S&C Vista SD Скачать руководство пользователя страница 25

Appendix C

NOTICE

Because of the nature of the internal connections of some secondary injection-style 
relay-test sets, a ground-loop condition can develop when 

both

 the test set and a PC are 

connected to an ac wall outlet . The ground-loop condition may damage the PC data port . 
Always isolate the PC by running it on an isolated ac supply or by running the PC on its 
battery packs .

Using Terminal  
Emulator Programs

The procedures for starting and using terminal­emulator program will vary depending 
on the specific terminal­emulator program. A simple terminal­emulator program was 
included with every copy of Microsoft Windows. 

NOTICE

Windows Vista, Windows 7, and Windows 8 do not include a terminal-emulation program . 
Users must select and install a terminal-emulator program to be able to communicate 
with the S&C Overcurrent Control . S&C recommends downloading one of two terminal-
emulator programs listed below .

Manufacturer:  Schweitzer Engineering Laboratories, Inc.
Program: 

AcSELerator QuickSet 5030

Website: www.selinc.com/sel­5030.htm
Note: 

This software is available to download for free.

Manufacturer: Hilgraeve
Program: HyperTerminal
Website: www.hilgraeve.com/hyperterminal.html
Note: 

This software is the same software supplied with previous versions  
of Microsoft Windows. It is available for purchase.

Basic instructions for the terminal­emulator programs “HyperTerminal” (which comes 

with Windows 95, 98, 2000, NT, ME, and XP, and available for download for Windows 
Vista, 7, and 8 users) and “AcSELerator QuickSet 5030” (available for download) are 
provided on page 26.

HyperTerminal

For Windows 95, 98, 2000, NT, ME, XP, Vista, 7, and 8:

Step 1

Click on the 

Start

 button.

(a) For Windows 95, 98, and ME select 

Programs

 and then 

Accessories

. In the  

Acces sories

 folder, select the 

HyperTerminal

 icon. Then double­click on  

Hypertrm.exe.

(b)  For Windows 2000, NT, and XP select 

Programs

, then 

Accessories, 

then 

Commu-

nications 

(or 

HyperTerminal

). Then select the 

HyperTerminal

 icon.

(c)  For Windows Vista, 7, and 8 open the 

HyperTerminal

 program from its file location  

(probably on the desktop).

Step 2

A dialog box will then ask for a “connection description.” This is a file that will be saved in 
the 

HyperTerminal

 folder with its own name and icon. It stores the appropriate set tings 

for connecting to the S&C Overcurrent Control so they do not have to be entered every 
time. In the “connection description” dialog box, enter a name for this file (for example, 
“Vista”). 

  

S&C Instruction Sheet 695-515

  

25

Содержание Vista SD

Страница 1: ...onfigure Menu 14 Test Trip Menu 16 Self Test Report Viewing of Self Test Report 17 Response to Self Test Failure 17 Self Test Failures and Warnings 18 Specifications Port Power 19 CT Power 19 Steady S...

Страница 2: ...ranty provisions as set forth in the applicable product line specification bulletin are exclusive The remedies provided in the former for breach of these warranties shall constitute the immediate purc...

Страница 3: ...OTICE NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not followed Following Safety Instructions If you do not understand any p...

Страница 4: ...G Hazardous voltage inside can shock burn or cause death Safety Information DANGER Never disconnect current transformer secondary circuits without de energizing the switchgear Hazardous voltage will s...

Страница 5: ...ounted style Vista SD units the overcurrent control enclosure is fully submersible The elec tronics module is removable for programming in the shop Programming A personal computer furnished by the use...

Страница 6: ...TCC curves can be customized into hundreds of dif ferent curves using a variety of instantaneous pickup settings discrete choices from 0 2 kA through 6 kA and definite time delay settings discrete ch...

Страница 7: ...rmation can be accessed via a personal computer con nected to the data port of the control Self Testing Whenever the overcurrent control is powered up and then periodically thereafter it automatically...

Страница 8: ...A for connecting thecontrolto auser furnished personal computer in the field These cables provide for both communications and power For Microsoft Windows users no special software is requiredtocommu n...

Страница 9: ...areas of the menu system The User Password must be entered to change control settings test trip the solenoids and change the User Password The Group Configure Password is required to change the global...

Страница 10: ...the Enter button View Menu INTERRUPTER 1 select number 1 View event report last 12 events 2 View load current 3 View relay settings 4 View relay self test 9 Switch to Main Menu View FI 1 1 View Event...

Страница 11: ...n 10 of the maximum phase current 4 If only one target is declared from the previous logic target the faulted pole of the remaining three with the highest cur rent The primary RMS magnitude of each po...

Страница 12: ...for menu Configure Menu 1 or 2 The Configure Menu option allows review and changes to the TCC curve set tings for the selected fault inter rupter The Configure Menu box below is for Fault Interrupter...

Страница 13: ...rt discussed in View Event Report on page 10 will be reset Press Q to return to menu Phase TCC Curve E K TAP MAIN U1 U2 U3 U4 U5 C1 C2 C3 C4 C5 E tap Minimum Pickup Amps 50 65 80 100 150 200 250 300 3...

Страница 14: ...m the new password re enter it after the third prompt USER PASSWORD CHANGE USER PASSWORD Enter new password four digits blank for no change Re enter new password Group Configure Menu The Group Configu...

Страница 15: ...n to menu ID for Interrupter 1 20 characters INTERRUPTER 1 interrupter pole 1 ID for Interrupter 2 20 characters INTERRUPTER 2 interrupter pole 2 1 pole or 3 pole trip mode for Interrupter 1 1 3 1 3 1...

Страница 16: ...of firmware Refer to the nearest S C Sales Office for instructions Test Trip Menu The Test Trip Menu option allows test tripping of the fault interrupters all three poles or single poles Step 1 Selec...

Страница 17: ...on and firmware date code Trip Caps The status of the trip capacitors is reported for each fault interrupter pole If the trip capacitors are not charged to at least 50 volts a low condition is reporte...

Страница 18: ...ion is enabled The message Relay enabled using default settings is displayed at the top of each menu If the EEPROM failure persists i e if default settings cannot be stored in EEPROM a self test failu...

Страница 19: ...C Curves 5 A primary and 5 of setting Time Overcurrent Response E K Coordinating Tap and Coordinating Main Curves 0 to 10 in terms of current OR 0 to 20 in terms of time OR 0 to 6 ms whichever gives t...

Страница 20: ...rs Terminal numbers are identified by labels on the electronics module or terminal block Trip outputs Electronics module Trip Outputs Terminal Number 1 2 Pole Mating Connector Part Number 1 2 Fault In...

Страница 21: ...Fault Interrupter 2 Pole 1 18 Fault Interrupter 2 Pole 2 19 Fault Interrupter 2 Pole 3 20 Fault Interrupter 2 Residual Power Inputs Terminal Number Power Pole 21 Fault Interrupter 1 Pole 1 22 Fault I...

Страница 22: ...onics module Communication Port Pin Out Electronics Module Pin Function 1 Power in 2 RXD Data In 3 TXD Data Out 4 No connection 5 Signal reference 6 No connection 7 No connection 8 No connection 9 Pow...

Страница 23: ...current control enclosure Pad mounted style shown 2 1 4 5 3 FACE VIEW Data Port Pin Out Control Enclosure Pin Function 1 Power return 2 RXD Data In 3 TXD Data Out 4 Power in 5 Signal reference S C Ins...

Страница 24: ...None Data Bits 8 Stop Bits 1 Flow Control XON XOFF The overcurrent control does not use hardware flow control RTS CTS AcSELerator Quickset SEL 5030 Parameter Setting Device Data Speed 9600 Data Bits...

Страница 25: ...rTerminal Website www hilgraeve com hyperterminal html Note This software is the same software supplied with previous versions of Microsoft Windows It is available for purchase Basic instructions for...

Страница 26: ...nnecting click on the Reconnect button on the toolbar Again this function is located under the Call menu Step 6 To exit this session select File Exit or click on the X button in the upper right hand c...

Страница 27: ...ents Example Referring to the coordination plot in Figure 2 on page 30 a Vista SD switchgear assembly with 600 ampere fault interrupt ers is placed into an electrical system where the upstream protect...

Страница 28: ...rity Characteristic Time s Current kA Maximum Rating 20 15 10 5 0 25 10 5 0 Figure 1 S C Overcurrent Control maximum current rating adjusted for C T saturation Table 1 on page 29 should be used to det...

Страница 29: ...ow the limits shown for the operation of the I2t security characteristic during fault levels up to 14 5 kA The Time Dial setting is below the threshold of 10 0 at a Pickup setting of 1200 amperes If t...

Страница 30: ...U4 Pick Up 880 00 A TD 0 800 0 1 51 Vista 200K fuse 0 01 0 4 1 10 1000 100 10000 Fuse S C SMU20 K 14 4kV Rating 200 0 A 12 47 kV Phase Relay Relay WEST CO 9 Tap Range Tap 0 Pick Up 960 00 A TD 2 CT 6...

Страница 31: ...0 1 00 0 50 6000 5000 3000 2500 1500 1250 600 500 300 250 150 125 60 50 30 25 15 12 5 6 5 3 2 5 100 90 80 40 70 60 50 30 20 10 9 8 4 7 6 5 3 2 1 9 8 4 7 6 5 3 2 1 09 08 04 07 06 05 03 02 01 100 90 80...

Страница 32: ...r Coordinating Main Curves Minimum Pickup Amperes 100 150 200 250 300 350 400 450 500 600 700 800 For Curves U1 U5 and C1 C5 Minimum Pickup Amperes 50 1200 1 A steps Time Dial Multiplier U Curves 0 5...

Страница 33: ...steps For Coordinating Tap and U1 U5 and C1 C5 Curves Definite Time Delay ms 60 Hz OFF 32 48 64 80 96 Definite Time Delay ms 50 Hz OFF 40 60 80 100 120 For Coordinating Main Curves Definite Time Dela...