background image

ASV115 

 

 

 

Very simple parameterisation of complex applications 

 

Uploading and downloading parameters to transfer configurations 
from one device to another 

 

Configurable units range 

 

Overview page for rapid entry of the main parameters 

 

Tree view for fast navigation through the individual configuration 
pages 

 

Integrated access to plant schematic and wiring diagram 

 

Print-out of device configuration 

 

Service functions for fast troubleshooting 

C

C

C

A

1

0

640

Device No. 31 (max.)

120

(L > 200 m)

120

(L > 200 m)

Shielding

Control cabinet

Device No. 1

MM

MM

24V~

Device No. 2

 

Structured user guidance 

 

Online monitoring of most important operation parameters 

 

Engineering and fitting notes 

The drive can be fitted in any position (including upside down). It is 
placed directly on the damper shaft and clipped to the anti-torque 
device. The self-centring shaft adaptor ensures gentle operation of 
the damper shaft. The damper drive can be easily removed from 
the damper shaft without dismantling the anti-torque device. 

 

The angle of rotation can be limited between 0° and 90° on the 
device and can be set continuously between 5° and 80°. The limita-
tion is set with a set-screw directly on the drive, and with the limit 
stop on the self-centring shaft adaptor. This shaft adaptor is suitable 
for damper shafts of Ø 8...16 mm, 

 6.5...12.7 mm. 

 

 

Note 
The housing must not be opened. 

 

 
For feedback of the operating status, it is advisable to display the 
actual value signal (air volume) in the management system. 

 

No account has been taken of special standards such as 
IEC/EN 61508, IEC/EN 61511, IEC/EN 61131-1 and 2. Local regu-
lations on installation, application, access, access authorisations, 
accident prevention, safety, dismantling and disposal must be 
observed. Compliance is also required with installation standards 
EN 50178, 50310, 50110, 50274, 61140 and similar. 

 

The RS-485 parameterisation interface in the housing cover is not 
suitable for continuous operation. After parameterisation has been 
completed, the parameter plug must be removed and the opening 
should be sealed to restore the IP protection type. 

 

Fitting outdoors 

We recommend that devices are given additional protection against 
the effects of weather if installed outside. 

 

Wiring 

Power supply 

To ensure fault-free operation, the following wire cross-sections and 
lengths must be observed for the 24 V power supply and the ground 
connection. 
All devices within a network segment must be supplied by the same 
transformer. The power supply should be wired in star formation, 
observing the max. cable length in accordance with the table below 
(column 1: 

1 Device

). 

 

Maximum cable lengths for various numbers of devices 

Maximum number of devices 

Cross-
section 

1* 8 16 24 

32 

0.32 mm²

50 

6.2 

3.2 

2.0 

1.6 

0.5 mm² 

80 

10.0 

5.0 

3.4 

2.6 

0.75 mm²

120 

05.0 

7.6 

5.0 

3.8 

1.00 mm²

160 

20.0 

10.0 

6.6 

5.0 

1.50 mm²

240 

30.0 

15.0 

10.0 

7.6 

*) Star formation recommended. 

 

Analogue signals 

Analogue and digital signals are connected via the power cable. To 
ensure perfect operation, the ground cable (for drives that are 
interconnected in order to exchange signals) must be on the same 
potential. 

 

The maximum cable length for analogue signals is dependent 
mainly on the voltage drop on the ground cable. A signal cable with 
a resistance of 100 

 results in a 10 mV voltage drop with an 

ASV115 connected. If ten ASV115s are connected to this cable in 
series, the resultant voltage drop is 100 mV or an error of 1%. 

 

SLC bus connection 

The integrated SLC bus is physically specified as an RS-485 inter-
face. Depending on the line length, up to 31 devices can be con-
nected within one network segment. On all the controllers, the 
terminals C08 should be linked together and have the same poten-
tial. Neither special cables nor terminating resistors are required for 
cabling < 200 m. The wiring should have a purely line topology 
(daisy chain). Stub cables are not permitted; however, if they can-
not be avoided, they should be limited to a maximum of 3 metres. 

 

Wiring diagram (SLC bus) 

 

 

www.sauter-controls.com  

7/13 

Содержание ASV115

Страница 1: ... SLC SAUTER Local Communication protocol Easy to parameterise using the SAUTER CASE VAV software Constant air volume control using parameterisable inputs Technical description Power supply 24 V Variable end values for the differential pressure s measuring range 50 150 Pa 100 300 Pa Efficient control algorithm Output signal 0 10 V for Air volume actual value rq Air volume control deviation eq or fo...

Страница 2: ...nded 7 Recommend hardness of tubes 40 Sha e g silicone 8 Connection 02 can be configured as an analogue input or analogue output using SAUTER CASE VAV software 9 Digital inputs for external potential free contacts gold plated recommended 10 The parametering tool is always one of the subscribers so a maximum of 31 devices can be linked 11 Recommended Belden 3106A Accessories Type Description 052045...

Страница 3: ...switching contact 1 DI04 Factory setting FS Full scale PR Room pressure TR Room temperature Heating Cooling DN Nominal diameter c o Change over ad Index ad for additive p Index p for priority V Index V for air volume s Index s for second priority q Index q for quantity Setting the air volume The following functions are generally available to operate the air volume controller Setting ranges Functio...

Страница 4: ... permitted angle of the damper Functional diagram for damper position The function can be set using Sauter CASE VAV 1 4 or higher which allows one of the following applications for the device to be selected VAV 10 001 M VAV 20 001 M or VAV 20 001 Sxi When setting the parameters for terminal AO02 using the feedback signal for the damper position it is recommended to perform an adaption using Manual...

Страница 5: ...ression and upward limitation is defined by the maximum possible plant air volume damper fully open As an example the calculation and setting of the parallel setpoint shift may be performed as follows In order to obtain the value for the resultant setpoint shift as a per centage of the air volume the configuration of connection AI02 must also be taken into account For example if the input was free...

Страница 6: ...f factor shift 0 AI AO 02 AO not available Sensor block diagram 6 13 www sauter controls com Bus F B10418 1 NC not connected 2 It is recommended to put the setting for forced operation for LOW voltage additionally to Vvar 3 Connection is recognised as LOW voltage and accordingly the factory setting for forced operation is performed other parameters provide different behaviour After applying power ...

Страница 7: ...uitable for continuous operation After parameterisation has been completed the parameter plug must be removed and the opening should be sealed to restore the IP protection type Fitting outdoors We recommend that devices are given additional protection against the effects of weather if installed outside Wiring Power supply To ensure fault free operation the following wire cross sections and lengths...

Страница 8: ...c Double earthed shielding is suitable as a protection against electromagnetic interference e g from frequency converters electric motors coils etc It is advisable to use twisted pairs Additional technical information The upper section of the housing with the lid and the lid release button contains the electronics and the sensor The lower section of the housing contains the brushless DC motor the ...

Страница 9: ...ntroller 2 as standard Taking into account the logical statuses the command signal shifts the parameterised air volume values in the range from min to max With the same setting for these limitations and for the nominal air volume for the installation nom i e the parameterised values on the supply and exhaust air controllers must be the same a set point shift enables a parallel shift of the air vol...

Страница 10: ...etpoint B11698 Plant schematic example 1 Key 1 VAV compact controller ASV115 2 Room temperature controller NRT300 3 Reducing box 4 Building Management System BMS night mode Air volume parameters supply exhaust Air volume setpoint cqV s 40 4 V Master supply air min 20 max 100 nom 1000 m h Master exhaust air min 20 max 100 nom 1000 m h c factor 100 1 2 kg m Air volume actual value master rqv 40 4 V ...

Страница 11: ...to the upstream pressure in the air network due to fluctuations in duct pressure control these disruptions can be detected and transmitted directly to the slave controller This guarantees an equal percentage relationship between the supply and exhaust air controllers The command signal or the actual value signal rqv from the master controller can be connected in parallel to several slave controlle...

Страница 12: ... schematic example 2 Key 1 VAV compact controller ASV115 2 Room temperature controller NRT300 3 Reducing box 4 Building Management System BMS night mode Air volume parameters supply exhaust Air volume setpoint cqV s 40 4 V Master supply air min 20 max 100 nom 1000 m h Slave exhaust air min 10 max 100 nom 1000 m h c factor 100 1 2 kg m Air volume actual value master rqv 40 4 V 400 m h Air volume ac...

Страница 13: ...0 m h Air volume parameters Room negative pressure supply exhaust Air volume setpoint cqV s 40 4 V Master supply air min 20 max 100 nom 1000 m h Master exhaust air min 10 max 100 nom 1100 m h c factor 100 1 2 kg m Air volume actual value master rqv 40 4 V 400 m h Air volume actual value master rqv 40 4 V 440 m h Printed in Switzerland Fr Sauter AG Im Surinam 55 CH 4016 Basle Tel 41 61 695 55 55 Fa...

Отзывы: