8-3. Automatic Switching between Cooling and Heating
When AUTO mode is selected, the microprocessor calculates the difference between the set temperature and
the room temperature, and automatically switches to COOLING or HEATING mode to maintain the desired
temperature.
Room temp. Set temp. COOL
Room temp. < Set temp. HEAT
This means that if the room temperature is higher than or equal to the set temperature, COOLING operation
begins. If the room temperature is lower than the set temperature, HEATING operation begins.
NOTE
Example of operation in the AUTO mode with the set room temperature at 23 C.
27
26
25
24
23
22
21
20
A
B
C
C
B
A
Zone
19
If one of the following conditions occurs, the air conditioner changes the
operation mode (from cool to heat or vice versa).
ZONE A:
ZONE B:
ZONE C:
F
F
O
F
F
O
Compressor
Operation mode
Room temperature
Heating
g
n
il
o
o
C
g
n
il
o
o
C
ON
ON
ON
More than
1 hour
Within
1 hour
Example:
The mode changes if the difference between the room
temperature and the set temperature is at least 3 C.
The mode changes if the difference between the room
temperature and the set temperature is at least 1.5 C.
if 1-hour has elapsed after the compressor is stopped.
The mode does not changes if the difference between the
room temperature and the set temperature is within 1.5 C.
Set temp.
47
Содержание 1 852 351 85
Страница 2: ...SANYO Electric Co Ltd Jul 2009 R D center ...
Страница 18: ...3 DIMENSIONAL DATA Indoor Unit SAP K77GHAX SAP K97GHAX SAP K127GHAX 16 ...
Страница 83: ...SANYO Electric Co Ltd Jul 2009 R D center ...
Страница 92: ......
Страница 93: ......
Страница 94: ......
Страница 95: ......
Страница 96: ......
Страница 97: ......
Страница 99: ...3 DIMENSIONAL DATA Indoor Unit SAP K77GHAX SAP K97GHAX SAP K127GHAX 16 ...
Страница 113: ......
Страница 123: ......
Страница 124: ......
Страница 125: ......
Страница 136: ...C 53 ON 1 ...
Страница 137: ......
Страница 146: ......
Страница 149: ......
Страница 150: ......
Страница 151: ......
Страница 152: ......
Страница 153: ......
Страница 154: ......
Страница 155: ......
Страница 156: ......
Страница 157: ......
Страница 158: ......
Страница 159: ......
Страница 160: ......
Страница 161: ......
Страница 162: ......
Страница 163: ......
Страница 164: ...SANYO Electric co Ltd Nov 2008 R D center ...