5

Note:

l

In area n (n=1-4), zone 1 connects with conventional smoke detector JTY

GD

01K; While the

connection is in open circuit, the system will alarm that zone 1 of area n has trouble; while the detector
alarms or the connecting wire is in short circuit, the system will alarm that zone 1 of area n has a fire
alarm.

l

In area n (n=1-4), zone 2 connects with conventional thermal detector JTW-ZD-01K; while the

connection is in open circuit, the system will alarm that zone 2 of area n has trouble; while the detector
alarms or the connecting wire is in short circuit, the system will alarm that zone 2 of area n has a fire
alarm.

l

The detector should be connected in serial (as shown in figure 5 and figure 6), the method of connection

is: connect the base of the first detector with terminal1# and 3# (the connection has no positive or
negative polarity); connect terminal3# of the next detector with terminal2# of the previous detector. The
terminal1# of each should be connected; a 10k/0.25w load resistance should be in parallel connection
with terminal1# and 2# on the base of the last detector.

l

The detector in zone 1 of area n respectively connects terminal 8# & 9# of (area n) control board; the

detector in zone 2 respectively connects terminal 7# & 9# of (area n) control board.

l

The connection of (area n) bell respectively connects terminal 25# & 26# of (area n) control board; when

any zone of area n rings a fire alarm, the control panel will send out signal to ring the alarm bell of area
n.

l

The connection of (area n) electromagnetic valve respectively connects terminal 28# & 29# of (area n)

control board, when the system judges that an emergency has happened in area n, terminal 29# of area
n will send DC24V signal.

l

The system will start area n (n=1-4) Releasing Device in the following two status:

Status Description

Remark

1

The system is in automatic status, there are fire alarms in zone 1&2 of area n
at the same time and it is delayed for 20 seconds

Non-pause

status

2

The emergent release button on the control panel of area n is pressed
properly and it is delayed for 20 seconds

Non-pause

status

Note

:

When the release is completed, the main panel will display the time of release in blinking,

blinking

00

on the area panel shows release is completed in the area.

l

Schematic diagram of the control panel

s inside connection is shown in figure 7.

l

Inside structure of the control panel is shown in figure 8, the meaning of each is as follows:

6.

The Connection of the Power Supply

JB-QB-QM200/4 adopts 220V 50Hz single-phase AC. When the AC supply voltage fluctuates between

AC187V-AC242V, the power supply will work normally and keep on charging the battery (if the battery is not
fully charged); if the AC input exceeds this range, the AC supply (AC-DC) module will enter protected status,
and the system will switch to be supplied by battery until the AC input turns normal. If it is fully charged, the
backup battery can maintain normal working (normal monitoring status) of the system for 48 hours.

Therefore, ensure that the AC supply of the system can be between AC187V-AC242V for a long time and

the time of power cut will not exceed 48 hours.

Note: AC input of the system should not exceed 320V; otherwise parts of the apparatus in the

system will be damaged.

The backup battery uses two DC12V/7.0AH storage batteries, the connection is shown in figure 9. There

are two wires elicited from the terminal of PS-06 power module in the control panel, among them one
terminal(BT+) connects the red wire, another(BT-) connects the black wire. Connect the red wire with "+" pole

1

Main display board

2

Area 1 display board

3

Area 2 display board

4

Area 3 display board

5

Area 4 display board

6

Below the splint- area 1 control board

above is area 3 control board

7

Below the splint

area 2 control board

above is area 4 control board

8

Main control board

9

PS-06 power module

10

Backup battery

11

Splint, used to fix area control board

Warning: In the process of installation, troubleshooting or maintenance, all electromagnetic
valves must be removed from the various parts they

ve driven. Thus, it can ensure that

mis-operation or wrong connection of the Extinguishing Device is avoided.

Warning: A relay of high-power is necessary when driving several electromagnetic
valves (the current is>3A) simultaneously, but the check of release trouble will be
unavailable.

Содержание JTW-ZD-01K

Страница 1: ...Multi Area Agent Releasing Control System ...

Страница 2: ...Keyboard Operation 8 VII Power Management for the Control Panel 8 VIII System Adjustment 9 IX System Maintenance 10 X General Troubleshooting 10 Warning The system may be damaged in the area where the input of AC power supply is beyond AC 270V for long time unless AC 220V is connected with the voltage stabilizer Power for the voltage stabilizer must be over 300W ...

Страница 3: ...s and resumes automatically when trouble is solved n Full electrical switch of AC and DC power supply n Monitor the status of backup batteries against overcharge and overdischarge Low consumption design 7 0 AH battery the system can work on up to 48 hours n Protect the keyboard by a lock to prevent wrong operation n HFC 227ea Low poison efficient extinguishing with no impact on ozonosphere n HFC 2...

Страница 4: ...g surface with the hanging hole in the back of the box and ensure there is enough room for the wiring and the opening of the control panel The installation dimension is shown in figure 1 size unit mm Note l At least the space of 1 meter needs to be saved for the operation on the front of the control panel l For the outlet hole on the top of the box at least the space of 0 3 meter needs to be saved...

Страница 5: ...x the storage steel cylinder in the cabinet l Connections between pipes and pipe accessories have been installed before leaving factory as is shown in figure 4 Note that the outlet of pipes should be aligned with the hole in the spray head on the panel of cabinet l Install the spray head a screwdriver can be used to tighten the spray head into the small hole l Confirm the place of the agent releas...

Страница 6: ... AC220V 50Hz JTY GD 01K 1 2 3 10K 1 2 3 10K JTW ZD 01K JTW ZD 01K 1 2 3 1 2 3 Figure 8 11 Figure 7 Area control board input output terminal 1 2 4 3 6 5 7 8 9 10 11 13 12 15 14 16 17 22 19 18 20 21 24 23 25 30 27 26 28 29 31 32 3 2 1 4 3 4 2 1 3 4 2 1 3 1 4 2 3 1 4 2 3 1 4 2 JTY GD 01K JTW ZD 01K Terminal load 10K Terminal load 10K Alarm Bell Eelectromagnetic valve ...

Страница 7: ...elayed for 20 seconds Non pause status Note When the release is completed the main panel will display the time of release in blinking blinking 00 on the area panel shows release is completed in the area l Schematic diagram of the control panel s inside connection is shown in figure 7 l Inside structure of the control panel is shown in figure 8 the meaning of each is as follows 6 The Connection of ...

Страница 8: ... power module DC TROUBLE The light is on when the battery connection is in open circuit or DC voltage is lower than 22V SYSTEM RELEASE When anyone area enters release status and start up the electromagnetic valve this light will be on SYSTEM FIRE When any detector zone finds fire alarms this light will be on SYSTEM TROUBLE When the system detects abnormity such as AC DC trouble release trouble zon...

Страница 9: ...MANUAL AUTO SILENCE SYSTEM RESET SYSTEM TEST MANUAL AUTO PAUSE HOUR QUERY MINUTE ZONE1 FIRE ZONE1 TROUBLE ZONE2 FIRE ZONE2 TROUBLE EMERGENT STOP RELEASE TROUBLE INPUT TROUBLE OUTPUT TROUBLE MANUAL RELEASE RELEASE DELAY RELEASE STARTUP RELEASE CONFIRM DELAY TIME EMERGENT RELEASE ZONE1 FIRE ZONE1 TROUBLE ZONE2 FIRE EMERGENT STOP RELEASE TROUBLE INPUT TROUBLE OUTPUT TROUBLE MANUAL RELEASE RELEASE DEL...

Страница 10: ...udible alarm changes in the following sequence trouble sound fire alarm sound release countdown sound release alarm sound MANUAL AUTO Press this key to switch between automatic and manual mode PAUSE This key pressed the system will switch to the pause mode and the indicator light will be on When any area of the system is in release delay status the keyboard lock doesn t limit the key That is wheth...

Страница 11: ...isconnect the detector fix the base and then rotate the detector counter clockwise to an angle The installation is just contrary but attention needs to be paid to the inhibiting device between the detector and the base the position should not be exceeded when rotating the detector 5 Turn on the power supply of the control panel turn on the AC DC switch on the power module and check whether the con...

Страница 12: ...c The system components should have no collision distortions and other mechanic damages without rust on the surface The coating should be perfect the nameplate should be clear shield lead sealing and safety mark of the manual equipment should be complete 3 Pointer on the pressure gauge of the storage device should be in the green zone please pressurize or report to us if the pointer is lower than ...

Страница 13: ...ck whether the keyboard lock is on and the keyboard light is on when the keyboard lock is off keys are invalid except the key silence and emergent release the key pause is controlled by the keyboard lock except when the control panel is in the state of release countdown Symptom On the control panel AC DC indicator lights are on at the same time When AC has no input or exceed the range of safety vo...

Отзывы: