Version
:
170720
SANJIANG ELECTRONICS
3
4.
Installation of Agent Releasing Device
Structure of the agent releasing device and the main parts is shown in Figure 4.
l
First ensure the outlet elbow of the electromagnetic valve is firmly placed and the outlet of the elbow is
vertically upward, and then carefully move the storage device into the cabinet. Short steel pipes can be
used as rollers to push the storage device into the cabinet; be careful with the aluminum alloy profiles of
the cabinet.
l
Thin steel strip in the middle of cabinet is used to fix the storage steel cylinder in the cabinet.
l
Connections between pipes and pipe accessories have been installed before leaving factory as is
shown in figure 4. Note that the outlet of pipes should be aligned with the hole in the spray head on the
panel of cabinet.
l
Install the spray head, a screwdriver can be used to tighten the spray head into the small hole
.
l
Confirm the place of the agent releasing device. The principle is to place it by wall for convenient
installation and maintenance. Check the load of the floor when necessary. Adjusting screws are placed
at four corners of the bottom plate of the cabinet to ensure that the cabinet is stable.
5.
System Connection
Schematic diagram of system connection is shown in figure 5
Figure 4
Figure 3
Содержание JTW-ZD-01K