3. Main Technical Parameters for Alarm bell

Input Voltage

DC24V

Max operating current

18mA

Power

3W

Operating Environment

Temperature

-10

℃~

50

Humidity

95%

noncondensing

Dimensions

φ

150

×

58mm

4. Main Technical Parameters for Extinguishing Agent Device

Model

Maximal Load

of Extinguishing

Agent (Kg)

Figuration Size
Length

×

Width

×

Height (mm)

Deposit

Pressure

(20

)

Action

Pressure

of

Release

Device

Time for
Ejecting

Startup
voltage
Startup

current

Operating

Temperature

Startup

way

Maximal

operating

Pressure

ZQW40

46

430

×

380

×

1500

2.5MPa

4.5

±

0.22

5MPa

8s

DC24V

1.2A

0

~50

Electro-

magnetic

Startup

3.4Mpa

ZQW70

80

480

×

450

×

1700

ZQW100

115

530

×

480

×

1700

ZQW120

138

530

×

480

×

1900

ZQW150

172

580

×

530

×

1900

IV. System Installation and Connection

1.

Installation of the control panel

Hang JB-QB-QM200/4 control panel stably on the dry, flat and bearing surface with the hanging hole in the

back of the box, and ensure there is enough room for the wiring and the opening of the control panel. The
installation dimension is shown in figure 1 (size unit: mm).

Note

l

At least the space of 1 meter needs to be saved for the operation on the front of the control panel.

l

For the outlet hole on the top of the box, at least the space of 0.3 meter needs to be saved for the wiring.

l

The bottom of the box is 1.1

1.3 meters from the floor.

l

Ensure the heat diffusion hole (sound hole) on the side is open.

l

The system resistance to earth must be

5

Ω

, there is an earth terminal (besides power supply) on the

plate of the box, when necessarily please use it .

l

The system must be placed indoors.

2.

Installation of Detector

l

Fix the base of the detector on the ceiling (The installation dimension is shown in figure 2, unit: mm).

l

Fix the detector on the base.

3.

Installation of Alarm Bell

l

Fix the base of the alarm bell on the wall (the installation dimension is shown in figure 3,unit: mm).

l

Hang the alarm bell on the base.

Figure 2

Figure 1

Содержание JTW-ZD-01K

Страница 1: ...Multi Area Agent Releasing Control System ...

Страница 2: ...Keyboard Operation 8 VII Power Management for the Control Panel 8 VIII System Adjustment 9 IX System Maintenance 10 X General Troubleshooting 10 Warning The system may be damaged in the area where the input of AC power supply is beyond AC 270V for long time unless AC 220V is connected with the voltage stabilizer Power for the voltage stabilizer must be over 300W ...

Страница 3: ...s and resumes automatically when trouble is solved n Full electrical switch of AC and DC power supply n Monitor the status of backup batteries against overcharge and overdischarge Low consumption design 7 0 AH battery the system can work on up to 48 hours n Protect the keyboard by a lock to prevent wrong operation n HFC 227ea Low poison efficient extinguishing with no impact on ozonosphere n HFC 2...

Страница 4: ...g surface with the hanging hole in the back of the box and ensure there is enough room for the wiring and the opening of the control panel The installation dimension is shown in figure 1 size unit mm Note l At least the space of 1 meter needs to be saved for the operation on the front of the control panel l For the outlet hole on the top of the box at least the space of 0 3 meter needs to be saved...

Страница 5: ...x the storage steel cylinder in the cabinet l Connections between pipes and pipe accessories have been installed before leaving factory as is shown in figure 4 Note that the outlet of pipes should be aligned with the hole in the spray head on the panel of cabinet l Install the spray head a screwdriver can be used to tighten the spray head into the small hole l Confirm the place of the agent releas...

Страница 6: ... AC220V 50Hz JTY GD 01K 1 2 3 10K 1 2 3 10K JTW ZD 01K JTW ZD 01K 1 2 3 1 2 3 Figure 8 11 Figure 7 Area control board input output terminal 1 2 4 3 6 5 7 8 9 10 11 13 12 15 14 16 17 22 19 18 20 21 24 23 25 30 27 26 28 29 31 32 3 2 1 4 3 4 2 1 3 4 2 1 3 1 4 2 3 1 4 2 3 1 4 2 JTY GD 01K JTW ZD 01K Terminal load 10K Terminal load 10K Alarm Bell Eelectromagnetic valve ...

Страница 7: ...elayed for 20 seconds Non pause status Note When the release is completed the main panel will display the time of release in blinking blinking 00 on the area panel shows release is completed in the area l Schematic diagram of the control panel s inside connection is shown in figure 7 l Inside structure of the control panel is shown in figure 8 the meaning of each is as follows 6 The Connection of ...

Страница 8: ... power module DC TROUBLE The light is on when the battery connection is in open circuit or DC voltage is lower than 22V SYSTEM RELEASE When anyone area enters release status and start up the electromagnetic valve this light will be on SYSTEM FIRE When any detector zone finds fire alarms this light will be on SYSTEM TROUBLE When the system detects abnormity such as AC DC trouble release trouble zon...

Страница 9: ...MANUAL AUTO SILENCE SYSTEM RESET SYSTEM TEST MANUAL AUTO PAUSE HOUR QUERY MINUTE ZONE1 FIRE ZONE1 TROUBLE ZONE2 FIRE ZONE2 TROUBLE EMERGENT STOP RELEASE TROUBLE INPUT TROUBLE OUTPUT TROUBLE MANUAL RELEASE RELEASE DELAY RELEASE STARTUP RELEASE CONFIRM DELAY TIME EMERGENT RELEASE ZONE1 FIRE ZONE1 TROUBLE ZONE2 FIRE EMERGENT STOP RELEASE TROUBLE INPUT TROUBLE OUTPUT TROUBLE MANUAL RELEASE RELEASE DEL...

Страница 10: ...udible alarm changes in the following sequence trouble sound fire alarm sound release countdown sound release alarm sound MANUAL AUTO Press this key to switch between automatic and manual mode PAUSE This key pressed the system will switch to the pause mode and the indicator light will be on When any area of the system is in release delay status the keyboard lock doesn t limit the key That is wheth...

Страница 11: ...isconnect the detector fix the base and then rotate the detector counter clockwise to an angle The installation is just contrary but attention needs to be paid to the inhibiting device between the detector and the base the position should not be exceeded when rotating the detector 5 Turn on the power supply of the control panel turn on the AC DC switch on the power module and check whether the con...

Страница 12: ...c The system components should have no collision distortions and other mechanic damages without rust on the surface The coating should be perfect the nameplate should be clear shield lead sealing and safety mark of the manual equipment should be complete 3 Pointer on the pressure gauge of the storage device should be in the green zone please pressurize or report to us if the pointer is lower than ...

Страница 13: ...ck whether the keyboard lock is on and the keyboard light is on when the keyboard lock is off keys are invalid except the key silence and emergent release the key pause is controlled by the keyboard lock except when the control panel is in the state of release countdown Symptom On the control panel AC DC indicator lights are on at the same time When AC has no input or exceed the range of safety vo...

Отзывы: