Installation 

   Typical Application, Location & Positioning 

 
The Merlin GDP4 is a multi-safe zone gas detection panel which can be used in many applications such as factories, 
car parks, shopping centres and most commonly - boiler houses. It can be used with up to 12 Merlin gas detectors 
(3 detectors per zone terminal) for monitoring and detecting gas including carbon monoxide, liquid petroleum gas 
and methane.  
The controller panel can be integrated with, but not limited to, a BMS (building management system), a fire panel, 
external alarms and remote emergency shut-off buttons.  
 
Locations for detectors will vary based on the intended application and target gas, they should be located near 
identified sources of a potential gas leaks/ pockets where hazardous gas could quickly accumulate and areas of 
identified consequential risk.  
The composition of the target gas and its density relative to air are used as the basis for any recommended height of 
detector placement. Generally, the installation height of a detector for a heavy gas (such as propane) would be close 
to the lowest point in the area, and for a light gas (such as methane) would be close to the highest point in the area.  
 
Any recommended heights may vary based on air flow and temperature conditions in addition to the proposed 
application and location – this is particularly apparent with oxygen depletion sensors, and the target gas that they 
are used for. 
 

Target Gas 

Typical Position 

Natural Gas/Methane (NG)  

High Level - 300mm (1ft) from ceiling  

Liquid Petroleum Gas (LPG)  

Low Level - 300mm (1ft) from ground level 

Carbon Monoxide (CO)  

Breathing Zone - 1700mm (5ft 6”) from ground level 

Hydrogen (H) 

High Level - 300mm (1ft) from ceiling 

Oxygen (O

2

*Breathing Zone - 1000-1500mm (3 - 5ft) from ground level 

 
* If you are installing and monitoring Oxygen depletion – consider the density of gas for its application and position 
the detector accordingly i.e. ground level for high density gases. 
 
The control panel should be located away from the area that it is monitoring and accessible is for both status 
observation and alarm purposes. The control panel should be located outside of the hazardous area that it is 
monitoring. Easy access is required both for status observation and alarm purposes. 

 

   Access & Mounting 

 

Unpack all the parts! 
Designed for surface mounting, it must be installed by a licensed, insured contractor or competent person. 

 

Carefully remove the front cover from the unit by unscrewing the four bolts 
located at each corner. To do this – use the socket wrench provided. Mark 
the four screw holes located on the back of the enclosure to the wall and 
ensure the wall surface is flat to prevent base distortion. 

 
After executing the mounting and the connections – replace the front cover 

and insert the security caps over the four bolts. 
 

 

 

Access to the interior of the panel, when carrying out any work, must be conducted by a competent person. 
Before carrying out any work ensure local regulations and site procedures are followed. 
We recommend all Merlin gas detection equipment and systems are commissioned by a competent/trained 
engineer to ensure correct installation and operation. Contact S&S Northern for more information. 

Содержание Merlin GDP4

Страница 1: ...be used in many applications such as factories car parks shopping centres and boiler houses The GDP4 is used with up to twelve 12 gas detectors in a single cable run for monitoring and detecting gas i...

Страница 2: ...ew 5 Board Connections Overview 5 Wiring your Detector 6 BMS Switch 6 Auto Reset Switch 6 Zone 1 4 Set Up Switches 6 Factory Set Condition 7 Trouble Shooting 7 Operation 7 Initial Power Up Commissioni...

Страница 3: ...of defects in material and workmanship for a period of three 3 years from date of purchase or one 1 years for oxygen detectors The manufacturer s liability hereunder is limited to replacement of the p...

Страница 4: ...s Methane NG High Level 300mm 1ft from ceiling Liquid Petroleum Gas LPG Low Level 300mm 1ft from ground level Carbon Monoxide CO Breathing Zone 1700mm 5ft 6 from ground level Hydrogen H High Level 300...

Страница 5: ...supply to the panel the power LED indicator will light up this is located on the front GAS VALVE 100 240vac electrical power output from the VALVE OUT terminal using a 3 core cable to a gas solenoid...

Страница 6: ...top pressed Auto Reset Switch The panel has a built in auto reset feature There is a dipswitch located on the circuit board labelled AUTO RESET This is factory set in the Off position i e when power i...

Страница 7: ...light up Gas On On start up the Gas on LED will flash for one minute to check for gas detected If no gas detected or any other faults the gas valve will open and the Gas On LED will illuminate GREEN G...

Страница 8: ...es tetraethyl lead halogens and halogenated compounds Manual Circuit Simulation Test When the test button on the circuit board is pressed and held for 3s the detector will simulate an open circuit to...

Страница 9: ...Nitrogen 60s All certified test gases supplied by S S Northern are classified as non flammable and non toxic however they do contain gas under pressure and may explode if heated to extreme temperatur...

Страница 10: ...Safe Areas not to be used in potentially explosive atmospheres Indicators LED Mounting Wall Mounting Electrical Max Power Consumption 20W Max Full Load Power Voltage Input Range 100 240vac Gas Valve...

Страница 11: ...Installation Operation Manual Merlin GDP4 Rev 11 03 21 11 Page intentionally left blank...

Страница 12: ...en damage caused by transit installation Every effort is made to ensure the accuracy of this document however S S Northern can assume no responsibility for any errors or omissions in this document or...

Отзывы: