10
the parameter has not been accepted.
4) By pressing [ENT] key this value is accepted and entered into EEPROM
(nonvolatile memory). When the accepted the decimal point disappears.
z
Enter password to access parameters setting group. Password is “5”.
z
Enter password to access interface parameters setting group. Password
is “15”.
5) If pressing [PAR] key, can be select each parameters when entered pass value.
6) Set parameter value after select using parameter.
7) Once finished changing parameter values, pressing [PAR] key for more than 2
seconds returns the controller to normal operation and the process value will be
displayed. Waiting approximately 80 seconds without pressing the key will return the
meter to normal operation as well.
4.4 Parameters
See table no. 3 for setting parameters.
Table 3. Parameter list
No. Symbol
Setting
Data
Range
Operation
PASS
0 -
Indicating
Changeable display of
input signal or load
current by [ENT] key.
1
PASS number
Protection of operating
parameter
None
2
Output limit high
0~100%
Disable when
connected external
VR.
3
Load current limit
high
5~240A
5