2 is short 

circuit.

Combined Temperature

/ Humidity sensor is defective.

Communication failure.

Temperature is greater than the 

maximum temperature.

Safety Switch open or Door 

sensor open.

PCB overheat.

E1

E2

E3

E4

E5

E6

E7

E8

oPEn

E10

Check the wire between the sensor and the control unit. If 

there is no problem with the wires and they are correctly 

installed, check the sensor. 

If no reason for the problem can be found, contact the 

retailer.

Check the wire between the sensor and the control unit. 

It has probably overheated. The reason for it needs to be 

discovered before using the sauna again. A new sensor 

is needed. 

If no reason for the problem can be found, contact the 

retailer.

Check the wire between the bench sensor and the control 

unit. If there is no problem with the wires and they are 

correctly installed, check the sensor. The heater can still 

be used with the sensor 1 only but 2 sensors are needed 

for the steamer.

If a new sensor is needed or no reason for the problem 

can be found, contact the retailer.

Check the RJ cable. If the area where the cable is 

located has many other cables, it can cause interference 

problems. Make sure that only one main board is set to 

Power Controller and the rest are Contactor Unit. Check 

DIP switch setting.

If no reason for the problem can be found, contact the 

retailer.

If this happens contact qualified electrician or maintenance 

personnel before using the sauna again.

Remove object on the top of the heater or close the Door 

sensor.

Check ventilation of power controller. Heater will turn back 

ON if power controller already cool-down.

Code

Table 2

Problem

Solution

5. TROUBLESHOOTING

If an error occurs, the heater will be 
switched off. There will be a warning beep 
and the code for the error will be displayed 
in the control panel. 

See more details on the table below.

WARNING 

Please note, only a qualified electrician or 
maintenance personnel is allowed to make the 
service operations and repairs!

Содержание SAUNOVA 2.0

Страница 1: ...ENGLISH MANUAL Congratulations on your purchase of Saunova 2 0 Control Unit Please read the manual carefully before using the control Not for use in the USA Canada and Mexico ...

Страница 2: ...eamer 6 2 3 2 Water Refill 7 2 3 3 Cabin Drying 7 3 Assembly and Installation 8 3 1 Control Unit to Heater Connection Diagram 8 3 2 Power Controller 9 3 3 Contactor Unit 9 3 4 Technical Diagram 10 3 5 Sensors 12 3 5 1 Sensor location with heaters mounted on the wall 12 3 5 2 Sensor location with heaters mounted on the floor 13 3 6 Maximum Session Time 13 3 7 Fan Optional 14 3 8 Installation of Pow...

Страница 3: ... qualified electrician is allowed to make electrical connections and repairs on the unit Use original parts only 2 Disconnect the Power Controller and the Contactor Unit from the electrical circuit before installation opening the lid of the power controller or contactor unit and repair 3 Check power supply rating before installation 4 Check the correct location of the sensor in the installation se...

Страница 4: ...by the actual temperature inside the sauna room 2 Press arrow keys to adjust temperature 3 To change the parameter values press the Mode button 4 Now the corresponding LED is blinking faster Use the up and down arrows to change the values 5 You can move from one parameter to another by short pressing the Mode button 6 Confirm the settings by long pressing the Mode button If no keys are pressed aft...

Страница 5: ...on However the sauna room light will not be switched off Light button can be used even the heater is off Also Fan 2 2 3 Pre run button Pre run button can only be enabled in Off Mode During the pre run parameter values can be changed Set the pre run time by pressing the Pre run button A countdown time is displayed Use the Up and Down arrow keys to change the pre run values After pre run time expire...

Страница 6: ...r more than 5 seconds A high beep will confirm the activation and the deactivation When key lock is activated only heater on off and cabin light functions can be used Toggle button is enabled only to see actual values If other buttons are pressed is shown in the display Unlock the buttons by pressing up and down arrow keys at the same time for more than 5 seconds A high beep will confirm it The ke...

Страница 7: ...tomatically react to the low level of water The water inlet will open to fill up the tank and steamer session can be continued without intervention In the manual fill the alarm beeps and FILL will be displayed as long as the user fills the tank However if the user does not refill the tank and it becomes empty a high tone interval beep and dry display will alarm the user The steamer will automatica...

Страница 8: ...nova 2 0 user interface can be installed either inside or outside the sauna room Only one user interface can be used to control the heater T H ja TS2 sensors are optional Follow local regulation of the junction box s location Junction Box max 500mm USER INTERFACE max 800mm height inside sauna USER INTERFACE SENSOR S HEATER INSIDE SAUNA ROOM OUTSIDE SAUNA ROOM POWER SUPPLY POWER CONTROLLER HEATER F...

Страница 9: ...f PVC insulated cable as a connecting cable is prohibited due to thermal embrittlement The maximum distance of the junction box from the floor is 500 mm measured from the upper corner of the box WARNING Do not embed the control unit into the wall because it may lead to overheating of the unit and cause damage 3 3 Contactor Unit If the heater used is more than 9 kW an additional contactor is needed...

Страница 10: ...SESSION TEMP SLAVE COMBI 1 2 3 BLACK BROWN WHITE WHITE BLUE BLACK BROWN WHITE BLUE BLUE TB 1 1 1 3 2 LIGHT FAN FILL EMPTY Note SAFETY SWITCH K7 J4 UB N U V W N N N N R in S in T in J3 J2 J1 RS1 F3 F1 F2 RS3 RS2 K6 K5 K4 K2 ERROR 1 2 3 4 K1 K3 REMON N N N N 3 4 2 4 REM ON LEVEL 5 core cable Control Unit Main Switch BROWN CONTROL A A B BLACK BLUE 1 1 0 1 Primary Supply Fuse Glass Light 1000 mA 160 m...

Страница 11: ...ed sensor is capable of measuring the humidity as well as the temperature With two sensors it is possible to receive more accurate measurements from the sauna room If the heater is mounted on the wall or floor standing less than 200mm from the wall the first temperature sensor needs to be mounted on the wall above the heater Place the sensor 150mm from the ceiling Fig 6 7 However if the heater is ...

Страница 12: ...se of the sauna For domestic use the total on time of the sauna is limited to 6 hours It includes pre run time and the session time The factory setting for the control unit is 6 hours For condominiums hotels and similar locations the operating period of the sauna heater is limited to 12 hours including the pre run time and the session time For public sauna the operating period of the sauna heater ...

Страница 13: ...d condense of water is not possible inside the controller 2 Unscrew two screws from the top cover 3 Remove the plastic cover of the control unit by pushing the front lock through the hole in the chassis 4 Insert the designated wires to corresponding terminals See Technical Diagram 5 Drill holes for the screws on the wall as where to attach the power controller Install the power controller in verti...

Страница 14: ...the Power Controller 4 Insert the casing on the cut section 5 Screw the Control panel to the wall on the holes provided 6 Snap the top cover of the panel to its place 3 10 The Power Controller Main Switch The power controller switch can be found on the top end of the unit Using this switch you can isolate the electronics from the mains power supply In order to put the unit into operation switch to...

Страница 15: ...h function is available when it is switched ON and Door Switch function when it is OFF Both functions cannot work at the same time 4 1 1 Safety Switch The safety switch function is for a triggering device that will cut the heater connection when a combustible foreign object is thrown to the heater 4 1 2 Door Switch Install a door sensor and connect it to the control A signal is channel to the cont...

Страница 16: ...d they are correctly installed check the sensor The heater can still be used with the sensor 1 only but 2 sensors are needed for the steamer If a new sensor is needed or no reason for the problem can be found contact the retailer Check the RJ cable If the area where the cable is located has many other cables it can cause interference problems Make sure that only one main board is set to Power Cont...

Страница 17: ... one sensor is installed the steamer cannot be used The user can confirm the error by pressing the on off button after which the heater will function normally but the steamer cannot be used The user switches the steamer on and dry is displayed immediately Check that the empty and tank level terminals from the heater are connected with the empty and the tank level in the Power Controller The steame...

Страница 18: ...RatedPower3Phases RatedVoltage3Phases RatedPowerSinglePhase RatedVoltageSinglePhase Frequency Switchingcapacityperphase Saunatemperaturerange Maximumsessiontime preset DimensionsSAUNOVA2 0Stypes UserInterface PowerController WeightSAUNOVA2 0Stypes UserInterface PowerController WeightSAUNOVA2 0Btypes 9kWAC1 3x3kW 400V3N 9kWAC1 230V1N 50 60Hz 16A 30 110 C 1 2 4 6 8 12 18 24h W 104x H 147 x D 37 W 26...

Страница 19: ...RatedVoltage3Phases Frequency Switchingcapacityperphase 9kWAC1 3x 3kW 400V3N 50 60Hz 16A Additional Powerexpansion tomaximumof 18kW ContactorUnit Description Power Rating Remarks Temperature Sensorwithfuse BenchTemperatureSensor BenchCombinedTemperature HumiditySensor Optional Optional Sensor Description Remarks ...

Отзывы: