Change Relay Settings
The
Change Relay Settings
option allows changes to the TCC curve settings for the selected
fault interrupter. There is a prompt for the input for each setting.
Step 1
After each prompt, enter the new setting and press the
Enter
button. The available choices
are shown in parenthesis. To retain the previous selection shown after the “ = ” , press the
Enter
button.
Step 2
After all of the settings have been entered, the new settings will be displayed in a table.
Enter “Y” for the
Yes
option or “N” for
No
option after the “Save Changes (Y/N)?” prompt. A
confirmation of the choice will be shown and the settings will be displayed. Note that when
new settings are saved, the event report discussed in “View Event Report” on page 10 will be
reset.
<Press ‘Q’ to return to menu>
Phase TCC Curve (E, K, TAP, MAIN, U1, U2, U3, U4, U5, C1, C2, C3, C4, C5) = E ?
tap
Minimum Pickup (Amps) (50, 65, 80, 100, 150, 200, 250, 300, 350, 400) = 50 ?
200
Instantaneous Pickup (kA) (OFF, 0.2, 0.3, 0.4, 0.5, 0.6, 0.7, 0.8, 0.9, 1, 2, 3, 4, 5, 6) = OFF ?
5
DefiniteTime Delay (ms) @ 60Hz (OFF, 32, 48, 64, 80, 96) = OFF ?
32
Ground TCC Curve (OFF, TAP, MAIN) = OFF ?
tap
Minimum Pickup (Amps) (50, 65, 80, 100, 150, 200, 250, 300, 350, 400) = 50 ?
200
Instantaneous Pickup (kA) (OFF, 0.2, 0.3, 0.4, 0.5, 0.6, 0.7, 0.8, 0.9, 1, 2, 3, 4, 5, 6) = OFF ?
1
DefiniteTime Delay (ms) @60Hz (OFF, 32, 48, 64, 80, 96) = OFF ?
32
PHASE
GROUND
TCC Curve Type
TAP
TAP
Min. Pickup (Amperes)
200
200
Inst. Pickup (kA)
5
1
DefiniteTime Delay (ms)
32
32
Save Changes (Y/N)?
y
SETTINGS SAVED
PHASE
GROUND
TCC Curve Type
TAP
TAP
Min. Pickup (Amperes)
200
200
Inst. Pickup (kA)
5
1
DefiniteTime Delay (ms)
32
32
Programming
S&C Instruction Sheet 695-515
13