Fire rated power operated doors must close and latch during a fire alarm condition. Ensure
proper procedures have been followed to allow a main power disconnect during a fire alarm
condition. Always check to ensure compliance to local building codes.
o
Upon job completion, always perform a functional test to ensure that the door(s)
close and latch following a power loss.
•
Other hardware may be required to complete the installation. For example, for pairs of
doors, if an Astragal is installed, a mechanical door coordinator may be required to ensure a
proper coordinated closing during a power loss.
•
Only fire rated hardware shall be used on a fire rated door & frame assembly.
•
Ensure the operator that is being installed has the proper fire rated label applied to the
header.