background image

   S&C Instruction Sheet 1042-511   

11

Installation

STEP 8. 

Enter the information from Step 7 on the 

Setup>Team

 screens.

STEP 9. 

Determine the 

Return to Normal

 mode for each team and enter this information 

on the 

Setup>Team

 screen. 

When the 

Return to Normal

 mode is enabled, team members can return the 

circuit to its normal configuration either automatically once a stable three-phase 
voltage has been restored to the faulted line segment, or by command. For teams 
with one or more tie switches, the 

Open Transition

 mode can be selected (the 

tie switch(es) open before the other team members return the circuit to its normal 
configuration) or the 

Closed Transition

 mode can be selected (the team members 

close all of the switches and then the tie switch(es) open). The 

Return to Normal 

process starts at the line segments closest to the normal source and works outward.

STEP 10. 

Configure the 

RTN Time

 setpoint.

Power must be restored to the faulted line segment for this amount of time (in 

minutes) before the 

Return to Normal

 process will start. Enter this information 

on the 

Setup>Team

 screen.

STEP 11. 

Configure the 

Maximum Capacity

 setpoint for each team member on the 

Setup> 

Team Configuration

 screen.

The maximum capacity is the amount of load on the most limited line section 

(because of conductor size, switch rating, etc.) served through a team member’s loca-
tion from either direction. Each member continuously subtracts its present load from 
its 

Maximum Capacity

 setpoint to determine its 

Local Capacity for Transfer

 value. 

The smallest 

Local Capacity for Transfer

 value encountered in a particular resto-

ration path determines the maximum load that the involved teams can transfer, the  

Available Capacity to Transfer

 value.

STEP 12. 

Configure the 

Alternate Source Sequence

 setpoint on the 

Setup>Team

 screen.

Using the normal switch functionality determined in Step 7, set the sequence 

team members will use to restore the line segment. This is an optional step used to 
guide the restoration process. Regardless of the alternate-source sequence configu-
ration, restoration progresses in the following order: When the fault is downstream 
of the team, the coach will: 1) try the normal source switch, 2) use the 

Alternate 

Source Sequence setting

 (if applicable), 3) try any tie switch(es), and 4) try any 

load-tie switch(es). When the fault is upstream of the team the coach will: 1) use 
the 

Alternate Source Sequence

 setting (if applicable), 2) try any tie switch(es), 

3) try any load-tie switch(es), and 4) try the normal source switch.

STEP 13. 

Determine whether any contracts are required to avoid overloading a line segment.

A bifurcated circuit acting as an alternate source for teams on both legs of the 

bifurcation may become overloaded if those teams must act to restore load at close 
to, or exactly, the same time. This overload may occur because those teams are not 
directly related and do not coordinate their reconfiguration activities.

To force coordination between these unrelated teams, set the 

Contract 

Required

 setpoint to the 

Yes

 state on the 

Setup>Team

 screen for teams that may 

add load to the alternate circuit during a reconfiguration event. The contract will 
prevent both teams from simultaneously closing to use the alternate source. When 
team members encounter a line segment in a restoration path that requires a con-
tract, they will communicate with all subsequent line segments in the direction of 
the alternate source to make sure the source and line segments will not be over-
loaded. The first team contract to arrive at the source will be approved if the team 
load would not overload the circuit. The second arriving contract will be approved 
only if it would also not cause an overload.

The extra communication required to transmit the contracts slows down the 

reconfiguration process. Contracts are described in Instruction Sheet 1042-541, 
“S&C 5800 Series Automatic Switch Controls With IntelliTeam

®

 II Automatic  

Restoration System: 

Operation

.”

Содержание 5800 Series

Страница 1: ...2 Special Warranty Provision 2 Safety Information Understanding Safety Alert Messages 4 Following Safety Instructions 4 Replacement Instructions and Labels 4 Installation Applicable Software 5 Planni...

Страница 2: ...ns of sale as set forth in Price Sheets 150 and 181 applies to the S C 6800 Series Automatic Switch Control except that the first paragraph of the said warranty is replaced by the following 1 General...

Страница 3: ...s applicable instruction sheets This warranty does not apply to major components not of S C manufacture such as batteries and communication devices However S C will assign to the immediate purchaser o...

Страница 4: ...if instructions including recommended precautions are not followed NOTICE NOTICE identifies important procedures or requirements that can result in product or property damage if instructions are not f...

Страница 5: ...trol or in the switch control itself during certain switchgear wiring or grounding system failures or due to a problem with the switch control itself For this reason access to switch controls should b...

Страница 6: ...ion see the About Fault Detection Switch Control Setup Point 6 in Instruction Sheet 1042 531 S C 5800 Series Automatic Switch Controls With IntelliTeam II Automatic Restoration System Setup When confi...

Страница 7: ...that will be part of the IntelliTeam II system Plan the communication system for peer to peer transmission and for data interchange with the SCADA master station if one is used Name the teams 16 chara...

Страница 8: ...nication hardware installation instructions Start IntelliLink software and establish communication between the team member and your computer setup instructions Use IntelliLink software to enter all se...

Страница 9: ...IntelliLink Remote Setup Software Is this the last team that needs to be checked Is each team where this control is a member ready for transfer Make sure all switches are in their normal configuration...

Страница 10: ...STEP 6 NotethenormallyOpen Closedstateforeachteammember Enterthisinformation on the Setup Team screen STEP 7 Createalayoutofthesource s switches andlinesegmentsthatincludestheteams Every switch should...

Страница 11: ...ence team members will use to restore the line segment This is an optional step used to guide the restoration process Regardless of the alternate source sequence configu ration restoration progresses...

Страница 12: ...serial connection is RS232 with a DB9 pin connector If the computer only has USB ports use a serial to USB cable adapter NOTICE S C ships several types of software controlled products Make sure to use...

Страница 13: ...determine which jumper is correct for the distribution system Table 2 Distribution System Jumper Selection 3 Wires Grounding Type Use Uni grounded wye system Delta jumper s 4 Wires Grounding Type Use...

Страница 14: ...terior STEP 6 Check the battery using the following procedure The 5800 Series Switch Control is shipped with a Hawker Gates Monoblock 24 Vdc or 36 Vdc battery The battery is terminated with a connecto...

Страница 15: ...the IntelliLink Software section in Instruction Sheet 1042 530 S C 5800 Series Automatic Switch Control with IntelliTeam Automatic Restoration System Setup STEP 2 If the switch control uses a modem fo...

Страница 16: ...d in pad mounted equip ment and the switch control is only powered from the sensors skip the remainder of this instruction sheet and go directly to Instruction Sheet 1042 530 S C 5800 Series Automatic...

Страница 17: ...ere elevated to primary high voltage Installers must follow the sequence of installation steps outlined in this chapter to ensure a safe and successful switch control installation STEP 3 Configure the...

Страница 18: ...the low voltage compartment as follows 1 Find the four studs on the wall of the low voltage compartment 2 Position the switch control so the four studs align with the four holes in the mounting flange...

Страница 19: ...nication and may optionally communicate with SCADA Installers must toggle the faceplate REMOTE LOCAL switch to the Local position to ensure the switch control does not perform remote switching command...

Страница 20: ...ew battery or the battery was shipped separately install it now WARNING If the enclosure heater was recently on the battery bracket may be hot Be careful not to touch a hot bracket The battery bracket...

Страница 21: ...With the ac line fuse still removed connect the red and black battery leads to the corresponding leads from the switch control This will supply dc voltage to the switch control For Scada Mate Switchin...

Страница 22: ...ts at J2 and J4 See Figure 14 For installations using three voltage sensors and nine current sensors the voltage input should be connected at J3 and the current inputs at J2 J4 and J6 See Figure 14 Ch...

Страница 23: ...ac line fuse is inserted the red AC ON and CHG ON LEDs should illuminate See Figure 13 on page 21 If the AC ON and CHG ON LEDs do not illuminate check the external ac voltage source if applicable The...

Страница 24: ...struction Sheet 1042 550 S C 5800 Series Automatic Switch Control with IntelliTeam Automatic Restoration System Troubleshooting d Check that the LCD screen is backlit and that data are displayed Then...

Страница 25: ...rrecting the error condition continue with Step 6 STEP 5 For S C switches remove the yellow Sensor Calibration sheet that came with the switch There will be a sheet for each set of sensors Put a copy...

Страница 26: ...make sure the communications equipment has power For overhead switch controls the communication equipment is on the back of the faceplate For 5800 Series Switch Controls installed in pad mounted gear...

Страница 27: ...S C Instruction Sheet 1042 511 27 Installation Diagrams...

Страница 28: ...28 S C Instruction Sheet 1042 511 Installation Diagrams...

Страница 29: ...S C Instruction Sheet 1042 511 29 Installation Diagrams...

Страница 30: ...30 S C Instruction Sheet 1042 511 Installation Diagrams...

Страница 31: ...S C Instruction Sheet 1042 511 31 Installation Diagrams...

Страница 32: ...32 S C Instruction Sheet 1042 511 Installation Diagrams...

Страница 33: ...S C Instruction Sheet 1042 511 33 Installation Diagrams...

Страница 34: ...34 S C Instruction Sheet 1042 511 Installation Diagrams...

Страница 35: ...S C Instruction Sheet 1042 511 35 Installation Diagrams...

Страница 36: ...36 S C Instruction Sheet 1042 511 Installation Diagrams...

Страница 37: ...S C Instruction Sheet 1042 511 37 Installation Diagrams...

Страница 38: ...38 S C Instruction Sheet 1042 511 Installation Diagrams...

Отзывы: