background image

S&C Instruction Sheet 1011-540    7

Control Operation

This section explains how the BankGuard Plus Controls 
the capacitor bank or reactor.

Overvoltage Protection for Capacitor Banks

Medium to large wye-connected shunt capacitor banks 
commonly use twofold protection against short circuits:
•  Individual capacitor units are protected by fuse links 

that clear internal faults, reducing the probability of 
case ruptures.

•  The system is protected against major faults by the 

bank protective control, such as power fuses or an S&C 
Circuit-Switcher.
If a fuse link operates to isolate a failed capacitor unit, 

the voltage across remaining units in the same series group 
will increase. This increased voltage can overstress and 
shorten the life of the other capacitor units in the group. 
As subsequent units fail, their isolation leads to further 
voltage increase on the remaining units. The result is an 
accelerating cascade of overvoltage that destroys good 
capacitor units.

This phenomenon is addressed in IEEE Standard 

18-1992, “IEEE Standard for Shunt Power Capacitors.” The 
standard specifies a curve that indicates the permissible 
capacitor unit operating time at varying per-unit multiples 
of the capacitor nameplate voltage rating. See Figure 2. 
This curve applies for up to 300 applications of power-

frequency overvoltages of the magnitude and duration 
shown. (The standard further requires that capacitors 
be capable of continuous operation to at least 110% of the 
rated voltage, including harmonics. Most capacitor manu-
facturers publish similar data, which may permit higher 
working voltages.) When the voltage applied to the surviv-
ing capacitor units exceeds the manufacturer’s maximum 
recommended working voltage (or in the absence of a 
recommendation, the IEEE standard), the entire bank 
should be removed from service.

Thus, large-sized capacitor banks require a third form 

of protection: a control sensitive enough to detect the 
isolation of the first failed unit in a capacitor bank but 
sophisticated enough to disregard system and inherent 
bank imbalances, spurious transients, and harmonics. 
Also, the ability to alarm upon isolation of that capacitor 
unit lets the user replace it before additional failures occur.

Protection for Reactors

When a developing turn-to-turn fault occurs in any phase 
winding, the ungrounded, wye-connected shunt reactor 
is protected from further damage by automatic switching 
initiated by the BankGuard Plus Control. The control also 
will isolate and lock out the entire shunt reactor when a 
predetermined neutral-to-ground voltage is exceeded.

Figure 2. Capacitor unit power-frequency overvoltage versus time (IEEE standard 18-1992).

Содержание BankGuard PLUS

Страница 1: ...eplate 5 Control Software 6 SCADA Communication Equipment 6 Control Operation Overvoltage Protection for Capacitor Banks 7 Protection for Reactors 7 Automatic Control Features 8 Ungrounded and Grounde...

Страница 2: ...retrieve and refer to this publication Proper Application WARNING The equipment in this publication is only intended for specific application The application must be within the ratings furnished for...

Страница 3: ...ecautions are not followed NOTICE NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not followed Following Safety Instructions If...

Страница 4: ...ed only to Qualified Persons See the Qualified Persons section on page 2 2 SAFETY PROCEDURES Always follow safe operating procedures and rules Always maintain proper clearance from energized component...

Страница 5: ...essible during regular operation and troubleshooting The BankGuard Plus Control faceplate includes LEDs and buttons for monitoring the capacitor bank reactor and the control It also includes an LCD sc...

Страница 6: ...ck perpetual calendar integrated circuit devices are battery backed and have a 10 year battery life in the Non Powered state The real time clock perpetual calendar integrated circuit counts seconds mi...

Страница 7: ...Figure 2 This curve applies for up to 300 applications of power frequency overvoltages of the magnitude and duration shown The standard further requires that capacitors be capable of continuous opera...

Страница 8: ...than the normal lockout process This logic is activated after a field adjustable time delay of 0 2 to 5 seconds by such faults producing a capacitor bank neutral to ground voltage in excess of an adj...

Страница 9: ...wye banks the control uses an ana log input and digital voltmeter to detect the capacitor bank neutral to ground voltage as monitored by an S C 15 Volt Ampere Potential Device A digital filter attenu...

Страница 10: ...utral to ground voltage magnitude to the Gross Over Voltage Level Lockout Level and Alarm Level setpoint values if enabled If the compensated neutral to ground voltage magnitude exceeds a setpoint val...

Страница 11: ...ded In addition to the neutral to ground potential device one 30 Volt Ampere S C Potential Device is required to be installed on any one of the line phases to obtain a reference angle when the Unbalan...

Страница 12: ...ue continuously for a time greater than the applicable time delay setpoint value the appropriate control action is taken The control will lock out the bank if the Gross Over Voltage Level or the Locko...

Страница 13: ...rovided in addition to capacitor unit manufacturing tolerance Using the Law of Cosines a corrected magnitude is obtained See Figure 8 A cor rected magnitude is calculated and stored in the control s m...

Страница 14: ...g the stored approximate corrected magnitude is subtracted from the real time tap point to ground voltages magnitude in percent during each 200 milliseconds to obtain a compensated neutral to ground v...

Страница 15: ...option STEP 3 In the dialog box select the type of report to generate and then click on the OK button There are four types of reports Full Includes all the information contained in the control System...

Страница 16: ...program files for this for this type of control The extension CFG is added automatically Note This process does not save the Location setting on the Setup screen or the Communications RTU Address set...

Страница 17: ...n the Cancel button to close the Connect dialog box If the IntelliLink software is already run ning choose the Disconnect option from the Connection menu and then choose the Close Screenset option fro...

Страница 18: ...reenset from memory STEP 2 FromtheFilemenu choosetheOpenSnapshot option The Open Controller Data File dialog box opens STEP 3 Select the snapshot desired to use and then click on the Open button STEP...

Страница 19: ...ndows choose Start menu Programs EnergyLine Update The Update window appears Figure 10 b Select the desired options and then click on the Start Update button Note If the control is not connected to CO...

Отзывы: