3. Specifications
Part Number:
4034180
Blower:
309 CFM @ 0.0" WG
Power:
640 watts @ 80°F and 60% RH
Supply Voltage:
115 volt – 1phase – 60 Hz
Current Draw:
5.7 amps
Operating Temp.:
49°F Min., 95°F Max.
Sized for:
2,200 Sq. Ft. - Typical
Miniumum Performance at 80°F and 60% RH
Water Removal:
90 Pints/Day
Efficiency:
6.1 Pints/kWh
Energy Factor:
2.88 L/kWh
Air Filter:
MERV-8, Standard Pleat
Size: 14" x 17.5" x 2"
Power Cord:
9', 115 VAC, Ground
Drain Connection:
3/4" Threaded Female NPT
Drain Hose:
8' Direct Gravity Drain Hose
(5/8" ID x 7/8" OD)
Refrigerant Type:
R410A (Refer to manufacturers label
for more information)
Refrigerant Amount:
1 lb. 5 oz.
Dimensions: Unit Shipping
Width: 14.5"
23"
Height: 19.4"
30"
Length: 26"
40"
Weight:
80 lbs.
95 lbs.
4. Installation
CAUTION!
Remove compressor shipping
tie from the unit. Failure to remove shipping tie
will cause excess vibration to be transmitted to
the frame.
4.1 Remove Compressor Shipping
Support
The Santa Fe Advance2 uses
a compressor to power the
refrigeration system. To protect the
compressor and refrigeration system during shipping a plastic
tie wrap secures it to the units frame. Remove the tie wrap by
cutting the tie wrap and pulling from the unit as shown. After
removing tie wrap, insert plastic plugs provided into the holes.
4.2 Location
The Santa Fe Advance2 can be installed in a variety of locations
to meet the owner’s needs; other considerations include:
1. Providing access to a 115 VAC power outlet (10' power
cord is provided).
2. Locating near a floor or other suitable drain.
3. Mount 4" above drain.
4. Do not install the Santa Fe Advance2 with the exhaust of
the unit within 1' of a wall or obstruction. Do not place the
unit near open water.
4.2A No Ducting (Figure 1)
The simplest installation is to place the Santa Fe Advance2
with no ducting. To ensure optimal performance, the air inlet
and the outlet of the unit must be at least 1' from walls and
other obstructions to air flow.
4.2B Duct Outlet (Figure 2)
Dehumidification performance can be modified by adding an
outlet duct to circulate air.
4.2C Remote Area, w/Outlets Ducted (Figure 3)
A simplified remote installation method than above uses
ducting between the Santa Fe Advance2 discharge and the
humid room; the Santa Fe Advance2 inlet draws air from
the room in which it’s located. This works well if there is an
adequate air flow path between the two rooms; e.g. high door
undercut, louvered door or wall grill. This eliminates the need
to remote mount the humidity control.
SANTA FE ADVANCE2 OWNER’S AND INSTALLER’S MANUAL
3
Santa Fe Advance2 Installer’s & Owner’s Manual
Input of
Humid Air
Output of
Dehumidified Air
Front View
Figure 2: Installation in humid area
with outlet ducting
Input of
Humid Air
Output of
Dehumidified Air
Front View
Figure 1: Installation with no ducting.