Installation & Operation Manual Merlin 1000S+
1000S+
IOM
Rev: 9 07-20
4
Typical Installation Arrangement
Terminal Connections
1.
POWER / LINE IN
240VAC Power should be supplied to the [POWER / LINE IN] terminal and fused at 3A.
On connecting the mains supply to the panel the power LED indicator will light up – this is
located on the front cover.
2.
GAS SOLENOID VALVE OUTPUT
240VAC electrical power supplied from the [VALVE OUT] connector using a 3 core cable can
be connected to a gas solenoid valve which can shut the gas supply on alarm status.
Pressure sensors should be screwed to the downstream port of the valve.
Refer to your valve manual for more information and wiring!
3.
ELECTRIC CONTACTOR OUTPUT
240VAC electrical power supplied from the [ELECTRIC CONTACTOR] connector using a 3 core
cable can be connected to a contactor.
Refer to your contactor manual for more information and wiring!