Installation and Wiring
15
For maintenance of the UPS, provide space of
at least approximately 1 meter (40 inches) at
the front and at least approximately 50 cm (20
inches) at the back.
§
6
6
.
.
I
I
n
n
s
s
t
t
a
a
l
l
l
l
a
a
t
t
i
i
o
o
n
n
a
a
n
n
d
d
W
W
i
i
r
r
i
i
n
n
g
g
Install the UPS in the installation location, attach the LCD panel, and perform the wiring work. When
installing and wiring the UPS, carefully follow the instructions in this instruction manual.
§
6
6
.
.
1
1
I
I
n
n
s
s
t
t
a
a
l
l
l
l
a
a
t
t
i
i
o
o
n
n
CAUTION
!
Installation work should be performed only by technically qualified personnel.
When installing the UPS, carefully follow the instructions in this Instruction
Manual. Improper installation can result in electric shock, bodily injury, and/or fire.
In accordance with the instruction manual, install the UPS on a stable surface that can bear
the 61kg (134.5 lbs). This surface should be flat, so the UPS cannot fall and cause bodily
injury. The possibility of vibration and shock should be minimized at the installation
location. Shock and vibration from, for example, an earthquake may cause the UPS to shift
or fall, possibly resulting in bodily injury.
For safety, wear protective shoes when performing installation work. All work that involves
lifting the UPS, such as attaching the brackets, should be carried out by at least two
persons. There is the danger that the UPS may fall or be dropped, resulting in bodily injury.
Also, be careful to avoid straining your lower back.
Be careful not to trap a hand or the like when attaching the brackets and installing the UPS.
There is the danger that the UPS could fall or be dropped during relocation or installation.
Always hold the bottom side of the UPS firmly with both hands. Failure to do so may result
in bodily injury or damage to the UPS.
§
6
6
.
.
1
1
.
.
1
1
C
C
h
h
e
e
c
c
k
k
i
i
n
n
g
g
I
I
n
n
s
s
t
t
a
a
l
l
l
l
a
a
t
t
i
i
o
o
n
n
E
E
n
n
v
v
i
i
r
r
o
o
n
n
m
m
e
e
n
n
t
t
Suitable installation environment: Ambient temperature
of 0 to 40°C (32 to 104°F) and relative humidity of 20 to
90%
Do not install the UPS in the following locations:
Where grounding is not possible.
Where the ambient temperature exceeds 40°C (104°F).
Where high humidity may occur.
Where corrosive gas or salt spray may be present.
Where it may be subject to vibration and shock.
Where dust may accumulate.
§
6
6
.
.
1
1
.
.
2
2
C
C
h
h
e
e
c
c
k
k
i
i
n
n
g
g
I
I
n
n
s
s
t
t
a
a
l
l
l
l
a
a
t
t
i
i
o
o
n
n
S
S
p
p
a
a
c
c
e
e
During installation, provide the following space around the UPS.
At least 20 cm (approx. 8 inches) at the front and at least 15 cm (approx. 6 inches) at the back:
As air intake or exhaust space for the cooling fan.
At least 1 meter (approx. 40 inches) from CRT displays:
To allow for slight leakage of magnetic flux.
Allow some space from devices which might be affected by magnetic flux.
At least 1 m
(40 inches)
At least 20 cm
(8 inches) at front
Notes on installation
The battery service life will be foreshortened if the UPS
is used in an environment where the ambient
temperature exceeds 30°C (86°F). We recommend that
the UPS is normally used and maintained at a
temperature between 20 to 25°C (68 to 77°F).
Note
At least 15 cm
(6 inches) at back
Содержание SANUPS A11J
Страница 1: ...M0009237 5 kVA Instruction Manual ...
Страница 25: ...Installation and Wiring 22 Blank page ...
Страница 41: ...Troubleshooting 38 Blank page ...
Страница 50: ...Blank page ...
Страница 51: ...Blank page ...
Страница 52: ......