SANJIANG ELECTRONICS

10

Note:

1. After testing, first remove power supply (include AC power and DC power) and reinstall the

electromagnet (As shown in figure 4), apply power again to ensure normal operation of the device.

2.

The spur guard on electromagnetic valve is used for locking cam deflector rod, which can be pulled
down only after drawing out spur guard when starting the container valve manually. Locking of cam
deflector rod will not influence nitrogen startup of electromagnetic valve.

3. The safety blade installed on the electromagnetic valve is used for avoiding wrong motion caused

by collision and shaking during transportation, installation and debugging. Before using
electromagnetic valve when system test is finished and the electromagnet is positioned, the safety
blade must be taken off, then the four setscrews of electromagnet should be fixed, otherwise
electromagnetic valve can

t be switched on. The safety blade can also be placed on one side of the

cabinet for re-fitting when moving bottles.

4. The safety circlip is used for locking manual lever, which can be pressed only after drawing out

safety circlip when starting the electromagnetic valve manually. Locking of manual lever will not
influence electric startup of the electromagnetic valve.

IX. System Maintenance

1. The Agent Releasing Control System should be checked and maintained periodically by people who have

been trained specially and have passed the exam.

2. The Agent Releasing Control System should be checked twice every month, the checking contents and the

requirements should be in conformity with the followings:

1

Check whether the control panel runs normally and the voltage of the battery is normal (a charging &
discharging test should be done on batteries every three months, so as to keep the performance of
the batteries. During the test, disconnect AC when AC and DC work normally, then batteries will
provide the power supply for the control panel which will alarm AC trouble, press the SILENCE key to
eliminate the alarm. Reconnect AC when voltage of batteries decreases to DC23V.

2

Visually inspect all system components such as agent releasing storage container, electromagnetic
driving device, pipes and spray head, etc. The system components should have no collision
distortions and other mechanic damages, without rust on the surface. The coating should be perfect,
the nameplate should be clear; shield, lead sealing and safety mark of the manual equipment should
be complete.

3

Pointer on the pressure gauge of the storage device should be in the green zone, please pressurize
or report to us if the pointer is lower than the green zone.

3. The Agent Releasing Control System should be checked twice completely every year, besides the provision

of monthly inspection, the checking contents and requirements should be in conformity with the followings:

1

The exit and usage of the protected zone, as well as the class, quantity and distribution of
inflammable matters should be in accordance with the design requirement.

2

Equipment, pipe, holder and hanging bracket in the storage cabinet should be fixed.

3

The hole of every spray head shouldn

t be blocked.

4

Perform a simulated automatic start-up test. If unqualified project is found, then re-debugging is
needed.

4. Pressurize

1

Disassemble the pressure gauge: First screw down clockwise the hexangular bolts on the switch of
the pressure gauge, then rotate the pressure gauge anticlockwise.

2

Apply the gas supply: Gas supply should adopt qualified industrial nitrogen gas; the joints should be
the same with that of the pressure gauge (external thread is M12 x 1).

3

Pressure supervision. The connecting pipe of the storage device should be equipped with switch
valve and pressure display.

After tightening all parts of the connecting pipe and checking without

error, first turn on the pressure switch on the storage container

s valve, then switch on the valve

slowly and watch closely the pressure display. Switch off the valve when pressure increases to
2.6Mpa slowly.

4

Remove the gas supply. Switch off pressure switch on the storage container valve and the switch
valve of gas supply, and then disconnect the connecting pipe.

5

Install the pressure gauge. Install and screw down clockwise the pressure gauge, then rotate the
hexangular bolts on the switch of the pressure gauge until its pointer moves. The Pointer should cover
over half of the green part.

X. General Troubleshooting

Symptom: After apply power, the control panel has no reaction and the indicator light of the power

supply is not on.

Please check whether the

AC

&

DC

switch on power module is turned on, whether the AC & DC

input fuse is burned.

Содержание JTW-ZD-01K

Страница 1: ...Multi Area Agent Releasing Control System ...

Страница 2: ...Keyboard Operation 8 VII Power Management for the Control Panel 8 VIII System Adjustment 9 IX System Maintenance 10 X General Troubleshooting 10 Warning The system may be damaged in the area where the input of AC power supply is beyond AC 270V for long time unless AC 220V is connected with the voltage stabilizer Power for the voltage stabilizer must be over 300W ...

Страница 3: ...s and resumes automatically when trouble is solved n Full electrical switch of AC and DC power supply n Monitor the status of backup batteries against overcharge and overdischarge Low consumption design 7 0 AH battery the system can work on up to 48 hours n Protect the keyboard by a lock to prevent wrong operation n HFC 227ea Low poison efficient extinguishing with no impact on ozonosphere n HFC 2...

Страница 4: ...g surface with the hanging hole in the back of the box and ensure there is enough room for the wiring and the opening of the control panel The installation dimension is shown in figure 1 size unit mm Note l At least the space of 1 meter needs to be saved for the operation on the front of the control panel l For the outlet hole on the top of the box at least the space of 0 3 meter needs to be saved...

Страница 5: ...x the storage steel cylinder in the cabinet l Connections between pipes and pipe accessories have been installed before leaving factory as is shown in figure 4 Note that the outlet of pipes should be aligned with the hole in the spray head on the panel of cabinet l Install the spray head a screwdriver can be used to tighten the spray head into the small hole l Confirm the place of the agent releas...

Страница 6: ... AC220V 50Hz JTY GD 01K 1 2 3 10K 1 2 3 10K JTW ZD 01K JTW ZD 01K 1 2 3 1 2 3 Figure 8 11 Figure 7 Area control board input output terminal 1 2 4 3 6 5 7 8 9 10 11 13 12 15 14 16 17 22 19 18 20 21 24 23 25 30 27 26 28 29 31 32 3 2 1 4 3 4 2 1 3 4 2 1 3 1 4 2 3 1 4 2 3 1 4 2 JTY GD 01K JTW ZD 01K Terminal load 10K Terminal load 10K Alarm Bell Eelectromagnetic valve ...

Страница 7: ...elayed for 20 seconds Non pause status Note When the release is completed the main panel will display the time of release in blinking blinking 00 on the area panel shows release is completed in the area l Schematic diagram of the control panel s inside connection is shown in figure 7 l Inside structure of the control panel is shown in figure 8 the meaning of each is as follows 6 The Connection of ...

Страница 8: ... power module DC TROUBLE The light is on when the battery connection is in open circuit or DC voltage is lower than 22V SYSTEM RELEASE When anyone area enters release status and start up the electromagnetic valve this light will be on SYSTEM FIRE When any detector zone finds fire alarms this light will be on SYSTEM TROUBLE When the system detects abnormity such as AC DC trouble release trouble zon...

Страница 9: ...MANUAL AUTO SILENCE SYSTEM RESET SYSTEM TEST MANUAL AUTO PAUSE HOUR QUERY MINUTE ZONE1 FIRE ZONE1 TROUBLE ZONE2 FIRE ZONE2 TROUBLE EMERGENT STOP RELEASE TROUBLE INPUT TROUBLE OUTPUT TROUBLE MANUAL RELEASE RELEASE DELAY RELEASE STARTUP RELEASE CONFIRM DELAY TIME EMERGENT RELEASE ZONE1 FIRE ZONE1 TROUBLE ZONE2 FIRE EMERGENT STOP RELEASE TROUBLE INPUT TROUBLE OUTPUT TROUBLE MANUAL RELEASE RELEASE DEL...

Страница 10: ...udible alarm changes in the following sequence trouble sound fire alarm sound release countdown sound release alarm sound MANUAL AUTO Press this key to switch between automatic and manual mode PAUSE This key pressed the system will switch to the pause mode and the indicator light will be on When any area of the system is in release delay status the keyboard lock doesn t limit the key That is wheth...

Страница 11: ...isconnect the detector fix the base and then rotate the detector counter clockwise to an angle The installation is just contrary but attention needs to be paid to the inhibiting device between the detector and the base the position should not be exceeded when rotating the detector 5 Turn on the power supply of the control panel turn on the AC DC switch on the power module and check whether the con...

Страница 12: ...c The system components should have no collision distortions and other mechanic damages without rust on the surface The coating should be perfect the nameplate should be clear shield lead sealing and safety mark of the manual equipment should be complete 3 Pointer on the pressure gauge of the storage device should be in the green zone please pressurize or report to us if the pointer is lower than ...

Страница 13: ...ck whether the keyboard lock is on and the keyboard light is on when the keyboard lock is off keys are invalid except the key silence and emergent release the key pause is controlled by the keyboard lock except when the control panel is in the state of release countdown Symptom On the control panel AC DC indicator lights are on at the same time When AC has no input or exceed the range of safety vo...

Отзывы: