11
4
Soft Start time
1~250 sec.
If set to ‘0’ stop the
function.
5
Operation for over
current limit alarm.
ALm: Alarm only
OFF: Cut off output
Cnt: Output control
6
Operation for line
failed alarm.
ALm: Alarm only
OFF: Cut off output
7
Operation for over
temperature alarm.
ALm: Alarm only
OFF: Cut off output
8
Input Filter
0~10 sec.
Against for fluctuation
9
Wait time for un-load
alarm.
0~254 sec.
If set to ‘0’ stop the
function.
10
Operation for internal
buzzer.
OFF, ON
OFF: Turn off
On: Turn on
5
11
Select input
Analog,
Interface
AnA: Analog (4~20mA)
COm: Interface
12
Address for interface
0~31
RS 485 address
13
Speed for interface
2400, 4800,
9600bps
RS 485 speed
14
Delay time for
interface
1~4
Delay time for reply
15
4.5 Wiring and Operating According to Control Signal
1) 4~20mA Current Input Signal
This is frequently used operation for control. Control signal is 4~20mA dc current.
Maximum output voltage is limited by external V.R or OUt parameter value.
Note 1) In case of connect external V.R, keep the terminals number.
Note 2) If connect external V.R, at G1, G2, and G3 terminal, disable internal parameter
OUt automatically.