background image

10    S&C Instruction Sheet 1011-540

Control Operation

In addition to the neutral-to-ground potential device, one 
30-Volt-Ampere S&C Potential Device is required to be 
installed on any one of the line phases to obtain a reference 
angle when the 

Unbalance Compensation

 feature is set in 

the 

Cap Only

 setting. During the setup of the 

Unbalance 

Compensation

 feature, a neutral-to-ground voltage 

magnitude sample and a reference angle (Aref) sample 
are used to obtain and store an approximate magnitude 
correction value. See the “Signal Processing” section on 
page 12 for an explanation of how the value is calculated.

Setup of the 

Unbalance Compensation

 feature should 

be accomplished during a time when any voltage unbal-
ances caused by the loads are minimal. During each con-
trol cycle, the stored approximate magnitude correction 
value is subtracted from the real-time neutral-to-ground 
voltage magnitude to obtain a compensated neutral-to-
ground voltage magnitude. Capacitor unit failures will 
cause the real-time neutral-to-ground voltage magnitude 
to change and, therefore, change the compensated neutral-
to-ground voltage magnitude. 

The control compares the compensated neutral-to- 

ground voltage magnitude with the 

Gross Over Voltage 

Level

Lockout Level

, and 

Alarm Level

 setpoint values, if 

enabled. If the compensated neutral-to-ground magnitude 
exceeds a setpoint value continuously for a time greater 
than the applicable 

Time Delay

 setpoint value, the appro-

priate control action is taken. The control will lock out the 
bank if the 

Gross Over Voltage Level 

or the 

Lockout 

Level

 setpoint value is exceeded or issue an alarm if the 

Alarm Level

 setpoint value is exceeded. The 

Cap Only 

value is generally selected when the voltage variations 
between the line phases are expected to be negligible 
in comparison to the neutral-to-ground voltage changes 
resulting from the loss of capacitor units.

In addition to the neutral-to-ground potential device, 

three S&C 30-Volt-Ampere Potential Devices are required 
to be installed on each line phase when the 

Unbalance 

Compensation

 feature is in the 

Cap/Line

 setting. The 

control uses the three potential devices to obtain the 
sum of the line voltages magnitude and a reference angle. 
Because the sum is obtained from all the line voltages, 
compensation for fixed system imbalances is provided. 

During the setup of the 

Unbalance Compensation 

feature, a neutral-to-ground voltage magnitude sample, a 
sum of the line voltages sample, and the reference angle 
are used to calculate and store a magnitude correction 
value. See the “Signal Processing” section on page 12 for 
an explanation of how the value is calculated. During each 
control cycle, the stored magnitude correction factor is 
subtracted from the real-time neutral-to-ground magni-
tude to obtain a compensated neutral-to-ground voltage 
magnitude. Capacitor unit failures will cause the real-time 
line-to-neutral voltage to change and, therefore, change 
the compensated neutral-to-ground voltage magnitude.

The control compares the compensated neutral-to-

ground voltage magnitude to the 

Gross Over Voltage 

Level

Lockout Level

, and 

Alarm Level

 setpoint values, 

if enabled. If the compensated neutral-to-ground voltage 

magnitude exceeds a setpoint value continuously for a 
time greater than the applicable 

Time Delay

 setpoint 

value, the appropriate control action is taken. The control 
will lock out the bank if the 

Gross Over Voltage Level 

or the 

Lockout Level 

setpoint values are exceeded. The 

control will issue an alarm if the 

Alarm Level

 setpoint 

value is exceeded.

For grounded wye banks, the control uses 

Tap Volt-

age Calibration

 logic. This logic develops the sum of the 

intermediate tap-point voltages on the three-phase legs, as 
monitored by the S&C 30-Volt-Ampere Potential Devices. 
A digital filter attenuates harmonics and noise.

When the 

Unbalance Compensation

 feature is dis-

abled, the magnitude of the sum of the intermediate tap-
point-to-neutral voltages is compared (in percent) with the 

Gross Over Voltage Level

Lockout Level

, and 

Alarm 

Level 

setpoint values, if enabled. Capacitor unit failures 

will cause the magnitude of the sum of the intermediate 
tappoint-to-neutral voltages to change. If the real-time 
magnitude of the sum exceeds a setpoint value continu-
ously for a time greater than the applicable 

Time Delay

 

setpoint value, the appropriate control action is taken. The 
Control will lock the bank out if the 

Gross Over Voltage 

Level

 or the 

Lockout Level

  setpoint value is exceeded. 

The control will issue an alarm if the 

Alarm Level 

setpoint 

value is exceeded.

In addition to the three 30-Volt-Ampere Potential 

Devices, one 30-Volt-Ampere S&C Potential Device is 
required to be installed on any one of the line phases to 
obtain a reference angle when the Unbalance Compensa-
tion feature setpoint value is set in the 

Cap Only

 setting. 

During setup of the 

Unbalance Compensation

 feature, 

a sample of the magnitude of the sum of the intermediate 
tap-point-to-neutral voltages and a reference angle sample 
are used to obtain and store an approximate magnitude 
correction value. See the “Signal Processing” section on 
page 12 for an explanation of how the value is calculated. 
Setup of the 

Unbalance Compensation

 feature should be 

accomplished during a time when any voltage unbalances 
caused by the loads are minimal. During each control 
cycle, the stored approximate magnitude correction value 
is subtracted from the magnitude of the real-time interme-
diate tap-point-to-neutral voltages sum. 

Capacitor unit failures will cause the magnitude of the 

real-time tap-point-to-neutral voltages sum to change, and 
therefore, change the magnitude of the compensated tap-
point-to-neutral voltages sum. The control compares the 
compensated intermediate tap-point-to-neutral voltages 
sum magnitude with the 

Gross Over Voltage Level

Lock-

out Level

, and 

Alarm Level 

setpoint values, if enabled. 

If the compensated intermediate tap-point-to-neutral 

magnitude exceeds a setpoint value continuously for a 
time greater than the applicable time delay setpoint value, 
the appropriate control action is taken. The control will 
lockout the bank if the 

Gross Over Voltage Level

 or 

the 

Lockout Level

 setpoint value is exceeded or issue 

an alarm if the 

Alarm Level

 setpoint value is exceeded.

Содержание BankGuard PLUS

Страница 1: ...eplate 5 Control Software 6 SCADA Communication Equipment 6 Control Operation Overvoltage Protection for Capacitor Banks 7 Protection for Reactors 7 Automatic Control Features 8 Ungrounded and Grounde...

Страница 2: ...retrieve and refer to this publication Proper Application WARNING The equipment in this publication is only intended for specific application The application must be within the ratings furnished for...

Страница 3: ...ecautions are not followed NOTICE NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not followed Following Safety Instructions If...

Страница 4: ...ed only to Qualified Persons See the Qualified Persons section on page 2 2 SAFETY PROCEDURES Always follow safe operating procedures and rules Always maintain proper clearance from energized component...

Страница 5: ...essible during regular operation and troubleshooting The BankGuard Plus Control faceplate includes LEDs and buttons for monitoring the capacitor bank reactor and the control It also includes an LCD sc...

Страница 6: ...ck perpetual calendar integrated circuit devices are battery backed and have a 10 year battery life in the Non Powered state The real time clock perpetual calendar integrated circuit counts seconds mi...

Страница 7: ...Figure 2 This curve applies for up to 300 applications of power frequency overvoltages of the magnitude and duration shown The standard further requires that capacitors be capable of continuous opera...

Страница 8: ...than the normal lockout process This logic is activated after a field adjustable time delay of 0 2 to 5 seconds by such faults producing a capacitor bank neutral to ground voltage in excess of an adj...

Страница 9: ...wye banks the control uses an ana log input and digital voltmeter to detect the capacitor bank neutral to ground voltage as monitored by an S C 15 Volt Ampere Potential Device A digital filter attenu...

Страница 10: ...utral to ground voltage magnitude to the Gross Over Voltage Level Lockout Level and Alarm Level setpoint values if enabled If the compensated neutral to ground voltage magnitude exceeds a setpoint val...

Страница 11: ...ded In addition to the neutral to ground potential device one 30 Volt Ampere S C Potential Device is required to be installed on any one of the line phases to obtain a reference angle when the Unbalan...

Страница 12: ...ue continuously for a time greater than the applicable time delay setpoint value the appropriate control action is taken The control will lock out the bank if the Gross Over Voltage Level or the Locko...

Страница 13: ...rovided in addition to capacitor unit manufacturing tolerance Using the Law of Cosines a corrected magnitude is obtained See Figure 8 A cor rected magnitude is calculated and stored in the control s m...

Страница 14: ...g the stored approximate corrected magnitude is subtracted from the real time tap point to ground voltages magnitude in percent during each 200 milliseconds to obtain a compensated neutral to ground v...

Страница 15: ...option STEP 3 In the dialog box select the type of report to generate and then click on the OK button There are four types of reports Full Includes all the information contained in the control System...

Страница 16: ...program files for this for this type of control The extension CFG is added automatically Note This process does not save the Location setting on the Setup screen or the Communications RTU Address set...

Страница 17: ...n the Cancel button to close the Connect dialog box If the IntelliLink software is already run ning choose the Disconnect option from the Connection menu and then choose the Close Screenset option fro...

Страница 18: ...reenset from memory STEP 2 FromtheFilemenu choosetheOpenSnapshot option The Open Controller Data File dialog box opens STEP 3 Select the snapshot desired to use and then click on the Open button STEP...

Страница 19: ...ndows choose Start menu Programs EnergyLine Update The Update window appears Figure 10 b Select the desired options and then click on the Start Update button Note If the control is not connected to CO...

Отзывы: