Version
:
170720
SANJIANG ELECTRONICS
1
I. Overview
Multi-area Agent Releasing Control System includes JB-QB-QM200/n
(
n
=
2
-
4
)
Agent Releasing Control
Panel (hereinafter briefed as JB-QB-QM200/4 or the control panel, with JB-QB-QM200/4 agent releasing control
panel as the main) and agent releasing device, HFC-227ea heptafluoropropane
(hereinafter briefed as
HFC-227ea) agent , smoke detector (JTY
-
GD
-
01K), thermal detector (JTW
-
ZD
-
01K), alarm bell (or fire
alarm sounder, hereinafter alarm bell represent), etc. It is applicable to fully put out electrical fire, liquid fire or
fusible solid fire, fire on solid surface and gas fire. It can be used safely and effectively in most places, such as the
computer room, communication equipment room, power distribution room, precise instrument room, generator
room, oil depot, chemical flammable materials warehouse and stack room, file room, cashbox, etc.
II. Features
n
Detect and alarm simultaneously by smoke and thermal detector in each area
n
Hardware WATCHDOG and software filtering algorithm
n
Check electromagnetic valve connection for the trouble of open circuit.
n
Max. delay timer for fire alarm is 2 seconds
n
High-power: the start-up time of electromagnetic valve in each area can be different, which can reach
3A/DC24V, with the control panel output of 6A/DC24V.
n
Release delay timer: 20 seconds.
n
Distinguish the alarms of trouble/fire/release delay/release.
n
Control panel alarms when trouble occurs and resumes automatically when trouble is solved.
n
Full electrical switch of AC and DC power supply.
n
Monitor the status of backup batteries, against overcharge and overdischarge; Low-consumption
design-7.0 AH battery, the system can work on up to 48 hours.
n
Protect the keyboard by a lock to prevent wrong operation.
n
HFC
-
227ea: Low poison, efficient extinguishing, with no impact on ozonosphere
n
HFC
-
227ea: Clean after fire extinguishing, with no electric medium.
n
Agent releasing control device can be directly placed in a protected room without the need to arrange
another room; the installation is convenient.
n
Complies with:
ü
GB16806-1997
“
General Technical Conditions of control for Fire Protection Equipment
”
in China
ü
ISO9001
“
Quality Assurance System
”
III. Technical Parameters
1. Main Technical Parameters for the Control Panel
Input Voltage
AC220V
Output Power
165W
Max Output Current
6A
Battery Capacity
2
×
7.0Ah DC12V
Max Output Current for Start-up of Extinguishing Device
3A(last 10 secs)
Max Output Current for Alarms
1A
Operation Environment
Temperature
:
0
℃~
50
℃
Humidity
:
≤
95%
(
noncondensing
)
Cabinet Dimensions
(
Length
×
Width
×
Height
)
460mm
×
144mm
×
620mm
2. Main Technical Parameters of the Detector
JTY-GD-01K
JTW-ZD-01K
Operating
Voltage
DC24V
DC24V
Supervisory
Current
<
50
µ
A
<
50
µ
A
Current for
Alarm
<
10mA
<
10mA
Operating
Environment
Temperature
:
-10
℃~
+55
℃
Humidity
:
≤
95%
(
40
℃)
Temperature
:
-10
℃~
+55
℃
Humidity
:
≤
95%
(
40
℃)
Base
DZ-GD-01K
DZ-ZD-01K
Connection
Non-polarity two-wire system
Non-polarity two-wire system
Installation
Ceiling Exposure
Ceiling Exposure
Protected
Zone
60m
2
(height h
<
6m)
30m
2
(
height h
<
8m
)
Cabinet
dimensions
Φ
100
×
40mm
Φ
100
×
30mm
Содержание JTW-ZD-01K