8-4. Freeze Prevention (Cooling and Dry)
This function prevents freezing of the indoor heat exchange coil.
When the temperature of the indoor heat exchange coil falls below 2 C for 2 minutes, the control circuit stops
the outdoor fan and compressor (The compressor stops 3 seconds after the outdoor fan stopped). During this
period, Indoor fan operates in LL. The outdoor fan does not start again until the temperature rises above 6 C.
(The compressor starts 2 seconds after the outdoor fan started.)
Outdoor fan
Compressor
Indoor fan
6 C
Indoor heat
exch. coil
temp.
2 C
ON
At least
approx. 2 min.
3 sec.
OFF
OFF
ON
ON
ON
Set Speed
Set Speed
LL
2 sec.
48
Содержание 1 852 351 85
Страница 2: ...SANYO Electric Co Ltd Jul 2009 R D center ...
Страница 18: ...3 DIMENSIONAL DATA Indoor Unit SAP K77GHAX SAP K97GHAX SAP K127GHAX 16 ...
Страница 83: ...SANYO Electric Co Ltd Jul 2009 R D center ...
Страница 92: ......
Страница 93: ......
Страница 94: ......
Страница 95: ......
Страница 96: ......
Страница 97: ......
Страница 99: ...3 DIMENSIONAL DATA Indoor Unit SAP K77GHAX SAP K97GHAX SAP K127GHAX 16 ...
Страница 113: ......
Страница 123: ......
Страница 124: ......
Страница 125: ......
Страница 136: ...C 53 ON 1 ...
Страница 137: ......
Страница 146: ......
Страница 149: ......
Страница 150: ......
Страница 151: ......
Страница 152: ......
Страница 153: ......
Страница 154: ......
Страница 155: ......
Страница 156: ......
Страница 157: ......
Страница 158: ......
Страница 159: ......
Страница 160: ......
Страница 161: ......
Страница 162: ......
Страница 163: ......
Страница 164: ...SANYO Electric co Ltd Nov 2008 R D center ...