17
5
Operation for over
current limit high
ALm: Alarm only
OFF: Cut off output
Cnt: Output control
6
Operation for line
failed
ALm: Alarm only
OFF: Cut off output
7
Operation for over
temp.
ALm: Alarm only
OFF: Cut off output
8
Input filter
0~10 sec.
Against for fluctuation
9
Wait time for un-load 0~254 sec.
If set to ‘0’ stop the
function.
10
Operation for internal
buzzer
OFF, ON
OFF: Disable
On: Enable
5
11
Remote set value
0~100%
12
Select input
Analog,
COm
AnA:Analog (4~20mA)
COm: Interface
15
Note) If set to the ‘Com’ on parameter no 12, TPR output will control by the
remote set value of parameter no. 11.