background image

 

ASV115 

 

4/13  

www.sauter-controls.com 

cqV.s

10V

100%

0

0

Vmin

Vmax

Vnom

0

5

10V

5

V

r qV

B

116

94

10V

100%

r qV

0

0

V

Vnom

B

1

169

3

damper position

Command signal c

qV.s

 can be configured in various modes via the 

software. Ranges 0…10 V, 2…10 V and free configurable are 
available. This relates to the 0…100% 

nom

 range. 

As standard, the following functions are specified by the factory 
setting for 24 V~ operation of the controller. 

 

Forced operation* AI01 

Designation 

Range 0…10 V 

Range 2…10 V 

Function 

NC = not connected 

-0.69 V 

-0.69 V 

min

 

LOW voltage 

-0.5…0.3 V 

-0.5…2.2 V 

Damper closed 

NORMAL voltage 

0.7…9.8 V 

2.2…9.8 V 

Control range (

var

HIGH voltage 

10.2…11 V 

10.2…11 V 

Control range (

var

OVER voltage 

> 11.4 V 

> 11.4 V 

Damper open 

*) Switching hysteresis is 0.4 V (4%)

 

as the default value

 

 

Seepage suppression 

In order to avert unstable control behaviour around the 

min

, so-

called 'seepages' are suppressed automatically. This suppression 
causes the damper to close if command variable (c

qV.s

 6% of the 

set nominal air volume. 

 

Control resumes when the command variable (c

qV.s

 7.8% of the 

nominal air volume. 
 

Functional diagram c

qV.s

 

 

 

Feedback for damper position (AO02) and actual value for air 
volume (AO03) 

Three measured variables are generally available as a feedback 
from the air volume control loop: damper position, air volume and 
operating pressure. These values can be read with SAUTER CASE 
VAV software in the 

Online

 

monitoring

 mode. 

 

Online monitoring 

Damper position 

° Angle of rotation 

0…100%  angle  of 
rotation 

Actual air volume 

m³/h 

0…100%

nom

 

Operating pressure 

Pa 

0…100% P

nom

 

 

The feedback signal for the damper position can be transmitted as 
an analogue signal via terminal AO02. The value equates to 
0…100% of the maximum permitted angle of the damper. 

 

Functional diagram for damper position 

 

 

The function can be set using Sauter CASE VAV 1.4 or higher, 
which allows one of the following applications for the device to be 
selected: VAV.10.001.M, VAV.20.001.M or VAV.20.001.Sxi. When 
setting the parameters for terminal AO02 using the feedback signal 
for the damper position, it is recommended to perform an adaption 
using 

Manual mode – adapt angle of rotation

. This determines the 

angle between the 'closed' and 'open' damper positions. 
In general, the actual value of the damper position is used for the 
following functions: 

 

 

Display on the BMS, for the purpose of monitoring the primary 
pressure. 

 

Fan control as a function of the various damper positions in the 
installation. 

 

In addition, the current air volume (actual value r

qV

) across the air 

volume box is measured at terminal AO03. The value corresponds 
to 0…100% of the set nominal air volume 

nom

. If no specific plant 

air volume is entered, 

nom

 corresponds to the value 

nAT

 set by 

the box manufacturer, which can generally be found on the specifi-
cation plate of the air volume box. 

 

Functional diagram for r

qV

 

 

 
The form of output signal r

qV 

can be configured in various modes 

using the SAUTER CASE VAV software. Ranges 0…10 V, 2…10 V 
and 'free configurable' are available. 

 

The actual value signal and the command signal always relate to 
the set air volume 

nom

 

 

Note 
Actual value signals from two or more controllers must not be 
connected together. 

 

 
The actual value signal for the air volume is generally used for the 
following functions: 

 

 

To display the air volume on the (BMS) 

 

Master-slave application; the actual value signal from the master 
controller is specified as the setpoint for the slave controller. 

 

The actual value signal r

qV

 can be used to calculate the current air 

volume. For this purpose, the voltage is measured on output AO03 
and is offset against the set nominal air volume. 

Содержание ASV115

Страница 1: ... SLC SAUTER Local Communication protocol Easy to parameterise using the SAUTER CASE VAV software Constant air volume control using parameterisable inputs Technical description Power supply 24 V Variable end values for the differential pressure s measuring range 50 150 Pa 100 300 Pa Efficient control algorithm Output signal 0 10 V for Air volume actual value rq Air volume control deviation eq or fo...

Страница 2: ...nded 7 Recommend hardness of tubes 40 Sha e g silicone 8 Connection 02 can be configured as an analogue input or analogue output using SAUTER CASE VAV software 9 Digital inputs for external potential free contacts gold plated recommended 10 The parametering tool is always one of the subscribers so a maximum of 31 devices can be linked 11 Recommended Belden 3106A Accessories Type Description 052045...

Страница 3: ...switching contact 1 DI04 Factory setting FS Full scale PR Room pressure TR Room temperature Heating Cooling DN Nominal diameter c o Change over ad Index ad for additive p Index p for priority V Index V for air volume s Index s for second priority q Index q for quantity Setting the air volume The following functions are generally available to operate the air volume controller Setting ranges Functio...

Страница 4: ... permitted angle of the damper Functional diagram for damper position The function can be set using Sauter CASE VAV 1 4 or higher which allows one of the following applications for the device to be selected VAV 10 001 M VAV 20 001 M or VAV 20 001 Sxi When setting the parameters for terminal AO02 using the feedback signal for the damper position it is recommended to perform an adaption using Manual...

Страница 5: ...ression and upward limitation is defined by the maximum possible plant air volume damper fully open As an example the calculation and setting of the parallel setpoint shift may be performed as follows In order to obtain the value for the resultant setpoint shift as a per centage of the air volume the configuration of connection AI02 must also be taken into account For example if the input was free...

Страница 6: ...f factor shift 0 AI AO 02 AO not available Sensor block diagram 6 13 www sauter controls com Bus F B10418 1 NC not connected 2 It is recommended to put the setting for forced operation for LOW voltage additionally to Vvar 3 Connection is recognised as LOW voltage and accordingly the factory setting for forced operation is performed other parameters provide different behaviour After applying power ...

Страница 7: ...uitable for continuous operation After parameterisation has been completed the parameter plug must be removed and the opening should be sealed to restore the IP protection type Fitting outdoors We recommend that devices are given additional protection against the effects of weather if installed outside Wiring Power supply To ensure fault free operation the following wire cross sections and lengths...

Страница 8: ...c Double earthed shielding is suitable as a protection against electromagnetic interference e g from frequency converters electric motors coils etc It is advisable to use twisted pairs Additional technical information The upper section of the housing with the lid and the lid release button contains the electronics and the sensor The lower section of the housing contains the brushless DC motor the ...

Страница 9: ...ntroller 2 as standard Taking into account the logical statuses the command signal shifts the parameterised air volume values in the range from min to max With the same setting for these limitations and for the nominal air volume for the installation nom i e the parameterised values on the supply and exhaust air controllers must be the same a set point shift enables a parallel shift of the air vol...

Страница 10: ...etpoint B11698 Plant schematic example 1 Key 1 VAV compact controller ASV115 2 Room temperature controller NRT300 3 Reducing box 4 Building Management System BMS night mode Air volume parameters supply exhaust Air volume setpoint cqV s 40 4 V Master supply air min 20 max 100 nom 1000 m h Master exhaust air min 20 max 100 nom 1000 m h c factor 100 1 2 kg m Air volume actual value master rqv 40 4 V ...

Страница 11: ...to the upstream pressure in the air network due to fluctuations in duct pressure control these disruptions can be detected and transmitted directly to the slave controller This guarantees an equal percentage relationship between the supply and exhaust air controllers The command signal or the actual value signal rqv from the master controller can be connected in parallel to several slave controlle...

Страница 12: ... schematic example 2 Key 1 VAV compact controller ASV115 2 Room temperature controller NRT300 3 Reducing box 4 Building Management System BMS night mode Air volume parameters supply exhaust Air volume setpoint cqV s 40 4 V Master supply air min 20 max 100 nom 1000 m h Slave exhaust air min 10 max 100 nom 1000 m h c factor 100 1 2 kg m Air volume actual value master rqv 40 4 V 400 m h Air volume ac...

Страница 13: ...0 m h Air volume parameters Room negative pressure supply exhaust Air volume setpoint cqV s 40 4 V Master supply air min 20 max 100 nom 1000 m h Master exhaust air min 10 max 100 nom 1100 m h c factor 100 1 2 kg m Air volume actual value master rqv 40 4 V 400 m h Air volume actual value master rqv 40 4 V 440 m h Printed in Switzerland Fr Sauter AG Im Surinam 55 CH 4016 Basle Tel 41 61 695 55 55 Fa...

Отзывы: