Installation & Operation Manual                                                                                               Merlin GDP4 

 

 

Rev: 11   03-21

 

7  

   Factory Set Condition 

 

SWITCH 

CONDITION 

BMS 

OFF 

AUTO RESET 

OFF 

ZONE 1 

OFF 

ZONE 2 

OFF 

ZONE 3 

OFF 

ZONE 4 

OFF 

 

   Trouble Shooting 

 

Fault. 

Possible Cause/Correction. 

Detector not responding. 

o

 

Incorrect wiring 

o

 

Zone switches not properly configured 

Panel not responding. 

o

 

Incorrect Wiring 

o

 

No Power 

o

 

Auto-Reset not properly configured 

 
 

Operation 

   Initial Power-Up (Commissioning) 

 

On connecting mains power, press reset to start the testing sequence. The system will close the solenoid valve 
when an emergency stop has been pressed, gas has been detected or any alarm signal has been triggered. 
When the system is connected to the mains power supply, the Power LED will illuminate RED.  

 

   LED Indicator Status 

 
Power 
Power LED will illuminate RED when power is supplied. When no power is present, this LED will not light up.  
 
Gas On 
On start up the Gas on LED will flash for one minute to check for gas detected. If no gas detected or any other faults 
the gas valve will open and the Gas On LED will illuminate.

 

GREEN = Gas On OFF = Gas Off 

If the test is unsuccessful, the relevant zone LED light will illuminate to indicate a fault. 
 
EM Stop 
If an emergency shut off button (either remote or on the panel) is pressed, the LED will illuminate AMBER and the 
gas will be turned off. The EM Stop button must be re-set before restarting the system. 
 
Heat Detector 
If the fusible link melts at >72° C, the LED will illuminate AMBER and the gas valve will de-energise.  
 
Fire Alarm 
On a fire alarm, the LED illuminates AMBER and gas supply  isolated. The alarm must be reset before restarting the 
system. Off = OK AMBER = Fire alarm activated. 
 
Zones 1-2-3-4 
Under normal working conditions this LED is GREEN. If the gas detector connected reaches the low level alarm this 
will show AMBER. If the gas detector connected reaches high level alarm this will show RED and the gas solenoid 
valve will close. 

Содержание Merlin GDP4

Страница 1: ...be used in many applications such as factories car parks shopping centres and boiler houses The GDP4 is used with up to twelve 12 gas detectors in a single cable run for monitoring and detecting gas i...

Страница 2: ...ew 5 Board Connections Overview 5 Wiring your Detector 6 BMS Switch 6 Auto Reset Switch 6 Zone 1 4 Set Up Switches 6 Factory Set Condition 7 Trouble Shooting 7 Operation 7 Initial Power Up Commissioni...

Страница 3: ...of defects in material and workmanship for a period of three 3 years from date of purchase or one 1 years for oxygen detectors The manufacturer s liability hereunder is limited to replacement of the p...

Страница 4: ...s Methane NG High Level 300mm 1ft from ceiling Liquid Petroleum Gas LPG Low Level 300mm 1ft from ground level Carbon Monoxide CO Breathing Zone 1700mm 5ft 6 from ground level Hydrogen H High Level 300...

Страница 5: ...supply to the panel the power LED indicator will light up this is located on the front GAS VALVE 100 240vac electrical power output from the VALVE OUT terminal using a 3 core cable to a gas solenoid...

Страница 6: ...top pressed Auto Reset Switch The panel has a built in auto reset feature There is a dipswitch located on the circuit board labelled AUTO RESET This is factory set in the Off position i e when power i...

Страница 7: ...light up Gas On On start up the Gas on LED will flash for one minute to check for gas detected If no gas detected or any other faults the gas valve will open and the Gas On LED will illuminate GREEN G...

Страница 8: ...es tetraethyl lead halogens and halogenated compounds Manual Circuit Simulation Test When the test button on the circuit board is pressed and held for 3s the detector will simulate an open circuit to...

Страница 9: ...Nitrogen 60s All certified test gases supplied by S S Northern are classified as non flammable and non toxic however they do contain gas under pressure and may explode if heated to extreme temperatur...

Страница 10: ...Safe Areas not to be used in potentially explosive atmospheres Indicators LED Mounting Wall Mounting Electrical Max Power Consumption 20W Max Full Load Power Voltage Input Range 100 240vac Gas Valve...

Страница 11: ...Installation Operation Manual Merlin GDP4 Rev 11 03 21 11 Page intentionally left blank...

Страница 12: ...en damage caused by transit installation Every effort is made to ensure the accuracy of this document however S S Northern can assume no responsibility for any errors or omissions in this document or...

Отзывы: