background image

8    S&C Instruction Sheet 695-505

Safety Precautions

 DANGER

Vista SD Underground Distribution Switchgear operates at high voltage. Failure 

to observe the precautions below will result in serious personal injury or death.
Some of these precautions may differ from your company’s operating procedures and 
rules. Where a discrepancy exists, follow your company’s operating procedures and 
rules.

1. 

QUALIFIED PERSONS. Access to the Vista SD 

underground distribution switchgear must be restricted 
only to qualified persons. See the “Qualified Persons” 
section on page 2.

2. 

SAFETY PROCEDURES. Always follow safe 

operating procedures and rules. Always maintain 
proper clearance from energized components.

3. 

PERSONAL PROTECTIVE EQUIPMENT. Always 

use suitable protective equipment such as rubber 
gloves, rubber mats, hard hats, safety glasses, and 
arc-flash clothing in accordance with safe operating 
procedures and rules.

4. 

DOORS. High-voltage compartment doors must be 

securely closed and latched, with padlocks in place at 
all times unless work is being performed inside the 
enclosure.

5. 

KEY INTERLOCKS. Optional key interlocks, if 

furnished, must be in place. Check the operating 
sequence of key interlocks to verify proper sequencing.  
After the switchgear is installed, destroy all duplicate 
keys or make them accessible only to authorized 
persons so that the key-interlock scheme will not be 
compromised.

6. 

OPENING DOORS. Do not apply any undue force 

when attempting to open a door. The use of undue 
force may damage the door-latching mechanism. 

7. 

SAFETY LABELS. Do not remove or obscure any of 

the “DANGER,” “WARNING,” “CAUTION,” or “NOTICE”  
labels.

8. 

ENERGIZED BUSHINGS. Always assume the 

bushings are energized unless proven otherwise by 
test, by visual evidence of an open-circuit condition at 
the load-interrupter switch or fault interrupter, or by 

observing that the load-interrupter switch or fault 
interrupter is grounded.

9. 

BACKFEED. Bushings, cables, load-interrupter 

switches, and fault interrupters may be energized by 
backfeed.

10. 

GROUNDING. 
•  Vista SD Switchgear must be connected to a 

suitable earth ground before energizing, and at all 
times when energized.

•  The ground wire(s) must be bonded to the system 

neutral, if present. If the system neutral is not 
present, proper precautions must be taken to 
ensure that the local earth ground cannot be 
severed or removed.

•  After the switchgear has been completely 

disconnected from all sources of power and tested 
for voltage, properly ground the load-interrupter 
switches and fault interrupters before touching any 
bushings or components to be inspected, replaced, 
serviced, or repaired.

11. 

LOAD-INTERRUPTER SWITCH OR FAULT 

INTERRUPTER POSITION.
•  Always confirm the open/closed position of the 

load-interrupter switch or fault interrupter by visually  
observing the position of the isolating disconnect.

•  Load-interrupter switch or fault interrupter may be 

energized by backfeed.

•  Load-interrupter switch or fault interrupter may be 

energized in any position.

12. 

MAINTAINING PROPER CLEARANCE. Always 

maintain proper clearance from energized 

 

components.

Содержание Vista SD 101

Страница 1: ...Location of Safety Labels and Tags Single Way Vault Mounted Style 5 Multi Way Vault Mounted Style 6 Pad Mounted Style 7 Safety Precautions 8 Shipping and Handling Packing 9 Inspection 9 Handling 10 I...

Страница 2: ...hey are not intended to be a substitute for adequate training and experience in safety procedures for this type of equipment Read this Instruction Sheet NOTICE Thoroughly and carefully read this instr...

Страница 3: ...d user s claim All other warranties whether express or implied or arising by operation of law course of dealing usage of trade or otherwise are excluded The only warranties are those stated in Price S...

Страница 4: ...cautions are not followed NOTICE NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not followed Following Safety Instructions If...

Страница 5: ...er Circuits and Components Live G 6700 C WARNING Do Not Block Pressure Relief Device not shown G 6742 D WARNING Voltage Tester Always Test for Proper Operation G 9451 Figure 1 Location of safety label...

Страница 6: ...d Components Live G 6700 C WARNING Do Not Block Pressure Relief Device not visible G 6742 D WARNING Voltage Tester Always Test for Proper Operation G 9451 Figure 2 Location of safety labels Model 312...

Страница 7: ...e G 6742 D WARNING Voltage Tester Always Test for Proper Operation G 9451 E WARNING Keep Out Hazardous Voltage Inside G 6398 Figure 3 Location of safety labels Model 422 4 way pad mounted style unit s...

Страница 8: ...attempting to open a door The use of undue force may damage the door latching mechanism 7 SAFETY LABELS Do not remove or obscure any of the DANGER WARNING CAUTION or NOTICE labels 8 ENERGIZED BUSHINGS...

Страница 9: ...ardboard Inspection Examine the shipment for external evidence of damage as soon after receipt as possible preferably before removal from the carrier s conveyance Check the bill of lading to make sure...

Страница 10: ...ble for two way and three way switchgear assemblies See Figure 4 and Figures 5 and 6 on page 11 STEP 2 Arrange the hoist slings to distribute lifting forces equally between the lifting tabs STEP 3 Avo...

Страница 11: ...on Sheet 695 505 11 Shipping and Handling Figure 6 Hoisting a pad mounted style Vista SD switchgear assembly multi way assembly shown Figure 5 Hoisting a multi way vault mounted style Vista SD switchg...

Страница 12: ...es mounted in the horizontal orientation catalog number suffix V3 the clearance between the back of the bus work and the floor of the vault is approximately inch 13 mm Be sure the floor beneath the sw...

Страница 13: ...switchgear assembly is suspended by the hoist slings remove the mounting stand feet STEP 6 Lower the switchgear assembly through the manhole opening STEP 7 Re install the mounting stand feet removed i...

Страница 14: ...lt in damage to the bushings and bushing wells STEP 2 Install cable support brackets in accordance with the appropriate reference drawing included in the installation and operation information kit See...

Страница 15: ...single or multiple connection to realize the maximum momentary rating of the switchgear assembly For a multiple cable connection cables smaller than 1 0 copper or equivalent should not be used STEP 4...

Страница 16: ...og dimensional drawing Make sure the hinged roof section and all doors open and the latch closes without binding Binding indicates enclosure distortion that must be corrected by additional shimming Ac...

Страница 17: ...ee Figure 14 Open door far enough to permit the door holder mechanism to engage automatically STEP 5 To open the left hand door lift the finger latch See Figure 15 Open door far enough to permit the d...

Страница 18: ...tical position is a two person exercise especially on switchgear assemblies having four or more ways NOTICE The hinged roof cannot be placed in the second more vertical position if the hinged roof cou...

Страница 19: ...into the pit horizontally and up to the gear at a 90 angle Failure to follow these precautions can result in damage to the bushings and bushing wells STEP 4 Install cable support brackets in accordanc...

Страница 20: ...re See Figure 18 Then cut the plastic cable ties holding the longer lever arms in the down position STEP 3 At one end of the enclosure pivot the longer lever arm up and position it on the back side of...

Страница 21: ...con tinuous ground bus catalog number suffix O connect the ground bus to the enclosure ground pad Then connect the enclosure ground pad to the system ground in accordance with the user s standard prac...

Страница 22: ...s instruc tions Optional mounting provisions for fault indicators catalog number suffix F1 or F2 are available for Vista SD Underground Distribution Switchgear If mounting provisions are specified mo...

Страница 23: ...ld open mechanism At the other end of the enclosure push up on the hinged roof just enough to allow the left hand hold open mechanism latch to be released ensuring the right hand hold open latching me...

Страница 24: ...es between the cable and the conduit and cap all empty conduits to prevent the entry of moisture and rodents STEP 2 Wipe down the exterior of the enclosure with a clean damp cloth Refinish any scratch...

Страница 25: ...t because the switchgear may be subjected to dc test voltage when connected to the cable The dc withstand test voltages listed in the table are approxi mately equal to the ac test voltage Dc Cable Tes...

Страница 26: ...made after installa tion of the power cable system including terminations and joints but before the cable system is placed in normal service A maintenance test is a field test made during the operati...

Страница 27: ...ging the cable and regrounding the cable Failure to follow these recommendations can result in a flashover injury and equipment damage NOTICE When VLF cable testing has been completed or has been inte...

Отзывы: