Profile Series v.G1.5 Mortise Exit Device
10/31/16
Step #5 – Exterior Door Options
A. Fire Stop Plate (P/N 52-0033)
Fire-rated doors require a fire stop plate on the outside of the door (Fig.5A).
1. Drill (2) 1/8" x 1-1/4" deep holes in the door if not already present.
Refer to template for fire-stop prep locations.
2. Attach with flap up and out using (2)
#8 x 1/2” self-tapping screws for
wood and metal doors.
Outside of Door
Step #6 – Gasket Installation (for Exterior Doors)
For exterior applications, use a gasket between
escutcheon and outside door surface:
1. Carefully remove the backing from the gasket.
2. Apply gasket to escutcheon carefully.
a. Starting in one place, press the adhesive side
of the gasket firmly against the escutcheon.
b. Work around the escutcheon, pressing the
sticky side of the gasket firmly against the
escutcheon edge.
c. The gasket should be aligned so that all edges
of the escutcheon are covered.
4. Attach escutcheon to the door.
Fig. 6B
Fig. 6A
Fig. 5A
B. Weather Conduit (P/N 52-2847)
Install weather conduit on
NON FIRE-RATED
exterior doors only.
1. Carefully insert the weather conduit
into the ribbon cable hole on
the inside of the door (Fig 5B).
2. Place the O-ring around the
weather conduit on the outside
and up against the door (Fig. 5C).
Fig.5B
Ribbon Cable Hole
Fig.5C
O-Ring
Outside of Door