background image

Self-Test Report

RAM

The RAM self­test verifies proper operation of the read/write memory. This test periodi­
cally performs a nondestructive write/read to successive blocks of RAM to determine 
whether a RAM failure has occurred. A failure occurs if the expected data are not read 
back from the RAM. In this case, protection is disabled and “fail” is reported.

Flash

The Flash self­test verifies the integrity of the data contained in system program Flash. If 
Flash is corrupted, protection is disabled and “fail” is reported.

CR-RAM

Areas of RAM containing constant data that have been copied from EEPROM are periodi­
cally examined to verify their integrity. If this critical RAM has been corrupted, protection 
is disabled and “fail” is reported.

EEPROM

The EEPROM self­test verifies the integrity of data contained in EEPROM. EEPROM self­
test failures are handled differently because self­test failures and control settings are both 
stored in EEPROM. Following an EEPROM self­test failure, factory­default settings are 
restored and protection is enabled. The message “Relay enabled using default settings” is 
displayed at the top of each menu. If the EEPROM failure persists (i.e., if default settings 
cannot be stored in EEPROM), a self­test failure is also generated.

Voltage Control

This logic monitors the power shunt circuitry in the power supply. On power up, each 
phase magnitude is averaged for 0.5 seconds. If the average is greater than or equal to 50 
amperes and the associated trip capacitor is not charged, the CT power circuit is defec­
tive and a failure is declared.

Self-Test Failures  
and Warnings

The following screen is an example of a self­test screen. The +5­volt power supply voltage 
is flagged with an “F”, and “Relay Disabled” appears above each menu.

The control records self­test failures in EEPROM and remains disabled until power 

is removed and restored. When power is restored, the self­test is repeated. If no failure 
occurs, the failure indication changes to “warn”—or “W” in the case of a power sup ply—
and protection is enabled.

INTERRUPTER 1
FID=S&C–1000 –R100 –970317

SELF TESTS
W = Warn  F = Fail
Pole #

1

2

3

Trip Caps

OK

OK

OK

Supply

+ 5V + 12V

Voltage

5.35F 12.12

RAM

FLASH

CR_RAM

EEPROM

V_CONTROL

OK

OK

OK

OK

OK

Press <ENTER> for menu

18    S&C Instruction Sheet 695-515 

Содержание Vista SD

Страница 1: ...onfigure Menu 14 Test Trip Menu 16 Self Test Report Viewing of Self Test Report 17 Response to Self Test Failure 17 Self Test Failures and Warnings 18 Specifications Port Power 19 CT Power 19 Steady S...

Страница 2: ...ranty provisions as set forth in the applicable product line specification bulletin are exclusive The remedies provided in the former for breach of these warranties shall constitute the immediate purc...

Страница 3: ...OTICE NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not followed Following Safety Instructions If you do not understand any p...

Страница 4: ...G Hazardous voltage inside can shock burn or cause death Safety Information DANGER Never disconnect current transformer secondary circuits without de energizing the switchgear Hazardous voltage will s...

Страница 5: ...ounted style Vista SD units the overcurrent control enclosure is fully submersible The elec tronics module is removable for programming in the shop Programming A personal computer furnished by the use...

Страница 6: ...TCC curves can be customized into hundreds of dif ferent curves using a variety of instantaneous pickup settings discrete choices from 0 2 kA through 6 kA and definite time delay settings discrete ch...

Страница 7: ...rmation can be accessed via a personal computer con nected to the data port of the control Self Testing Whenever the overcurrent control is powered up and then periodically thereafter it automatically...

Страница 8: ...A for connecting thecontrolto auser furnished personal computer in the field These cables provide for both communications and power For Microsoft Windows users no special software is requiredtocommu n...

Страница 9: ...areas of the menu system The User Password must be entered to change control settings test trip the solenoids and change the User Password The Group Configure Password is required to change the global...

Страница 10: ...the Enter button View Menu INTERRUPTER 1 select number 1 View event report last 12 events 2 View load current 3 View relay settings 4 View relay self test 9 Switch to Main Menu View FI 1 1 View Event...

Страница 11: ...n 10 of the maximum phase current 4 If only one target is declared from the previous logic target the faulted pole of the remaining three with the highest cur rent The primary RMS magnitude of each po...

Страница 12: ...for menu Configure Menu 1 or 2 The Configure Menu option allows review and changes to the TCC curve set tings for the selected fault inter rupter The Configure Menu box below is for Fault Interrupter...

Страница 13: ...rt discussed in View Event Report on page 10 will be reset Press Q to return to menu Phase TCC Curve E K TAP MAIN U1 U2 U3 U4 U5 C1 C2 C3 C4 C5 E tap Minimum Pickup Amps 50 65 80 100 150 200 250 300 3...

Страница 14: ...m the new password re enter it after the third prompt USER PASSWORD CHANGE USER PASSWORD Enter new password four digits blank for no change Re enter new password Group Configure Menu The Group Configu...

Страница 15: ...n to menu ID for Interrupter 1 20 characters INTERRUPTER 1 interrupter pole 1 ID for Interrupter 2 20 characters INTERRUPTER 2 interrupter pole 2 1 pole or 3 pole trip mode for Interrupter 1 1 3 1 3 1...

Страница 16: ...of firmware Refer to the nearest S C Sales Office for instructions Test Trip Menu The Test Trip Menu option allows test tripping of the fault interrupters all three poles or single poles Step 1 Selec...

Страница 17: ...on and firmware date code Trip Caps The status of the trip capacitors is reported for each fault interrupter pole If the trip capacitors are not charged to at least 50 volts a low condition is reporte...

Страница 18: ...ion is enabled The message Relay enabled using default settings is displayed at the top of each menu If the EEPROM failure persists i e if default settings cannot be stored in EEPROM a self test failu...

Страница 19: ...C Curves 5 A primary and 5 of setting Time Overcurrent Response E K Coordinating Tap and Coordinating Main Curves 0 to 10 in terms of current OR 0 to 20 in terms of time OR 0 to 6 ms whichever gives t...

Страница 20: ...rs Terminal numbers are identified by labels on the electronics module or terminal block Trip outputs Electronics module Trip Outputs Terminal Number 1 2 Pole Mating Connector Part Number 1 2 Fault In...

Страница 21: ...Fault Interrupter 2 Pole 1 18 Fault Interrupter 2 Pole 2 19 Fault Interrupter 2 Pole 3 20 Fault Interrupter 2 Residual Power Inputs Terminal Number Power Pole 21 Fault Interrupter 1 Pole 1 22 Fault I...

Страница 22: ...onics module Communication Port Pin Out Electronics Module Pin Function 1 Power in 2 RXD Data In 3 TXD Data Out 4 No connection 5 Signal reference 6 No connection 7 No connection 8 No connection 9 Pow...

Страница 23: ...current control enclosure Pad mounted style shown 2 1 4 5 3 FACE VIEW Data Port Pin Out Control Enclosure Pin Function 1 Power return 2 RXD Data In 3 TXD Data Out 4 Power in 5 Signal reference S C Ins...

Страница 24: ...None Data Bits 8 Stop Bits 1 Flow Control XON XOFF The overcurrent control does not use hardware flow control RTS CTS AcSELerator Quickset SEL 5030 Parameter Setting Device Data Speed 9600 Data Bits...

Страница 25: ...rTerminal Website www hilgraeve com hyperterminal html Note This software is the same software supplied with previous versions of Microsoft Windows It is available for purchase Basic instructions for...

Страница 26: ...nnecting click on the Reconnect button on the toolbar Again this function is located under the Call menu Step 6 To exit this session select File Exit or click on the X button in the upper right hand c...

Страница 27: ...ents Example Referring to the coordination plot in Figure 2 on page 30 a Vista SD switchgear assembly with 600 ampere fault interrupt ers is placed into an electrical system where the upstream protect...

Страница 28: ...rity Characteristic Time s Current kA Maximum Rating 20 15 10 5 0 25 10 5 0 Figure 1 S C Overcurrent Control maximum current rating adjusted for C T saturation Table 1 on page 29 should be used to det...

Страница 29: ...ow the limits shown for the operation of the I2t security characteristic during fault levels up to 14 5 kA The Time Dial setting is below the threshold of 10 0 at a Pickup setting of 1200 amperes If t...

Страница 30: ...U4 Pick Up 880 00 A TD 0 800 0 1 51 Vista 200K fuse 0 01 0 4 1 10 1000 100 10000 Fuse S C SMU20 K 14 4kV Rating 200 0 A 12 47 kV Phase Relay Relay WEST CO 9 Tap Range Tap 0 Pick Up 960 00 A TD 2 CT 6...

Страница 31: ...0 1 00 0 50 6000 5000 3000 2500 1500 1250 600 500 300 250 150 125 60 50 30 25 15 12 5 6 5 3 2 5 100 90 80 40 70 60 50 30 20 10 9 8 4 7 6 5 3 2 1 9 8 4 7 6 5 3 2 1 09 08 04 07 06 05 03 02 01 100 90 80...

Страница 32: ...r Coordinating Main Curves Minimum Pickup Amperes 100 150 200 250 300 350 400 450 500 600 700 800 For Curves U1 U5 and C1 C5 Minimum Pickup Amperes 50 1200 1 A steps Time Dial Multiplier U Curves 0 5...

Страница 33: ...steps For Coordinating Tap and U1 U5 and C1 C5 Curves Definite Time Delay ms 60 Hz OFF 32 48 64 80 96 Definite Time Delay ms 50 Hz OFF 40 60 80 100 120 For Coordinating Main Curves Definite Time Dela...

Страница 34: ......

Отзывы: