Indoor Unit
SAP-K127GHAX
Outdoor Unit
SAP-C127GHAX
Insulation of Refrigerant Tubing
Because capillary tubing is used in the outdoor unit, both the
wide and narrow tubes of this air conditioner become cold. To
prevent heat loss and wet floors due to dripping of
condensation,
both tubes must be well insulated
with a
proper insulation material. The thickness of the insulation
should be a min. 8 mm.
After a tube has been insulated,
never try to bend it into a narrow
curve because it can cause the tube
to break or crack.
Wide tube
Thickness:
Min. 8 mm
Insulation
Narrow tube
Thickness:
Min. 8 mm
IMPORTANT
CAUTION
20
Compressor
4-way
valve
Accumulator
Wide tube
service
valve
Wide tube
O.D.
12.7 mm
(1/2 ")
Narrow
tube
service
valve
Narrow tube
O.D.
6.35 mm
(1/4")
Heat exchanger
Heat exchanger
Cooling cycle
Heating cycle
t
i
n
u
r
o
o
d
t
u
O
t
i
n
u
r
o
o
d
n
I
Capillary tube
(for heating)
Check
valve
Capillary tube
both for heating
and cooling
(
)
Содержание 1 852 351 85
Страница 2: ...SANYO Electric Co Ltd Jul 2009 R D center ...
Страница 18: ...3 DIMENSIONAL DATA Indoor Unit SAP K77GHAX SAP K97GHAX SAP K127GHAX 16 ...
Страница 83: ...SANYO Electric Co Ltd Jul 2009 R D center ...
Страница 92: ......
Страница 93: ......
Страница 94: ......
Страница 95: ......
Страница 96: ......
Страница 97: ......
Страница 99: ...3 DIMENSIONAL DATA Indoor Unit SAP K77GHAX SAP K97GHAX SAP K127GHAX 16 ...
Страница 113: ......
Страница 123: ......
Страница 124: ......
Страница 125: ......
Страница 136: ...C 53 ON 1 ...
Страница 137: ......
Страница 146: ......
Страница 149: ......
Страница 150: ......
Страница 151: ......
Страница 152: ......
Страница 153: ......
Страница 154: ......
Страница 155: ......
Страница 156: ......
Страница 157: ......
Страница 158: ......
Страница 159: ......
Страница 160: ......
Страница 161: ......
Страница 162: ......
Страница 163: ......
Страница 164: ...SANYO Electric co Ltd Nov 2008 R D center ...