background image

Table 1. I

2

t Security Characteristic Settings Limits (660:1 CT)

 

Curve

Affected Settings for  

Fault Current ≥ 14.5 kA 

Affected Settings for  

Fault Current = 10.0 kA

U1

Time Dials > 4 .3 @ 50 A pickup 
Time Dials > 3 .2 @ 1200 A pickup

Time Dials > 9 .1 @ 50 A pickup 
Time Dials > 5 .9 @ 1200 A pickup

U2

Time Dials > 3 .9 @ 50 A pickup 
Time Dials > 3 .3 @ 1200 A pickup

Time Dials > 8 .3 @ 50 A pickup 
Time Dials > 5 .8 @ 1200 A pickup

U3

Time Dials > 7 .3 @ 50 A pickup 
Time Dials > 6 .0 @ 1200 A pickup

Time Dials > 14 .9 @ 450 A pickup 
Time Dials > 10 .2 @ 1200 A pickup

U4

Time Dials > 14 .9 @ 730 A pickup 
Time Dials > 10 .0 @ 1200 A pickup

Time Dials > 14 .9 @ 1100 A pickup 
Time Dials > 13 .2 @ 1200 A pickup

U5

Time Dials > 14 .5 @ 50 A pickup 
Time Dials > 10 .6 @ 1200 A pickup

Not applicable

C1

Time Dials > 0 .37 @ 50 A pickup 
Time Dials > 0 .27 @ 1200 A pickup

Time Dials > 0 .78 @ 50 A pickup 
Time Dials > 0 .48 @ 1200 A pickup

C2

Time Dials > 0 .99 @ 760 A pickup 
Time Dials > 0 .61 @ 1200 A pickup

Time Dials > 0 .99 @ 1040 A pickup 
Time Dials > 0 .84 @ 1200 A pickup

C3

Not applicable

Not applicable

C4

Time Dials > 0 .17 @ 50 A pickup 
Time Dials > 0 .06 @ 1200 A pickup

Time Dials > 0 .37 @ 50 A pickup 
Time Dials > 0 .09 @ 1200 A pickup

C5

Not applicable

Not applicable

For our sample coordination study, with a U4 curve selected to have an 880­ 

ampere pickup and a 0.8 

Time Dial

   setting, we are well below the limits shown 

for the operation of the “I

2

t security characteristic” during fault levels up to 14.5 

kA. The 

Time Dial

 setting is below the threshold of 10.0 at a 

Pickup

 setting of  

1200 amperes.

If the setting was above the limit for the “I

2

t security characteristic,” a warning message 

would be displayed with the calculation of the cross over point in primary amperes of the 
selected US or IEC curve with the “I

2

t security characteristic” curve. A sample warning 

message is shown below.

“Phase overcurrent control will operate on the TOC curve for faults up to 18476 A. 
Phase overcurrent control will operate on its maximum I

2

t (thermal) limit curve for 

faults above 18476 A. Refer to S&C Instruction Sheet 681­515 Appendix D.”
When this occurs, the user must consider the following:
If the fault level displayed in the warning message is 

higher

 than the maximum 

avail able fault current level at the switchgear assembly, the “I

2

t security character­

istic” will not become enabled. If the fault level displayed in the warning message is 

lower

 than the maximum available fault current level, then the “I

2

t security character­

istic” will become enabled resulting in a faster time to operate. To prevent this from 
occurring, new settings selec tions should be considered to prevent miscoordination 
between upstream source­side and downstream load­side devices. Contact S&C Electric  
Company—Power Systems Solutions for application assistance.

Appendix D

  

S&C Instruction Sheet 695-515

  

29

Содержание Vista SD

Страница 1: ...onfigure Menu 14 Test Trip Menu 16 Self Test Report Viewing of Self Test Report 17 Response to Self Test Failure 17 Self Test Failures and Warnings 18 Specifications Port Power 19 CT Power 19 Steady S...

Страница 2: ...ranty provisions as set forth in the applicable product line specification bulletin are exclusive The remedies provided in the former for breach of these warranties shall constitute the immediate purc...

Страница 3: ...OTICE NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not followed Following Safety Instructions If you do not understand any p...

Страница 4: ...G Hazardous voltage inside can shock burn or cause death Safety Information DANGER Never disconnect current transformer secondary circuits without de energizing the switchgear Hazardous voltage will s...

Страница 5: ...ounted style Vista SD units the overcurrent control enclosure is fully submersible The elec tronics module is removable for programming in the shop Programming A personal computer furnished by the use...

Страница 6: ...TCC curves can be customized into hundreds of dif ferent curves using a variety of instantaneous pickup settings discrete choices from 0 2 kA through 6 kA and definite time delay settings discrete ch...

Страница 7: ...rmation can be accessed via a personal computer con nected to the data port of the control Self Testing Whenever the overcurrent control is powered up and then periodically thereafter it automatically...

Страница 8: ...A for connecting thecontrolto auser furnished personal computer in the field These cables provide for both communications and power For Microsoft Windows users no special software is requiredtocommu n...

Страница 9: ...areas of the menu system The User Password must be entered to change control settings test trip the solenoids and change the User Password The Group Configure Password is required to change the global...

Страница 10: ...the Enter button View Menu INTERRUPTER 1 select number 1 View event report last 12 events 2 View load current 3 View relay settings 4 View relay self test 9 Switch to Main Menu View FI 1 1 View Event...

Страница 11: ...n 10 of the maximum phase current 4 If only one target is declared from the previous logic target the faulted pole of the remaining three with the highest cur rent The primary RMS magnitude of each po...

Страница 12: ...for menu Configure Menu 1 or 2 The Configure Menu option allows review and changes to the TCC curve set tings for the selected fault inter rupter The Configure Menu box below is for Fault Interrupter...

Страница 13: ...rt discussed in View Event Report on page 10 will be reset Press Q to return to menu Phase TCC Curve E K TAP MAIN U1 U2 U3 U4 U5 C1 C2 C3 C4 C5 E tap Minimum Pickup Amps 50 65 80 100 150 200 250 300 3...

Страница 14: ...m the new password re enter it after the third prompt USER PASSWORD CHANGE USER PASSWORD Enter new password four digits blank for no change Re enter new password Group Configure Menu The Group Configu...

Страница 15: ...n to menu ID for Interrupter 1 20 characters INTERRUPTER 1 interrupter pole 1 ID for Interrupter 2 20 characters INTERRUPTER 2 interrupter pole 2 1 pole or 3 pole trip mode for Interrupter 1 1 3 1 3 1...

Страница 16: ...of firmware Refer to the nearest S C Sales Office for instructions Test Trip Menu The Test Trip Menu option allows test tripping of the fault interrupters all three poles or single poles Step 1 Selec...

Страница 17: ...on and firmware date code Trip Caps The status of the trip capacitors is reported for each fault interrupter pole If the trip capacitors are not charged to at least 50 volts a low condition is reporte...

Страница 18: ...ion is enabled The message Relay enabled using default settings is displayed at the top of each menu If the EEPROM failure persists i e if default settings cannot be stored in EEPROM a self test failu...

Страница 19: ...C Curves 5 A primary and 5 of setting Time Overcurrent Response E K Coordinating Tap and Coordinating Main Curves 0 to 10 in terms of current OR 0 to 20 in terms of time OR 0 to 6 ms whichever gives t...

Страница 20: ...rs Terminal numbers are identified by labels on the electronics module or terminal block Trip outputs Electronics module Trip Outputs Terminal Number 1 2 Pole Mating Connector Part Number 1 2 Fault In...

Страница 21: ...Fault Interrupter 2 Pole 1 18 Fault Interrupter 2 Pole 2 19 Fault Interrupter 2 Pole 3 20 Fault Interrupter 2 Residual Power Inputs Terminal Number Power Pole 21 Fault Interrupter 1 Pole 1 22 Fault I...

Страница 22: ...onics module Communication Port Pin Out Electronics Module Pin Function 1 Power in 2 RXD Data In 3 TXD Data Out 4 No connection 5 Signal reference 6 No connection 7 No connection 8 No connection 9 Pow...

Страница 23: ...current control enclosure Pad mounted style shown 2 1 4 5 3 FACE VIEW Data Port Pin Out Control Enclosure Pin Function 1 Power return 2 RXD Data In 3 TXD Data Out 4 Power in 5 Signal reference S C Ins...

Страница 24: ...None Data Bits 8 Stop Bits 1 Flow Control XON XOFF The overcurrent control does not use hardware flow control RTS CTS AcSELerator Quickset SEL 5030 Parameter Setting Device Data Speed 9600 Data Bits...

Страница 25: ...rTerminal Website www hilgraeve com hyperterminal html Note This software is the same software supplied with previous versions of Microsoft Windows It is available for purchase Basic instructions for...

Страница 26: ...nnecting click on the Reconnect button on the toolbar Again this function is located under the Call menu Step 6 To exit this session select File Exit or click on the X button in the upper right hand c...

Страница 27: ...ents Example Referring to the coordination plot in Figure 2 on page 30 a Vista SD switchgear assembly with 600 ampere fault interrupt ers is placed into an electrical system where the upstream protect...

Страница 28: ...rity Characteristic Time s Current kA Maximum Rating 20 15 10 5 0 25 10 5 0 Figure 1 S C Overcurrent Control maximum current rating adjusted for C T saturation Table 1 on page 29 should be used to det...

Страница 29: ...ow the limits shown for the operation of the I2t security characteristic during fault levels up to 14 5 kA The Time Dial setting is below the threshold of 10 0 at a Pickup setting of 1200 amperes If t...

Страница 30: ...U4 Pick Up 880 00 A TD 0 800 0 1 51 Vista 200K fuse 0 01 0 4 1 10 1000 100 10000 Fuse S C SMU20 K 14 4kV Rating 200 0 A 12 47 kV Phase Relay Relay WEST CO 9 Tap Range Tap 0 Pick Up 960 00 A TD 2 CT 6...

Страница 31: ...0 1 00 0 50 6000 5000 3000 2500 1500 1250 600 500 300 250 150 125 60 50 30 25 15 12 5 6 5 3 2 5 100 90 80 40 70 60 50 30 20 10 9 8 4 7 6 5 3 2 1 9 8 4 7 6 5 3 2 1 09 08 04 07 06 05 03 02 01 100 90 80...

Страница 32: ...r Coordinating Main Curves Minimum Pickup Amperes 100 150 200 250 300 350 400 450 500 600 700 800 For Curves U1 U5 and C1 C5 Minimum Pickup Amperes 50 1200 1 A steps Time Dial Multiplier U Curves 0 5...

Страница 33: ...steps For Coordinating Tap and U1 U5 and C1 C5 Curves Definite Time Delay ms 60 Hz OFF 32 48 64 80 96 Definite Time Delay ms 50 Hz OFF 40 60 80 100 120 For Coordinating Main Curves Definite Time Dela...

Страница 34: ......

Отзывы: