Installation & Operation Manual                                                                                               Merlin GDP4 

 

 

Rev: 11   03-21

 

8  

   Mute & Reset Buttons 

 

MUTE The mute button is located on the front fascia of the GDP4 and is used to mute the sounder inside the board 

when in alarm. The internal buzzer operates at approximately >60db measured 30cm (1ft) from a closed panel. The 
mute button is used to mute the sounder inside the board when in alarm. 
 

RESET The reset button is located on the front fascia of the GDP4 and is used to turn the system on and to reset the 

system following alarm. 

 
 

General Maintenance 

   Cleaning 

 

Keep your gas detector in good working order - follow these basic principles; 
 

 

Remove any dust/debris from the outer enclosure regularly using a slightly damp cloth. 

 

Never use detergents or solvents to clean your device. 

 

Never spray air fresheners, hair spray, paint or other aerosols near the device. 

 

Never paint the device. Paint will seal vents and interfere with the device. 

 

 

 

Concentrations of alcohol found in many products may damage, deteriorate or affect the gas sensing 
elements such as; wine; deodorants; stain removers and thinners. Other gases and substances to avoid are; 
corrosives (i.e. chlorine & hydrogen chloride); alkali metals; basic or acidic compounds; silicones; tetraethyl 
lead; halogens and halogenated compounds!  

 

   Manual Circuit Simulation Test  

 
When the test button on the circuit board is pressed and held for ~3s the detector will simulate an open circuit to 
ensure outputs, alarms, indications and external devices etc. operate as intended in response to gas.  
 

 

 

Access to the interior of the detector, when carrying out any work, must be conducted by a competent 
person! This test does not check the gas-sensing element itself! 
 

   Bump Test (Gas Response Check) 

 
What is a Bump Test?  
Gas response checks are often referred to as a ‘bump test’. Bump tests are important to make sure a device is able 
to detect a release of gas as early as possible. The aim of the bump test is to make sure a detector is working at its 
optimum by briefly exposing the unit to a known concentration of the target gas that usually exceeds the highest 
alarm point. If the detector goes into alarm and all signals/outputs activate, then the system is working safely. If the 
system fails to operate as intended in an alarm state, the gas detector must not be used until a full inspection and 
service has been conducted.  
 
Why is it important?  
A detector may visually appear in good working order, but its sensitivity can be inhibited by external factors. Dust, 
humidity, temperature fluctuations, cleaning products, contaminants or sensor drift (ageing) can cause a decline in 
sensitivity and eventual failure.  
 
 
 

Содержание Merlin GDP4

Страница 1: ...be used in many applications such as factories car parks shopping centres and boiler houses The GDP4 is used with up to twelve 12 gas detectors in a single cable run for monitoring and detecting gas i...

Страница 2: ...ew 5 Board Connections Overview 5 Wiring your Detector 6 BMS Switch 6 Auto Reset Switch 6 Zone 1 4 Set Up Switches 6 Factory Set Condition 7 Trouble Shooting 7 Operation 7 Initial Power Up Commissioni...

Страница 3: ...of defects in material and workmanship for a period of three 3 years from date of purchase or one 1 years for oxygen detectors The manufacturer s liability hereunder is limited to replacement of the p...

Страница 4: ...s Methane NG High Level 300mm 1ft from ceiling Liquid Petroleum Gas LPG Low Level 300mm 1ft from ground level Carbon Monoxide CO Breathing Zone 1700mm 5ft 6 from ground level Hydrogen H High Level 300...

Страница 5: ...supply to the panel the power LED indicator will light up this is located on the front GAS VALVE 100 240vac electrical power output from the VALVE OUT terminal using a 3 core cable to a gas solenoid...

Страница 6: ...top pressed Auto Reset Switch The panel has a built in auto reset feature There is a dipswitch located on the circuit board labelled AUTO RESET This is factory set in the Off position i e when power i...

Страница 7: ...light up Gas On On start up the Gas on LED will flash for one minute to check for gas detected If no gas detected or any other faults the gas valve will open and the Gas On LED will illuminate GREEN G...

Страница 8: ...es tetraethyl lead halogens and halogenated compounds Manual Circuit Simulation Test When the test button on the circuit board is pressed and held for 3s the detector will simulate an open circuit to...

Страница 9: ...Nitrogen 60s All certified test gases supplied by S S Northern are classified as non flammable and non toxic however they do contain gas under pressure and may explode if heated to extreme temperatur...

Страница 10: ...Safe Areas not to be used in potentially explosive atmospheres Indicators LED Mounting Wall Mounting Electrical Max Power Consumption 20W Max Full Load Power Voltage Input Range 100 240vac Gas Valve...

Страница 11: ...Installation Operation Manual Merlin GDP4 Rev 11 03 21 11 Page intentionally left blank...

Страница 12: ...en damage caused by transit installation Every effort is made to ensure the accuracy of this document however S S Northern can assume no responsibility for any errors or omissions in this document or...

Отзывы: