background image

 WARNING!

4.3 Electrical Requirements

The Santa Fe Advance2 plugs into a common grounded outlet 
on a 110-120 VAC  15-Amp circuit. While operating, it draws 
less than 6 amps @ 80°F, 60% RH and less than 5.5 amps @ 
75°F, 50% RH. Use of a ground fault circuit interrupter (GFCI) 
protected circuit is recommended. The unit should not be used 
in areas prone to flooding.

 

4.4 Installing Feet

Included with your Santa Fe 
Advance2 are four leveling 
feet. It is important to level the 
unit for proper draining. 

Installing Leveling Feet  

See Figure 2 for installing leveling feet.
1.  Lay down a protective pad (pillow, blanket, etc.).
2.   Carefully turn unit onto side opposite drain port.

3.   Align leveling foot shaft with one of the four threaded 

hole locations as shown in Figure 2.

4.  Screw each leveling foot in ten revolutions.
5.  Carefully bring unit to upright position.
6.   Level unit for proper water drainage.
7.  Wait 10 minutes before operating.

 CAUTION!

Note: Operating the unit immediately after bringing it to an 
upright position can possibly damage the compressor. A 
short amount of time is needed (10 minutes) to allow the oil 
to return to it’s reservoir for lubrication.

 CAUTION!

 

 

For proper drainage, the 

unit must be mounted so the drain outlet is at 

least 4" above the floor drain, and must be fully 

supported under the base.

4.5 Condensate Water Removal

The Santa Fe Advance2 drains via gravity, therefore, it does not 
have the ability to push condensate (water) uphill. The drain 
hose must run downhill toward the drain location. Condensate 
can be drained by using the 5/8” clear vinyl hose and the 3/4” 
threaded adapter provided. Ensure the threaded adapter is 
threaded in tightly.

 CAUTION!

The Santa Fe Advance2 drains via gravity, therefore, it does not 
have the ability to push condensate (water) upwards. The drain 
hose must run down towards the drain location. Condensate 
can be drained by using the 5/8” clear vinyl hose and the 3/4” 
threaded adapter provided. Ensure the threaded adapter is 
threaded in tightly.

 CAUTION!

The Santa Fe Advance2 requires a drain trap. Creating a drain 
trap allows a small amount of water to build up in the trap area 
of the clear hose. This prevents air from back flowing through 
the hose and into the dehumidifier; essentially causing the unit 
to backflow water out of the corners of the machine. Position 
the trap in the hose approximately 8"-10” from the dehumidi-
fier and make sure the highest point of the trap is still at least 
2”below the black drain port adapter on the dehumidifier. If the 
highest point of the trap is above the drain port, water will back 
flow into the dehumidifier. Check the hose regularly to ensure 
water is draining properly.
Several trap options include:

SANTA FE ADVANCE2 OWNER’S AND INSTALLER’S MANUAL

4

Santa Fe Advance2 Installer’s & Owner’s Manual

Figure 1: Four leveling feet

Figure 2: Insert leveling feet 
in locations

CONDITIONED SPACE

Input of

Humid Air 

Output of

Dehumidified Air 

Figure 3: 
Installation in 
a remote area 
with ducted 
outlets

Pretzel Loop

Pretzel Loop

Floor Bend

PVC Trap

PVC materials available from 
your local hardware store.

Standard Loop

Содержание 4034180

Страница 1: ...33 7533 www Santa Fe Products com Designed for Basement and Crawlspace Dehumidification n High capacity n High efficiency n Environmentally friendly n Patent pending dual air distribution INSTALLER S OWNER S MANUAL P N 4034180 Serial No ________________________ Install Date ___________ Sold by Patent Pending Dual Air Distribution ...

Страница 2: ... leaving the unit unattended ensure children do not have access to the equipment Do not allow children to play with or near the unit or in its air flow The unit is designed to be installed indoors only Read the installation operation and maintenance instructions carefully before installing and using this unit Proper adherence to these instructions is essential to obtain maximum benefit from your S...

Страница 3: ...2 can be installed in a variety of locations to meet the owner s needs other considerations include 1 Providing access to a 115 VAC power outlet 10 power cord is provided 2 Locating near a floor or other suitable drain 3 Mount 4 above drain 4 Do not install the Santa Fe Advance2 with the exhaust of the unit within 1 of a wall or obstruction Do not place the unit near open water 4 2A No Ducting Fig...

Страница 4: ...drain hose must run downhill toward the drain location Condensate can be drained by using the 5 8 clear vinyl hose and the 3 4 threaded adapter provided Ensure the threaded adapter is threaded in tightly CAUTION The Santa Fe Advance2 drains via gravity therefore it does not have the ability to push condensate water upwards The drain hose must run down towards the drain location Condensate can be d...

Страница 5: ...ill cause the unit s internal impeller to run continuously whether the unit is dehumidifying or not This function is desirable if the unit is used for air circulation Turning the fan switch to FAN AUTO will cause the unit s internal blower to run only while the unit is dehumidifying 7 Maintenance CAUTION NOTE Do not operate the unit without the filter or with a less effective filter The heat excha...

Страница 6: ...pressor run capacitor n Blower runs with fan switch AUTO but compressor cycles on off 1 Low ambient temperature and or humidity causing unit to cycle through defrost mode 2 Defrost thermostat defective 3 Defective compressor overload 4 Defective compressor SANTA FE ADVANCE2 OWNER S AND INSTALLER S MANUAL 6 Santa Fe Advance2 Installer s Owner s Manual n Blower does not run with fan switch in either...

Страница 7: ...11 Wiring Diagram SANTA FE ADVANCE2 OWNER S AND INSTALLER S MANUAL 7 Santa Fe Advance2 Installer s Owner s Manual ...

Страница 8: ...to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer Customer Responsibilities As a further condition to obtaining warranty coverage hereunder the Customer must send a valid warranty claim to Therma Stor such that Therma Stor receives such claim prior to the end of the applicable warranty period ...

Страница 9: ......

Страница 10: ......

Страница 11: ......

Страница 12: ...1 800 533 7533 www santa fe products com ...

Отзывы: