56 S&C Instruction Sheet 461-504
Using TripSaver
®
II Service Center Confi guration Software Version 1.8
Select a Fuse Link Curve
The following describes how to select the fuse link curve:
Emulated Device.
Select the
Fuse Link
option from the
Emulated Device
pull-down
menu. See Figure 78.
Figure 78. The Fuse Link option.
A new
Speed
field and an
Ampere Rating
field name will then open. See Figure 79.
Figure 79. The Speed and Ampere Rating fields.
Speed.
Select the fuse link speed from the list in the
Speed
pull-down menu. See Figure 80.
Figure 80. The Speed pull-down menu.
Ampere Rating.
Select fuse link ampere rating from the list. For fuse links, the minimum
trip current is about twice the ampere rating. See Figure 81.
Note:
This fi eld is not active
unless a Speed type for fuse link has been selected. When changing the Speed selection
at any time, all data entered in the
Ampere Rating
pull-down menu and the optional
Advanced TCC Curve Setup
setting will be erased.
Figure 81. The Ampere Rating drop-down menu.
Note:
When the ampere rating has been selected, the curve selection process is com-
pleted, and the test operation can be copied to the clipboard or saved to a setpoint file.
An optional
Advanced TCC Curve Setup
field will also open.