12
GPRS-T1
SATEL
Note: If an extra test transmission (using the CLIP service or the GPRS-S
OFT
program
command) is generated, the time before sending the periodical test transmission will
be counted from the beginning.
SMS test transmission
– enter in this field the SMS message body which will be sent as
the converter test transmission to the selected telephone numbers.
Note: If you have defined the time period after which the test transmission is to be sent, and
the "SMS test transmission" field remains blank, SMS messages containing
information on the module status will be sent – as test transmissions – to the selected
telephone numbers (see: "Send SMS with module status to CLIP" option).
Fig. 8. "Test transmissions, CLIP / SMS messaging" tab.
Send test as event to monitoring stations
– if this option is enabled, the converter test
transmission can be sent to the monitoring stations. The method of sending the event code
(SMS, GPRS) depends on the rules defined for each monitoring station in the "GSM
telephone, Monitoring stations" tab. It is necessary to define the event code to be sent.
Event codes for converter test transmission
The table makes it possible to define the codes which will be sent to the monitoring
stations for the converter test transmission.
Format
– format in which the event code will be sent. The formats you can select from are
4/2 (for Ademco Express) or CID (Contact ID). Click twice on the format field to change
the displayed format. If the last converted event was in the SIA format, this format will
be shown in the field.
Code
– event code. For the 4/2 format, 2 characters (digits or letters from A to F) should
be programmed, and for the Contact ID – 3 digits. In case of the Contact ID format, you
can use the code editor. To open the code editor window, click on the button designated
with three dots, available in the "Event" field.